Check code Check code name<br />

Cause<br />

[H01] / [1F]<br />

(AI-NET)<br />

Compressor breakdown<br />

Rotor-stop conduction has<br />

occurred.<br />

1. Outdoor unit power line error<br />

2. Compressor circuit system error<br />

3. Compressor error<br />

4. Abnormal overload in operation<br />

5. A3-IPDU P.C. board error<br />

Sub-code:<br />

01: Compressor 1,<br />

02: Compressor 2,<br />

03: Compressor 3<br />

Is power voltage<br />

of outdoor unit<br />

normal?<br />

No<br />

* 380-415V ± 10%<br />

Correct power line.<br />

Yes<br />

Does voltage<br />

drop occur when<br />

other compressor<br />

starts?<br />

Yes<br />

No<br />

Is connection<br />

of wiring or connection of<br />

connector on A3-IPDU P.C.<br />

board normal?<br />

No<br />

Correct connector connection<br />

or wiring.<br />

Yes<br />

Is winding<br />

resistance between<br />

phases of corresponding<br />

compressor normal?<br />

(Note 1)<br />

Yes<br />

No<br />

Take off lead wire of compressor.<br />

1. Check resistance between windings:<br />

It is normal if there are 0.1Ω to 0.4Ω.<br />

2. Check insulation between outdoor cabinet and terminal:<br />

It is normal if there are 10MΩ or more.<br />

Compressor error (Motor<br />

burning, etc.)<br />

Is not it an abnormal<br />

overload?<br />

Yes<br />

Correct cause of overload.<br />

No<br />

Check IPDU P.C. board.<br />

Note 1<br />

After checking the output, when connecting the compressor<br />

lead again to the compressor terminal, check surely there is<br />

no distortion on the Fasten receptacle terminal.<br />

If it is loosened, caulk it with pinchers, etc and then connect<br />

lead to the terminal firmly.<br />

V<br />

W<br />

U<br />

Details of compressor<br />

power connecting section<br />

Check code Check code name<br />

Cause<br />

[F29] / [12]<br />

(AI-NET)<br />

Indoor other error Indoor P.C. board error<br />

This error is detected during operation of air conditioner of IC10 non-volatile memory (EEPROM) on<br />

indoor unit P.C.board. Replace service P.C. board.<br />

* If EEPROM was not inserted when power was turned on or it is absolutely impossible to read/write<br />

EEPROM data, the automatic address mode is repeated. In this case, [97 error] is displayed on AI-NET<br />

central controller.<br />

(Approx. 3 minutes) (Approx. 1 minute)<br />

(Power ON)<br />

[SET DATA]<br />

is displayed<br />

on remote<br />

controller.<br />

[SET DATA]<br />

disappears.<br />

(Repetition)<br />

LED (D02) 1Hz<br />

flashes for approx.<br />

10 seconds on<br />

indoor unit P.C.<br />

board.<br />

Reboot (Reset)<br />

Check code Check code name<br />

Cause<br />

[F31] / [1C]<br />

(AI-NET)<br />

Outdoor EEPROM error 1. Outdoor unit power error (Voltage, noise, etc.)<br />

2. Outdoor I/F P.C. board error<br />

Is there any trouble<br />

of outdoor unit<br />

power supply?<br />

No<br />

Check power voltage and line.<br />

Correct power line.<br />

Check external noise, etc.<br />

Yes<br />

Check I/F P.C. board.<br />