10-3.Work procedure after Repair<br />

When vacuuming in the repaired outdoor unit, follow the procedure described below.<br />

<br />

(1) Fully open PMV1 and 2 and PMV4 (MMY-MAP1404 and MAP1604 only) in accordance with the table below.<br />

Note: PMV full-opening operation via short-circuiting of the CN30 pins is automatically undone after 2 minutes,<br />

causing the valves to fully close. To maintain fully open state, turn off the power switch of the outdoor unit<br />

within 2 minutes of the short-circuiting of the CN30 pins.<br />

SW12<br />

Bit 1 Bit 2 Bit 3 Bit 4<br />

CN30<br />

PMV operation<br />

OFF OFF OFF OFF Short-circuit PMV1 and 2 fully open for 2 minutes.<br />

OFF ON OFF OFF Short-circuit PMV4 fully opens for 2 minutes.<br />

(2) Be sure to perform vacuuming in from the three check joints shown in the diagram below (liquid pipe, discharge<br />

pipe and suction pipe).<br />

M<br />

Right-side<br />

Fan motor<br />

Fan<br />

Main heat exchanger<br />

(TO)<br />

PMV1<br />

PMV2<br />

Right-side sub-heat exchanger<br />

Left-side<br />

PMV4<br />

(TE2)<br />

(TE1)<br />

Main heat exchanger<br />

Left-side sub-heat exchanger<br />

Check valve<br />

Check valve<br />

4-way valve<br />

High-pressure sensor<br />

(TS1)<br />

(SV6)<br />

SV<br />

SV<br />

(TL)<br />

Fusible<br />

plug<br />

(SV3D)<br />

SV<br />

Oil separator<br />

(SV2)<br />

Low-pressure sensor<br />

Liquid tank<br />

(SV41)<br />

SV<br />

SV<br />

(SV42)<br />

SV<br />

Accumulator<br />

(TD1)<br />

Highpressure<br />

(SV3C)<br />

SW<br />

SV<br />

(TD2)<br />

Highpressure<br />

SW<br />

Highpressure<br />

SW<br />

(SV43)<br />

(TD3)<br />

(TK4)<br />

Compressor<br />

1<br />

(Inverter)<br />

Compressor<br />

2<br />

(Inverter)<br />

Compressor<br />

3<br />

(Inverter)<br />

(TK1)<br />

(TK2)<br />

(TK3)<br />

(TK5)<br />

Oil pipe<br />

SV<br />

(SV3E)<br />

SV<br />

(SV3F)<br />

(SV3A)<br />

SV<br />

Check valve<br />

SV<br />

(SV3B)<br />

Check valve<br />

Liquid-side<br />

service valve<br />

Gas-side<br />

service valve<br />

Balance pipe<br />

packed valve<br />

254