Check code Check code name<br />

Cause<br />

[L06] / [96]<br />

(AI-NET)<br />

Duplicated indoor units with priority<br />

(Displayed on the indoor units other than<br />

ones with priority and on the outdoor unit)<br />

Two or more indoor units with priority are duplicated.<br />

Sub-code: ammount of indoor units with priority<br />

When priority is given to two or more indoor units, this check code is displayed on indoor units other than the units<br />

set as prior ones and the outdoor unit.<br />

• As only one indoor unit with priority is valid, change the setup.<br />

Check code Check code name<br />

Cause<br />

[L07] / [99]*<br />

(AI-NET)<br />

A group line exists in an individual<br />

indoor unit<br />

A group line is connected to an individual indoor unit.<br />

Is there group cabling?<br />

Yes<br />

Check the addresses of setup<br />

item code DN 12, 13, and 14.<br />

No<br />

There is individual indoor<br />

unit.<br />

Yes<br />

Correct indoor group address.<br />

No<br />

Check indoor P.C. board.<br />

Failure ➝ Replace<br />

Check code Check code name<br />

Cause<br />

[L03] / [96]<br />

(AI-NET)<br />

Duplicated indoor header units There are two or more indoor header units in a group<br />

during group control.<br />

1) Check whether the connection on remote controllers (group and/or individual) has been changed since the<br />

group configuration and address checking on the remote controllers finished.<br />

2) If the group configuration and address are normal when power has been turned on, the mode automatically<br />

shifts to address setup mode. For setting up addresses again, refer to "Address setup".<br />

Check code Check code name<br />

Cause<br />

[L04] / [96]<br />

(AI-NET)<br />

Duplicated setup of outdoor line<br />

address<br />

Outdoor line addresses are duplicated.<br />

Is there duplicated<br />

line address setup?<br />

Yes<br />

Correct the line address<br />

setup.<br />

No<br />

Are<br />

communication<br />

wire connections of<br />

[U1.U2], [U3.U4], and<br />

[U5, U6] normal?<br />

No<br />

Correct the wire connection.<br />

Yes<br />

Check outdoor I/F P.C. board.<br />

Failure ➝ Replace<br />

Re-set up the address.<br />

(Refer to "Address setup".)<br />

Check code Check code name<br />

Cause<br />

[L05] / [96] (AI-NET)<br />

Duplicated indoor units with priority<br />

(Displayed on indoor unit with<br />

Two or more prior indoor units exist.<br />

priority)<br />

This check code is displayed on the indoor unit set as a prior one when two or more prior indoor units are detected.<br />

• Priority setup with two or more units is not available. As only one indoor unit with priority is valid, change the<br />

setup.<br />

213