Main<br />

remote<br />

controller<br />

Check code<br />

Outdoor 7-segment display<br />

Check<br />

code<br />

Sub-code<br />

AI-NET central<br />

control<br />

remote<br />

controller<br />

F29 – – 12<br />

F31 F31 – 1C<br />

H01<br />

H02<br />

H03<br />

H01<br />

H02<br />

H03<br />

01: Compressor 1<br />

side<br />

02: Compressor 2<br />

side<br />

03: Compressor 3<br />

side<br />

01: Compressor 1<br />

side<br />

02: Compressor 2<br />

side<br />

03: Compressor 3<br />

side<br />

01: Compressor 1<br />

side<br />

02: Compressor 2<br />

side<br />

03: Compressor 3<br />

side<br />

H05 H05 –<br />

*1 Total shutdown in case of header unit<br />

Continued operation in case of follower unit<br />

1F<br />

1d<br />

17<br />

H06 H06 – 20<br />

Location<br />

of<br />

detection<br />

Indoor<br />

unit<br />

I/F<br />

IPDU<br />

IPDU<br />

IPDU<br />

I/F<br />

I/F<br />

Description<br />

Other indoor<br />

error<br />

Outdoor<br />

EEPROM<br />

error<br />

Compressor<br />

breakdown<br />

Compressor<br />

error (lockup)<br />

MG-CTT error<br />

Current<br />

detection<br />

circuit error<br />

TD1 sensor<br />

miswiring<br />

(incomplete<br />

insertion)<br />

Activation of<br />

low-pressure<br />

protection<br />

System<br />

status<br />

Stop of<br />

corresponding<br />

unit<br />

All stop *1<br />

All stop<br />

All stop<br />

All stop<br />

All stop<br />

All stop<br />

Error detection<br />

condition(s)<br />

Indoor P.C. board does not<br />

operate normally.<br />

Outdoor P.C. board (I/F)<br />

does not operate normally.<br />

Inverter current detection<br />

circuit detects overcurrent<br />

and shuts system down.<br />

Overcurrent is detected<br />

several seconds after<br />

startup of inverter<br />

compressor.<br />

Current flow of at least<br />

specified magnitude is<br />

detected despite inverter<br />

compressor having been<br />

shut turned off.<br />

Discharge temperature of<br />

compressor 1 (TD1) does<br />

not increase despite<br />

compressor being in<br />

operation.<br />

Low-pressure Ps sensor<br />

detects operating pressure<br />

lower than 0.02MPa.<br />

Check items (locations)<br />

• Check for defect in indoor P.C.<br />

board (faulty EEPROM)<br />

• Check power supply voltage.<br />

• Check power supply noise.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />

• Check power supply voltage.<br />

(AC200V ± 10%).<br />

• Check for defect in<br />

compressor.<br />

• Check for possible cause of<br />

abnormal overloading.<br />

• Check for defect in outdoor<br />

P.C. board (A3-IPDU).<br />

• Check for defect in<br />

compressor.<br />

• Check power supply voltage.<br />

(AC200V ± 10%).<br />

• Check compressor system<br />

wiring, particularly for open<br />

phase.<br />

• Check connection of<br />

connectors/terminals on A3-<br />

IPDU P.C. board.<br />

• Check conductivity of case<br />

heater.<br />

(Check for refrigerant<br />

entrapment inside<br />

compressor.)<br />

• Check for defect in outdoor<br />

P.C. board (A3-IPDU).<br />

• Check outdoor MG-CTT.<br />

• Check current detection circuit<br />

wiring.<br />

• Check defect in outdoor P.C.<br />

board (A3-IPDU).<br />

• Check installation of TD1<br />

sensor.<br />

• Check connection of TD1<br />

sensor connector and wiring.<br />

• Check resistance<br />

characteristics of TD1 sensor.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />

• Check service valves to<br />

confirm full opening<br />

(both gas and liquid sides).<br />

• Check outdoor PMVs for<br />

clogging (PMV1, 2).<br />

• Check for defect in SV2 or SV4<br />

circuits.<br />

• Check for defect in lowpressure<br />

Ps sensor.<br />

• Check indoor filter for clogging.<br />

• Check valve opening status of<br />

indoor PMV.<br />

• Check refrigerant piping for<br />

clogging.<br />

• Check operation of outdoor fan<br />

(during heating).<br />

• Check for insufficiency in<br />

refrigerant quantity.<br />

MG-CTT: Magnet contactor<br />