MULTI TYPE
MULTI TYPE
MULTI TYPE
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Main<br />
remote<br />
controller<br />
Check code<br />
Outdoor 7-segment display<br />
Check<br />
code<br />
Sub-code<br />
AI-NET central<br />
control<br />
remote<br />
controller<br />
F29 – – 12<br />
F31 F31 – 1C<br />
H01<br />
H02<br />
H03<br />
H01<br />
H02<br />
H03<br />
01: Compressor 1<br />
side<br />
02: Compressor 2<br />
side<br />
03: Compressor 3<br />
side<br />
01: Compressor 1<br />
side<br />
02: Compressor 2<br />
side<br />
03: Compressor 3<br />
side<br />
01: Compressor 1<br />
side<br />
02: Compressor 2<br />
side<br />
03: Compressor 3<br />
side<br />
H05 H05 –<br />
*1 Total shutdown in case of header unit<br />
Continued operation in case of follower unit<br />
1F<br />
1d<br />
17<br />
H06 H06 – 20<br />
Location<br />
of<br />
detection<br />
Indoor<br />
unit<br />
I/F<br />
IPDU<br />
IPDU<br />
IPDU<br />
I/F<br />
I/F<br />
Description<br />
Other indoor<br />
error<br />
Outdoor<br />
EEPROM<br />
error<br />
Compressor<br />
breakdown<br />
Compressor<br />
error (lockup)<br />
MG-CTT error<br />
Current<br />
detection<br />
circuit error<br />
TD1 sensor<br />
miswiring<br />
(incomplete<br />
insertion)<br />
Activation of<br />
low-pressure<br />
protection<br />
System<br />
status<br />
Stop of<br />
corresponding<br />
unit<br />
All stop *1<br />
All stop<br />
All stop<br />
All stop<br />
All stop<br />
All stop<br />
Error detection<br />
condition(s)<br />
Indoor P.C. board does not<br />
operate normally.<br />
Outdoor P.C. board (I/F)<br />
does not operate normally.<br />
Inverter current detection<br />
circuit detects overcurrent<br />
and shuts system down.<br />
Overcurrent is detected<br />
several seconds after<br />
startup of inverter<br />
compressor.<br />
Current flow of at least<br />
specified magnitude is<br />
detected despite inverter<br />
compressor having been<br />
shut turned off.<br />
Discharge temperature of<br />
compressor 1 (TD1) does<br />
not increase despite<br />
compressor being in<br />
operation.<br />
Low-pressure Ps sensor<br />
detects operating pressure<br />
lower than 0.02MPa.<br />
Check items (locations)<br />
• Check for defect in indoor P.C.<br />
board (faulty EEPROM)<br />
• Check power supply voltage.<br />
• Check power supply noise.<br />
• Check for defect in outdoor<br />
P.C. board (I/F).<br />
• Check power supply voltage.<br />
(AC200V ± 10%).<br />
• Check for defect in<br />
compressor.<br />
• Check for possible cause of<br />
abnormal overloading.<br />
• Check for defect in outdoor<br />
P.C. board (A3-IPDU).<br />
• Check for defect in<br />
compressor.<br />
• Check power supply voltage.<br />
(AC200V ± 10%).<br />
• Check compressor system<br />
wiring, particularly for open<br />
phase.<br />
• Check connection of<br />
connectors/terminals on A3-<br />
IPDU P.C. board.<br />
• Check conductivity of case<br />
heater.<br />
(Check for refrigerant<br />
entrapment inside<br />
compressor.)<br />
• Check for defect in outdoor<br />
P.C. board (A3-IPDU).<br />
• Check outdoor MG-CTT.<br />
• Check current detection circuit<br />
wiring.<br />
• Check defect in outdoor P.C.<br />
board (A3-IPDU).<br />
• Check installation of TD1<br />
sensor.<br />
• Check connection of TD1<br />
sensor connector and wiring.<br />
• Check resistance<br />
characteristics of TD1 sensor.<br />
• Check for defect in outdoor<br />
P.C. board (I/F).<br />
• Check service valves to<br />
confirm full opening<br />
(both gas and liquid sides).<br />
• Check outdoor PMVs for<br />
clogging (PMV1, 2).<br />
• Check for defect in SV2 or SV4<br />
circuits.<br />
• Check for defect in lowpressure<br />
Ps sensor.<br />
• Check indoor filter for clogging.<br />
• Check valve opening status of<br />
indoor PMV.<br />
• Check refrigerant piping for<br />
clogging.<br />
• Check operation of outdoor fan<br />
(during heating).<br />
• Check for insufficiency in<br />
refrigerant quantity.<br />
MG-CTT: Magnet contactor<br />
183