(1) Cooling test operation function<br />

This function is provided to change collectively the mode of all the indoor units connected to the same system for<br />

the cooling test operation mode, by using switches on the interface board of the header unit.<br />

<br />

Power ON<br />

Be sure to turn on power at the indoor side<br />

before power-ON of outdoor unit.<br />

Set SW01/SW02/SW03 on the interface P.C. board of the header unit<br />

to [2/5/1]. ([C. ] is displayed on 7-segment display [A].)<br />

Press SW04 on the same board for 2 seconds or more.<br />

Start<br />

[Test run] is displayed on the remote controller of<br />

the indoor unit to be operated.<br />

Check that [ – C] is displayed on 7-segment<br />

display [B] on the interface P.C. board of the<br />

header unit.<br />

[A]<br />

[C. ]<br />

[B]<br />

[ – C]<br />

Operation check<br />

Return SW01/SW02/SW03 on the interface P.C. board of the header<br />

unit to [1/1/1],<br />

or press the push-switch SW05 for 2 seconds or more.<br />

Stop/End<br />

7-segment display [A]<br />

SW04<br />

7-segment display [B]<br />

SW05<br />

NOTE)<br />

SW01 SW02 SW03<br />

<br />

The test operation returns to the normal operation after 60 minutes.<br />

151