Check code Check code name<br />

Cause<br />

[P29] / [16]<br />

(AI-NET)<br />

Compressor position detective<br />

circuit error<br />

1. Wire/connector connection error<br />

2. Compressor error<br />

3. A3-IPDU P.C. board error<br />

Sub-code:<br />

01: Compressor 1, 02: Compressor 2, 03: Compressor 3<br />

Are connector<br />

connection and wiring<br />

normal?<br />

No<br />

Check and correct circuit and<br />

cables such as wiring to<br />

compressor, etc.<br />

Yes<br />

Is the unit grounded?<br />

Yes<br />

Compressor error ➝ Replace<br />

No<br />

Is not winding<br />

shorted? (Is winding<br />

resistance 0.1 to<br />

0.4Ω?)<br />

Yes<br />

Compressor error ➝ Replace<br />

No<br />

Is not winding<br />

opened?<br />

Yes<br />

Compressor error ➝ Replace<br />

No<br />

Check A3-IPDU P.C. board.<br />

Failure ➝ Replace<br />

Check code Check code name<br />

Cause<br />

[P31] / [47]<br />

(AI-NET)<br />

Other indoor error<br />

(Group follower unit error)<br />

Another indoor unit in the group is abnormal.<br />

When the header unit of the group detected error [E03], [L03], [L07] or [L08], the follower unit of the group displays<br />

[P31] error and stops. There are no check code display and alarm record of the main remote controller.<br />

224

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!