Main<br />

remote<br />

controller<br />

Check code<br />

Outdoor 7-segment display<br />

Check<br />

code<br />

Sub-code<br />

AI-NET central<br />

control<br />

remote<br />

controller<br />

Location<br />

of<br />

detection<br />

Description<br />

System status<br />

Error detection<br />

condition(s)<br />

Check items (locations)<br />

H07 H07 – d7<br />

I/F<br />

Low oil level<br />

protection<br />

All stop<br />

Operating compressor<br />

detects continuous state of<br />

low oil level for about 2 hours.<br />

<br />

• Check balance pipe<br />

service valve to confirm full<br />

opening.<br />

• Check connection and<br />

installation of TK1, TK2,<br />

TK3, TK4, and TK5<br />

sensors.<br />

• Check resistance<br />

characteristics of TK1,<br />

TK2, TK3, TK4, and TK5<br />

sensors.<br />

• Check for gas or oil leak in<br />

same line.<br />

• Check for refrigerant<br />

entrapment inside<br />

compressor casing.<br />

• Check SV3A, SV3B,<br />

SV3C, SV3D, SV3E, and<br />

SV3F valves for defect.<br />

• Check oil return circuit of<br />

oil separator for clogging.<br />

• Check oil equalizing circuit<br />

for clogging.<br />

01: TK1 sensor<br />

error<br />

02: TK2 sensor<br />

error<br />

03: TK3 sensor<br />

error<br />

04: TK4 sensor<br />

error<br />

05: TK5 sensor<br />

error<br />

I/F<br />

Error in<br />

temperature<br />

sensor for oil<br />

level detection<br />

All stop<br />

All stop<br />

Sensor resistance is infinity<br />

or zero (open/short circuit).<br />

Sensor resistance is infinity<br />

or zero (open/short circuit).<br />

• Check connection of TK1<br />

sensor connector.<br />

• Check resistance<br />

characteristics of TK1<br />

sensor.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />

• Check connection of TK2<br />

sensor connector.<br />

• Check resistance<br />

characteristics of TK2<br />

sensor.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />

H08<br />

H08<br />

d4<br />

All stop<br />

Sensor resistance is infinity<br />

or zero (open/short circuit).<br />

• Check connection of TK3<br />

sensor connector.<br />

• Check resistance<br />

characteristics of TK3<br />

sensor.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />

All stop<br />

Sensor resistance is infinity<br />

or zero (open/short circuit).<br />

• Check connection of TK4<br />

sensor connector.<br />

• Check resistance<br />

characteristics of TK4<br />

sensor.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />

All stop<br />

Sensor resistance is infinity<br />

or zero (open/short circuit).<br />

• Check connection of TK5<br />

sensor connector.<br />

• Check resistance<br />

characteristics of TK5<br />

sensor.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />

H15 H15 –<br />

I/F<br />

TD2 sensor<br />

miswiring<br />

(incomplete<br />

insertion)<br />

All stop<br />

Air discharge temperature of<br />

(TD2) does not increase<br />

despite compressor 2 being<br />

in operation.<br />

• Check installation of TD2<br />

sensor.<br />

• Check connection of TD2<br />

sensor connector and<br />

wiring.<br />

• Check resistance<br />

characteristics of TD2<br />

sensor.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />