6-4. Test Operation of Indoor Unit<br />

▼ Check function for operation of indoor unit (Functions at indoor unit side)<br />

This function is provided to check the operation of the indoor unit singly without communication with the remote<br />

controller or the outdoor unit. This function can be used regardless of operation or stop of the system.<br />

However, if using this function for a long time, a trouble of the equipment may be caused. Limit using this function<br />

within several minutes.<br />

[How to operate]<br />

1) Short-circuit CHK pin (CN71 on the indoor P.C. board).<br />

The operation mode differs according to the indoor unit status in that time.<br />

Normal time: Both float SW and fan motor are normal.<br />

Abnormal time: Either one of float SW or fan motor is abnormal.<br />

2) Restricted to the normal time, if short-circuiting DISP pin (CN72 on the indoor P.C. board) in addition to<br />

short-circuit of CHK pin (CN71 on the indoor P.C. board), the minimum opening degree (30pls) can be set<br />

to the indoor PMV only.<br />

When open DISP pin, the maximum opening degree (1500pls) can be obtained again.<br />

[How to clear]<br />

Open CHK pin. While the system is operating, it stops once but automatically returns to operation after several<br />

minutes.<br />

DISP pin open<br />

Short-circuit of CHK pin<br />

Normal time<br />

DISP pin short circuit<br />

Abnormal time<br />

Fan motor (H) (H) Stop<br />

Indoor PMV (*) Max. opening degree (1500pls) Min. opening degree (30pls) Min. opening degree (30pls)<br />

Louver Horizontal Horizontal Immediate stop<br />

Drain pump ON ON ON<br />

Communication All ignored All ignored All ignored<br />

P.C. board LED Lights Lights Flashes<br />

• To exchange the indoor PMV coil, set the indoor PMV to Max. opening degree.<br />

• For the detailed positions of CHK pin (CN71 on indoor P.C. board) and DISP pin (CN72 on indoor P.C. board),<br />