DCPL-K4A02<br />

maximum dry density and optimum moisture content (OMC). These<br />

reference values of dry density and moisture content shall be used to<br />

compute the dry density ratio of each of the field density test samples taken<br />

from that test lot.<br />

The degree of compaction shall be determined by considering the mean<br />

density of the samples in each test lot. The mean dry density shall be equal<br />

to or exceed the minimum specified density. In no individual case shall<br />

density be less than the minimum value specified by more than 2 percent,<br />

otherwise further rolling shall be done at the appropriate locations.<br />

The contractor shall lay a further layer or fill only after compaction or a<br />

particular layer has been found and approved by the Engineer.<br />

4.0.0 TESTING AND ACCEPTANCE CRITERIA<br />

4.1.0 Soil Testing<br />

The following tests shall be undertaken by the Contractor and results and<br />

reports shall be submitted to the Engineer for approval. Test failures<br />

are to be immediately notified to the Engineer, otherwise results to be<br />

submitted within 24 hours of testing. Each layer of material shall be tested<br />

for compaction.<br />

Each layer is to be tested in a manner that is representative of its full<br />

depth. The Engineer may at his discretion instruct the Contractor to<br />

increase or decrease the frequency of testing.<br />

a) Minimum one test per 500 cu.m. of soil coming out of the borrow<br />

pits for determination of natural moisture contents in order to<br />

evaluate how far the natural moisture content tallies with the<br />

optimum value and whether further addition or reduction of water<br />

content would be necessary. Test to be done in accordance with IS<br />

: 2720 (Part-II).<br />

b) Minimum two sets of laboratory tests per 8000 cu.m. of soil coming<br />

out of the borrow pits for determination of dry density at optimum<br />

moisture content. Test to be done in accordance with IS : 2720<br />

(Part-VII, XIV, XXVIII, XXIV) as applicable.<br />

c) Minimum two sets of test per 500 cu.m. of loose fill for<br />

determination of moisture content just prior to compaction of area<br />

filling. Test to be done in accordance with IS: 2720 (Part-II).<br />

d) For each compacted layer, minimum one test per 2000 sq.m. of<br />

compacted area for determination of moisture content and dry<br />

density.<br />

(PCA.774.S034sca) V.II-D2/S-I : 18