TITLE:<br />

LIGHTING DISTRIBUTION BOARD<br />

& LIGHTING PANEL<br />

SPEC<strong>IF</strong>ICATION NO. PES-558-01A<br />

VOLUME - II B<br />

SECTION - D<br />

REV.NO. 0 DATE<br />

SHEET 1<br />

OF<br />

3.2.3 Independent gasketted hinged door with operating handle shall be provided for<br />

access to transformer & its taps. Operating handle shall have built-in key locking<br />

arrangement.<br />

3.2.4 Suitable ventilation arrangement for the transformer compartment to dissipate the<br />

heat of the transformer shall be provided. The arrangement shall be in the form of<br />

louvers and the same shall be provided with galvanized wire mesh with dust catchers<br />

on the inside.<br />

3.2.5 The degree of protection for transformer compartment shall be IP:42 unless<br />

mentioned otherwise in Data Sheet A.<br />

3.2.6 Connections between transformer secondary terminals and the busbars shall be<br />

made by using PVC insulated flexible copper cables or busbars.<br />

3.2.7 Warning plate shall be provided on transformer enclosure. The inscription of warning<br />

plate shall be as given below:<br />

- DO NOT OPEN DOORS WHEN ENERGISED<br />

- KEEP TAPS AT SAME POSITION FOR ALL PHASES<br />

3.2.8 Transformer enclosure shall be provided with a danger plate.<br />

3.3 Lighting Transformer<br />

3.3.1 Lighting transformer, where specified shall form an integral part of lighting distribution<br />

board.<br />

3.3.2 Lighting transformer shall be dry type, natural air cooled and suitable for mounting<br />

inside the lighting distribution board. Transformer shall be non-encapsulated type,<br />

unless specified otherwise in Data Sheet A.<br />

3.3.3 Rating of transformer shall be 50 kVA as per type of LDB.<br />

3.3.4 Voltage rating shall be given in Data Sheet A.<br />

3.3.5 Percentage impedance shall be 3% for 50kVA and 4% for 100 kVA transformers,<br />

unless specified otherwise in Data Sheet A.<br />

3.3.6 Off circuit tap changers/links shall be provided for + 5% in steps of 2.5%.<br />

3.3.7 Transformer winding insulation shall be class “F” or better.<br />

3.3.8 Transformer shall be of vector group Dynl.