DCPL-K9A01<br />

3.10.5 All avialion fixtures and accessories shaa be weatherproof, outdoor type<br />

capable of withstanding highly humid and flue-laden almO$phere and generally<br />

conforming to degree of protection IPW-55.<br />

3.10.6 Obstruction lighting system shaU be operated by the Contractor for not less<br />

lhan 60 days. Equipment and work which fails during the test period shall be<br />

repaired or replaced. System performance win be considered satisfactory when<br />

the obstruction rtghting system has operated continuously for a period of at<br />

least sixty (60) days.<br />

3.11.0 Temporary Obstrud:lon lighting<br />

3.11.1 Temporary obstruction lighting shall be provided by the Contractor during<br />

construdlon. Obstruction lights shan be provided at the uppermost part of the<br />

stack or the SUtTOUnding scaffolding as constructiOn proceeds upwants. As<br />

such level spedfied to have permanent obstruction fights Is passed, that level<br />

shall be provided with temporary lighting: For. Temporary obstruction l.ighting.<br />

fixture as per G!§C catalogue "2A750 (l) neon" shaD be used.<br />

3.11.2 Power for operation. of the temporary obstruCtion right shall be obtaineti from<br />

the Construction Power System. Supply circuit for these lights shall be<br />

furnished. installed and maintained by the Contractor.<br />

3.11.3 The temporary ob$Iruction Dghting system shall be operated & maintained by<br />

the Contractor from Sun set to Sun rise. tnl pennanent obstruction Lighting<br />

system is Installed and commissioned.<br />

( 3.11.4 Contractor shall supply six (6) nos. lighting fixtures simftar to the type used by<br />

him for Temporary Obstruction Lighting for Client's use in the event of outage,<br />

if any, of Pennanent Obstruction' lighting fIXtures.<br />

(<br />

3.12.0 Wiring<br />

( 3.12.1 Wires for lightirlg system shaH be PVC insulated. 650 V Ilrade.<br />

l:·"<br />

(.<br />

3.12.2 WIIl!S shall be run in GI conduits suitable for outdOOr installation., Maximum<br />

conduit fill shall be asfollOW$ :<br />

Cable Size<br />

Conduit Size<br />

20 rom 25 mm 32 mm 40 mm 50 Ill'"<br />

If<br />

a) 2.5 Sq. mm Cu 3 5 9<br />

ti<br />

1;', '<br />

...:r<br />

(;<br />

• e<br />

b) 10.0 Sq. mm AI 2 5 7 8<br />

Maximum no. of COJIductors admissible for<br />

conduit<br />

Suitable pull boxes shall be provided at convenient locations.<br />

(PCA.CD.Q03.StlO5CSA24.doc.doc) V.II-D2IS-XXIV: 31<br />