3.5.2 Cement Paint<br />

OCPL-K9AOl<br />

and ihe drying lime between consecutive coals shall not be less than 5 hours.<br />

The overall combined thickness of paint shall be a minimum of 230 microns.<br />

The outside face of the Chimney shall. unless specified othelWise. shall be<br />

painted with Cement water proof paint. The quality shall be approved by the<br />

Engineer. Necessary samples shall be submitted to the Engineer for his<br />

approval. The sUrfece of the shaH shall be prepared as per paint<br />

manufacturer's specjficalion. In addItion. care shall be taken thai the surface<br />

Is free from stain. honey comb and any rough and uneven surface. The joints<br />

between two shuttering and two lifts of shuttering shall be so prepared that<br />

any uneveness. if by chance exists. shall be removed. If one coat of paint Is<br />

not suffICient to give. the required finish. the Contractor sha. repaint the<br />

surfece. until the engineer is satisfjed with the Workmenship. The paint shall<br />

conform, unless othelWise slated, to 15:5410. Necessary samples, test<br />

certificates and manufacturer's literature shall be submitted.to the Engineer<br />

for approval. . .<br />

3.5.3 Insulation and Packing<br />

AU insulation material should be of dimension and type, shown in the drawing.<br />

Load· bearing insulations at supports and side restraints of Steel liners should<br />

be an assembly of M.S. Plates, Stainless Steel Plates, PTFE (Poly Tetra<br />

Fluoro Ethylene) sheets and or/asbestos fibre reinforr.ed boards (SINOANYO<br />

BLOCKS). Insuliltion to be fIXed on outer surface of steel flues should be<br />

mede of glass or mineral wool.<br />

a) load Bearing Insulation Block<br />

~oad bearing assembly should consist of three units and be fabricated<br />

according to approved drawings. It would be fabricated from mild steel<br />

units with a stainless steel sheet bearing plate and load bearing<br />

insulation blocks as indicated in drawing.<br />

The first unit is bolted to the. supporting beam. 11 consists of a M.S.<br />

base plate with bolt holes on which:a ffiachined M.s. 'plate is welded.<br />

This plate IS. provided with receSs.for .PTFE sheet (conf9rming io. BS :<br />

... 5400) to seal. being lubricaled.with sllicbn grease.'<br />

'.<br />

;.<br />

#<br />

The second unit also consists of a M.S. plate having adequate size &<br />

thickness as shown in drawing. While one surface of the plate is<br />

provided with a stainless steel bearing plate the other surface has a<br />

thin layer of lead! elastomeric sheet. The side having stainless steel<br />

surface is placed on PTFE surface of First unit.<br />

The third unit consists of two layers of load bearing insulation blocks<br />

each having a minimum thickness of 50 mm and factory bonded to<br />

top & bottom M.S. plates. These are separated by 100 nnm. long load<br />

bearing insulation dowels as shown in the drawing. These plates are<br />

In tum welded to two additional M.S. plates. Of the two surfaces thus<br />

(PCA.CQ.OO3.SIlO5CSA24.doc.doc) V.iI-02lS-XXIV : 26<br />