12.03.2014 Views

Volume-IF - JantERmantER

Volume-IF - JantERmantER

Volume-IF - JantERmantER

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

iv)<br />

TITLE:<br />

TECHNICAL SPEC<strong>IF</strong>ICATION FOR<br />

REINFORCED CONCRETE<br />

CHIMNEY<br />

SPEC<strong>IF</strong>ICATION NO. PE-TS-360-620-C001<br />

VOLUME - II B<br />

SECTION - C SUBSECTION : I<br />

REV.NO. 0 DATE 18.09.2010<br />

SHEET<br />

OF<br />

The m aterials a nd w orkmanship m ust be of good qua lity a nd a ccepted<br />

standards and specifications.<br />

v) All materials for construction are to be procured by the contractor and should<br />

conform to relevant I.S. specification.<br />

vi)<br />

vii)<br />

viii)<br />

The site Engineer reserves the right to reject a ny material not upt o the<br />

specifications.<br />

Unless specified other otherwise rates quoted under the contractor shall apply<br />

for works irrespective of lifts and leads. R ates shall also. include providing<br />

scaffolding and its subsequent removal.<br />

After completion of the work the buildings and areas around them should be<br />

cleared all rubbish debris etc. and handed over in fit condition for occupation.<br />

12.0 INSULATION<br />

12.1 The heat insulation to be fixed on t he inner surface of shell shall be semi-rigid resin<br />

bonded f ibrous m aterial c onforming t o I S: 819, or e quivalent with a maximum<br />

coefficient of thermal conductivity of 0.52 MW/CM/Deg. C at a mean temperature of<br />

100 deg. C . The Insulation material shall have a delivered density of 100 K g/Cu.M<br />

for resin-bonded rock wool or 64 Kg/Cu.M for resin-bonded glass wool. Thickness of<br />

the insulation as specified in BOQ 's is the minimum as installed.<br />

12.2 No negative tolerance shall be pe rmitted i n t he bul k de nsity of i nsulation. T he<br />

insulation s hall be i n t he f orm of s labs w rapped on t he i nner s urface of shell with<br />

galvanized wire mesh as specified. The insulation should not be affected by acid and<br />

should be free from any impurities which may cause corrosion.<br />

12.3 The i nsulation should be a ble t o s ustain s tructural vi brations a nd s hould not s ettle<br />

under these conditions during erection, construction and operation in any case. The<br />

insulation shall also be suitable tied to prevent dislocation under adverse conditions.<br />

Care sh ould be t aken i n t he s election of t he i nsulation m aterial t o e nsure t hat t he<br />

material can safely withstand the l ong term expos ure to the maximum flue gas<br />

temperature without deterioration or break-down. Slag Wool insulation shall not be<br />

acceptable.<br />

12.4 Unbounded wool shall be of Type–I loose, glass wool in conformance with IS: 3690<br />

or T ype-I l oose r ock W ool i n c onformance W ith I S: 3677. The insulation shall be<br />

packed to achieve a density of 64 Kg/Cu.M in case of glass wool and 100 kg/Cu.M in<br />

case of rock Wool. Bonded and unbonded insulation shall be of the same material.<br />

12.5 The insulation material shall be tested for its stipulated characteristics and properties<br />

listed i n t his s pecification a nd I S : 8183 a nd t he dr awing a ccordance w ith the IS:

Hooray! Your file is uploaded and ready to be published.