DCPL-K4A02<br />

d) The pipe culverts shall be made with proper care regarding the invert<br />

of the pipe, gradient, if any, etc. as specified on drawings and/or as<br />

instructed by the Engineer.<br />

e) Where R.C.C. pipes are encased in concrete at road crossings or at<br />

other places the pipes need be suitably supported avoiding<br />

reinforcements of concrete blocks, joints properly done before<br />

concreting is taken up. Concreting of total height of block may be<br />

done in a single operation or may be done upto some height for<br />

pipes to be properly laid in position and remaining height of block to<br />

be concreted subsequently.<br />

f) The R.C.C. pipes shall be joined with cement mortar. Cement mortar<br />

shall consist of 1 part cement and 2 parts of clean sand with only<br />

enough water for workability. Procedure of jointing shall be as per<br />

IS:783 - latest edition.<br />

3.12.3 Relation with Water Supply Pipeline<br />

Unless specifically cleared by the Engineer, under no circumstances shall<br />

drainage pipes be allowed to come close to water supply pipelines.<br />

3.13.0 Manholes and Inspection Chambers<br />

3.14.0 Masonry<br />

3.14.1 Brick Masonry<br />

The maximum distance between manholes shall be 30 meter unless<br />

specifically permitted otherwise. In addition at every change of alignment,<br />

gradient or diameter there shall be a manhole or inspection chamber. The<br />

distance between manhole or inspection chamber and gully chamber shall<br />

not exceed 6 meters unless permitted otherwise. Manhole shall be<br />

constructed so as to be water-tight under test. The channel or drain at the<br />

bottom of chamber shall be plastered with 1:2 cement sand mortar and<br />

finished smooth to the grade. The channels and drains shall be shaped and<br />

laid to provide smooth flow.<br />

Connection to existing pipelines shall be through a manhole.<br />

Manholes shall be provided with standard covers, usually C.I. or as directed<br />

by the Engineer. The covers shall be close fitting so as to prevent gases<br />

from coming out.<br />

All bricks shall be of first class (Class A) quality, well burnt, of uniform size,<br />

shape and colour free from cracks, flaws or nodules of free lime. Bricks<br />

shall be soaked in water for at least two hours prior to use and shall be laid<br />

truly horizontal and vertical in headers and stretchers with cement mortar<br />

consisting of one part of cement and four parts of sand, unless otherwise<br />

mentioned in the schedule of Items or directed by the Engineer, in<br />

layers not exceeding 1.5 M in height. Each layer shall be allowed at least 24<br />

(PCA.775.S034sca7) V.II-D2/S-VII : 27