TITLE:<br />

LIGHTING DISTRIBUTION BOARD<br />

& LIGHTING PANEL<br />

SPEC<strong>IF</strong>ICATION NO. PES-558-01A<br />

VOLUME - II B<br />

SECTION - D<br />

REV.NO. 0 DATE<br />

SHEET 1<br />

OF<br />

b) The fuse carriers shall be easily withdrawable for replacement of fuse,<br />

Insulated fuse pullers shall be provided where fuses are not mounted in<br />

insulating carriers to remove and replace fuses in live conditions.<br />

c) Fuses shall preferably be fitted with a device to indicate operation (i.e. when<br />

the fuse has blown).<br />

d) Live terminals of fuse bases shall be shrouded to prevent contact with<br />

personnel where fuse links are not mounted in carriers and are directly<br />

plugged into the fuse base. Inter-phase barriers extending throughout the<br />

length of the fuse base shall be provided to prevent inter-phase short circuit.<br />

They shall be shrouded from all sides to prevent accidental contact.<br />

e) Fuse carriers and bases shall be of good quality moulded insulating material.<br />

Porcelain fuse bases and carriers will not be accepted.<br />

3.8 Cable Terminations<br />

3.8.1 All cable, either incoming or outgoing to the LDB, shall be terminated in a cable<br />

chamber. For each panel, there shall be a cable chamber on the side. The door of<br />

cable chamber should open or be locked with the help of a tool. Unless stated<br />

otherwise in Data Sheet A, all cables shall enter from the bottom.<br />

3.8.2 Removable undrilled gland plates of sheet steel shall be provided in the cable<br />

chamber for entry of cables. Minimum thickness of gland plate shall be 3mm. The<br />

gland plate shall be of adequate size for connecting requisite number of cable glands<br />

for power and control cables.<br />

3.8.3 Heavy duty bolt-on termination tinned copper lugs of compression type shall be used<br />

in for power cable termination.<br />

3.8.4 For supporting and clamping of cable cores at regular interval in cable alleys,<br />

suitable slotted angle upto the respective terminal blocks shall be provided.<br />

3.8.5 The supply of tinned copper cable lugs for power cables from part the supply of<br />

equipment.<br />

3.9 Earthing<br />

3.9.1 An earth busbar of adequate size of galvanized MS shall be provided at the bottom<br />

for the entire length of the LDB.