TITLE SPEC<strong>IF</strong>ICATION NO. PES-509-02A<br />

LIGHTNING PROTECTION &EARTHING<br />

OF CHIMNEY<br />

(SUPPLY & INSTALLATION)<br />

VOLUME<br />

II B<br />

SECTION<br />

D<br />

REV NO. 0 DATE 08.02.2002<br />

SHEET 3 OF 4<br />

1.0 GENERAL<br />

1.1 This section includes the design, fabrica tion, supply, installation and testing of<br />

Lightning Protection system for the Chim ney(s). The requirem ents of this specification<br />

shall be complied with in relation to the requirements set out in Data Sheet-A & Section-<br />

C.<br />

1.2 The contractor’s scope, besides m aterial s upply shall include com plete installation of<br />

Lightning Protection System , protective coating application, and testing of the system .<br />

All m aterials, consum ables, erection equipm ent etc. as required for the com pletion of<br />

installation and testing facilities shall be supplied.<br />

2.0 CODES & STANDARDS<br />

2.1 The latest revisions of the following codes & standards shall be applicable:<br />

IS:2309 Code of practice for protection of bu ildings & allied structures against<br />

lightning.<br />

IS:3043 Code of Practice for earthing<br />

IS:4759<br />

Hot-dipped galvanised coating on structural steel<br />

IS:2629<br />

Recommended practice for Hot-dipped galvanising for Iron & Steel.<br />

IS:2633<br />

Methods of Testing Uniformity of Coating on zinc-coated Articles.<br />

IS:1731<br />

Dimensions for Steel flats for structural & General Engineering Purposes.<br />

IS:1752<br />

Electroplated Coatings of Cadmium on Iron & Steel<br />

Indian Electricity Rules, 1956,<br />

Indian Electricity Act, 1960.<br />

IS:4990(Part-I) Criteria for Design of Reinforced concrete Chimney.<br />

3.0 DESIGN REQUIREMENTS<br />

3.1 Lightning Protection system for the chim ney shall consist of air-term ination network<br />

comprising requisite num ber of vertical coppe r rods, 20m m in dia, projecting at least<br />

1000mm above the top of the chim ney and th e flues, spaced uniform ly along the top<br />

periphery of the outer shell of the Chim ney and that of the flues. A ring of 75x6m m GI<br />

strip shall be laid along the top periphery of the flues and the Chim ney, form ing the