TITLE SPEC<strong>IF</strong>ICATION NO. PES-509-02A<br />

LIGHTNING PROTECTION &EARTHING<br />

OF CHIMNEY<br />

(SUPPLY & INSTALLATION)<br />

VOLUME<br />

II B<br />

SECTION<br />

D<br />

REV NO. 0 DATE 08.02.2002<br />

SHEET 3 OF 4<br />

3.14 The com plete lightning protection system arrangem ent including air-term inations,<br />

conductors, connections, fittings etc. and m aterials located on the exterior within 10m<br />

from the top of the chimney shall have lead coating of 2.0mm thickness.<br />

3.15 All exposed m etal structures such as ha nd rails, platform s, ladders/stairs shall be<br />

connected to the downconductors through earthing band rings, of 50x6m m GI strip<br />

located 2000mm above each platform . Ladders and platforms shall be bonded together<br />

for electrical continuity. A strip of 25x3 mm GI shall be used for connection between<br />

equipment and earthing band rings. Similarly, all lighting fixtures shall be earthed.<br />

3.16 Temporary lightning protection system shall have to be provided and m aintained during<br />

the construction of chimney or till f inal lightning protection system is installed by the<br />

contractor free of cost and in line with IS:4998(Part-I).<br />

3.17 For general reference and guidance, Below Ground Earthing Typical Details drg.no.<br />

PE-DG-XXX-509-0004 & drg.no.PE-DG-XXX-509-003 may be used.<br />

4.0 GALVANISING<br />

4.1 All steel strips and m aterials requiring ga lvanisation shall be hot-dip galvanised<br />

according the IS:2629 & IS:4759. Galvanising shall be done at a place where<br />

galvanising and testing facilities conforming to the relevant Indian Standards exist. The<br />

galvanising shall be sm ooth, clean, uniform , continuous & free from acid spots. The<br />

thickness of zinc deposit at any spot shall not be less than 75 m icrons. The purchaser<br />

reserves the right to m easure the thickness of zinc deposit and reject any com ponent<br />

which shows thickness of zinc at any loca tion less than 75 m icrons. Should the<br />

galvanising of the sample be found defective, the entire batch of the steel will have to be<br />

re-galvanised at the seller’s cost.<br />

4.2 All nuts, bolts and washers, wherever used, shall be cadmium coated or zinc passivated,<br />

the thickness of plating conforming to the relevant Indian Standards.<br />

5.0 INSPECTION & TESTING<br />

5.1 The following stages of manufacture/installation shall be stage inspected by purchaser or<br />

his duly authorised representative:<br />

5.1.1 Inspection of all material such as vertical ai r terminals, steel strips, electrodes, test links<br />

including hardware items such as bolts, nuts etc.<br />

5.1.2 Inspection of m anufacturing processes su ch as shearing, punching, beinding, welding,<br />

galvanising, painting etc.<br />

5.1.3 Inspection of installation procedures<br />

The actual inspection will be carried out as per the agreed Quality Plan.<br />

5.2 TESTING<br />

5.2.1 The supplier shall perform all tests nece ssary to ensure that the m aterial and<br />

workmanship conform to relevant standard s and that such tests are adequate to