PEM-6666-0<br />

TITLE SPEC<strong>IF</strong>ICATION NO. PE-TS-360-620-C001<br />

TECHNICAL SPEC<strong>IF</strong>ICATION FOR VOLUME II B<br />

STACK ELEVATOR SECTION C SUB SECTION III<br />

REV 0 DATE<br />

SHEET<br />

OF<br />

Earthing system furnished and installed and include a complete earthing system for the<br />

elevator. Earthing equipment and materials shall be furnished and installed in accordance with<br />

the reference codes and standards these specification and the contractor’s shop drawings as<br />

reviewed and accepted by the Engineer-in-Charge.<br />

b) Materials<br />

The earthing of all electrical items being supplied by the Bidder shall be in his scope. For<br />

earthing the various equipment, conductor sizes shall be as listed below:<br />

i) MCCs Motor above 90 KW : 50 x 6 Sq.mm G.I. flat<br />

ii) Motors above 30 KW, upto<br />

75 KW and lighting panel/<br />

control panels/auxiliary panels : 25 x 6 Sq. mm G.I. flat<br />

iii) Motor above 5 KW upto 30 KW : 25 x 3 mm G.I. flat<br />

iv) Motors upto 5 KW and misc. : 8 SWG GI wire<br />

Small item like conduits,<br />

Junction boxes etc.