TITLE:<br />

LIGHTING NOTES AND DETAILS<br />

LIGHTING NOTES<br />

SPEC<strong>IF</strong>ICATION NO. PES-558-0004<br />

VOLUME - II<br />

SECTION - C Sub Sec -II<br />

REV.NO. 0 DATE<br />

SHEET 1<br />

OF<br />

1.0 These lighting notes and details shall be read and construed in conjunction with the<br />

lighting specifications and drawings<br />

2.0 Contractor shall develop final conduit/cable routings based on fixture location and<br />

other site conditions.<br />

3.0 Unless otherwise shown, the mounting heights of lighting fixtures and accessories<br />

shall generally be as follows.<br />

3.a. Lighting fixture in general areas of powerhouse, miscl. Pump house etc.<br />

3.a.i. Low bay type : 3000 mm to bottom.<br />

3.a.ii. Medium bay type : bet 3500 mm to 8000 mm to bottom.<br />

3.a.iii. High bay type : above 8000mm to bottom.<br />

3.b. Bracket lights over door opening : 300 mm bot of fixture above opening.<br />

3.c. Receptacles<br />

3.c.i. In control room office : 450 mm floor to center.<br />

3.c.ii. Elsewhere : 900 mm floor to center.<br />

3.d. Local switches<br />

: 1500 mm floor to center<br />

3.e. Lighting panels<br />

: 1800 mm floor to top<br />

4.0 All outdoor illumination fixtures unless it fed from photocell/tank-switch controlled<br />

lighting panel shall be provided with outdoor type local switches.<br />

5.0 Separate neutral wire shall be provided for each circuit. Wiring throughout the<br />

installation shall be such that there is no break in the neutral wire in the form of switch<br />

or fuse.