TITLE:<br />

TECHNICAL SPEC<strong>IF</strong>ICATION FOR<br />

REINFORCED CONCRETE<br />

CHIMNEY<br />

SPEC<strong>IF</strong>ICATION NO. PE-TS-360-620-C001<br />

VOLUME - II B<br />

SECTION - C SUBSECTION : I<br />

REV.NO. 0 DATE 18.09.2010<br />

SHEET<br />

OF<br />

1.0 BRIEF DESCRIPTION<br />

.<br />

The chimney will be single flue reinforced concrete structure of 220 m etres height.<br />

Flue will have first class acid/heat proof firebrick lining. This brick lining work will<br />

be supported on internal RCC corbels at 10 M etres i nterval. A part f rom a viation<br />

warning l ight, c omplete e xternal s urface of t he w indshield s hall be pa inted i n<br />

alternate band of signal red and white colour starting with signal red colour at the top<br />

and i n l ine w ith a viation r equirements. E xternal pa inting s hall ha ve acid and heat<br />

resisting properties c onfirming to IS-158, t otal dr y t hickness(DFT) sha ll be atleast<br />

150 microns. Platforms on e xternal s urface of R CC w indshield w ith pr ovision of<br />

personnel access sha ll be provi ded at maximum twenty-five (25) m etre int erval.<br />

Suitable personnel access door and truck entry door shall be provided. The top of roof<br />

slab and top of acid resistant bricks over the roof shall be painted with two coats of<br />

‘EXPILUX 5 COAL T AR E POXY P AINT’ ove r a t hin coat of t he same paint as<br />

manufactured by M/s. Berger P aints ( India). The ove rall D FT sha ll be at l east 230<br />

microns. RCC hoppe r s hall be pr ovided a t bot tom l evel. A rrangement shall be<br />

provided for measuring concentration of particulate matters. NO X AND SO X in the<br />

flue gas for monitoring and taking necessary measure for pollution control. It will also<br />

have necessary arrangement for earthing during construction. Access from ground to<br />

external platforms shall be provided with cage ladder.<br />

The grade level slab shall be of r einforced c oncrete w ith a n i ronite f inish. T he<br />

chimney shall have a suitable foundation system depending upon soil characteristics.<br />

Apart from aviation warning light, the complete external surface of the wind shield<br />

shall be painted in alternate band of red and white colour and in line with aviation<br />

requirements, out of which the top 50 metre of paint shall have acid and heat resistant<br />

properties and rest of the surface shall be painted with water proof cement paint or<br />

synthetic enamel paint.<br />

The c himney r oof s lab if re quired shall be of r einforced concrete t reated for w ater<br />

proofing and protected by a layer of acid resistant tiles laid in acid resistant mortar.<br />

Suitable personnel access door and truck entry door shall be provided. A personnel<br />

access hatch in the of slab, liner access hatches, rain water drainage system, flue acid<br />

drainage, bird screens or louvers on the ventilation openings shall also be provided.<br />

Arrangement shall be provided for m easuring c oncentration of pa rticulate m atters,<br />

Nox & Sox in the flue gas for monitoring and taking necessary measure for pollution<br />

control. It w ill a lso have necessary arrangement f or el ectrical pow er suppl y ,<br />

distribution boards, socket outlets, power and control cabling raceways system, stair<br />

and platform lighting, lightening protection and earthing system.<br />

Stack elevator will be provided to run along outside surface of wind shield.