TITLE:<br />

LIGHTING DISTRIBUTION BOARD<br />

& LIGHTING PANEL<br />

3.0 LIGHTING DISTRIBUTION BOARDS<br />

SPEC<strong>IF</strong>ICATION NO. PES-558-01A<br />

VOLUME - II B<br />

SECTION - D<br />

REV.NO. 0 DATE<br />

SHEET 1<br />

OF<br />

3.1 Sheet thickness : 2.0 mm<br />

3.2 Degree of protection :<br />

a) Main panel : IP 54<br />

b) Transformer cubicle : IP 33<br />

3.3 Type of Incomer : Switch-Fuse<br />

3.4 Type of Outgoing Feeders : Switch-Fuse<br />

3.5 Voltage rating of transformer : 415 V<br />

3.6 Whether transformer is encapsulated: No<br />

3.7 Transformer impedance<br />

a) 100 kVA : - %<br />

b) 50 kVA : 4.0 %<br />

3.8 Bus bar material : Aluminium<br />

3.9 Earth busbar material : GI (50X6 mm)<br />

3.10 Cable entry : Bottom<br />

3.11 Whether under voltage relay : Not applicable<br />

required in DC LDB<br />

4.0 LIGHTING PANEL<br />

4.1 Application : Both Indoor & outdoor<br />

4.2 Sheet thickness : 2.0 mm<br />

4.3 Degree of protection<br />

a) Indoor : IP : 54<br />

b) Outdoor : IP : 55<br />

(weather-proof<br />

protection with canopy)<br />

4.4 Type of Incomer : Switch-Fuse<br />

4.5 No. of poles for Aviation lighting : 1 / 3<br />

panel MCBs