DCPL-K4A02<br />

VOLUME : II-D/2<br />

SECTION-XI<br />

TECHNICAL SPEC<strong>IF</strong>ICATION<br />

FOR<br />

FALSE FLOORING<br />

1.0.0 SCOPE<br />

This specification covers supplying, installation, repairing, finishing, testing,<br />

protection and maintenance till handing over of removable free access false<br />

flooring systems consisting of an assembly of panels mounted on adjustable<br />

pedestal and supporting steel grid system to provide an under floor space.<br />

2.0.0 FALSE FLOORING SYSTEM<br />

2.1.0 Base<br />

The system shall be placed over a base of R.C.C. floor slab and with<br />

necessary grouting etc. to fix the supporting structure.<br />

2.2.0 Supporting Structure<br />

2.3.0 Floor Panel<br />

The supporting structure shall comprise of fabricated jacks made out of 25<br />

mm. dia. MS rounds having 150 mm. threads at top. This jack shall be<br />

welded to 100 mm x 100 mm x 6 mm thick MS base plate pedestal.<br />

Pedestals shall be vertically true and located at 600 mm centre to centre to<br />

conform to the size of the floor panels and shall be fixed to the RCC floor slab<br />

with ARALDITE. The jack shall be equipped with locking device to prevent<br />

loss of finished elevation. Adjustment shall be provided by the threaded rod<br />

member and elevating nut. The capital shall be of aluminium alloy die cast<br />

and shall receive cold rolled MS floor supporting channels of size 40 mm x 40<br />

mm x 3.15 mm thickness as per drawings, both for main and cross runners.<br />

The pedestal shall be equipped with conducting grounding pad. All MS<br />

members shall be treated with steel protective paint as per drawing.<br />

2.3.1 The floor panels shall be made of phenol for maldehyde bonded particle<br />

board treated with fire resistant paint as per schedule items. Size of each<br />

panel shall be 600 mm x 600 mm with all panel edges finished to a tolerance<br />

of + 0.25 mm on the diagonals. The edges of the floor panels shall be<br />

covered by 4 mm. thick rigid PVC edging. The underside of the panel shall<br />

have 0.05 mm. thick Aluminium foil which shall be fixed to the particle board<br />

with resin-based adhesive.<br />

(PCA.775.S034sc11) V.II-D2/S-XI : 1