TITLE SPEC<strong>IF</strong>ICATION NO. PE-TS-360-620-C001<br />

TECHNICAL SPEC<strong>IF</strong>ICATION FOR<br />

VOLUME: IIB<br />

STACK ELEVATOR<br />

SECTION C<br />

REV 0 DATE<br />

SHEET<br />

OF<br />

Damaged earth system conductors or cables shall be repaired or replaced by the Contractor as<br />

directly by the Engineer-in-Charge.<br />

Earth connections except equipment earthing connections shall be made by electric arc<br />

welding. Bolted connections shall be used for earthing equipment.<br />

Earthing bushings within all enclosures, including equipment enclosure, shall be wired together<br />

and connected internally to the enclosure earthing lug at earthing bus with bare conductor.<br />

Electrical equipment shall be earthed. Large equipment will be furnished with a earthing bus.<br />

Most other equipment will be furnished with earthing pads and/or earthing lugs. Earthing<br />

connection surfaces shall be cleaned immediately prior to connection. Contractor shall provide<br />

all earthing material required but not furnished with the equipment. Where the earth conductor<br />

is included with the power conductors in the motor circuit raceway a compression type earth<br />

conductor termination shall be used and connected to the motor frame inside the motor<br />

terminal housing. Where the earth conductor is not included with the power conductors in the<br />

motor circuit raceway, the motor frame shall be earthed to the earth grid.<br />

Suitable earthing facilities acceptable to the Engineer-in-Charge shall be furnished on motors<br />

not so equipped. Earthing facilities shall consist of compression type earth conductor<br />

termination bolted to the motor frame and providing a minimum of joint resistance. Conduit<br />

system is not considered to be a earthing conductor. No earthing conductor shall be smaller in<br />

size than 4 Sq. mm unless it is a part of an acceptance cable assembly.<br />

7.00.0 INSPECTION AND TESTING<br />

7.01.0 The following specific test as applicable shall be carried out by the Contractor as minimum<br />

requirement for the elevators.<br />

7.01.01 All materials used in manufacture of various components shall be of tested quality<br />

and shall conform to relevant standards / specifications.<br />

7.01.02 All welding shall be carried out as per welding procedures qualified as per ASME<br />

Section-IX. Welding procedures shall be forwarded for approval. Only welders<br />

qualified as per ASWME Section-IX shall be employed for welding.<br />

7.01.03 All NOT operators should be qualified as per SNT-TC-IA.<br />

7.01.04 All forgings shall be subjected to ultrasonic test to ensure free from internal defects.<br />

7.01.05 All welds shall be subjected to dye-penetration test and visual examination.<br />

7.01.06 All forged components shall be subjected to DP/MPI after machining.