LIGHTING DISTRIBUTION BOARD<br />

& LIGHTING PANEL<br />

SPEC<strong>IF</strong>ICATION NO. PES-558-01A<br />

VOLUME - II B<br />

SECTION - D<br />

REV.NO. 0 DATE<br />

SHEET 1<br />

OF<br />

1.0 SYSTEM DESIGN DATA<br />

1.1 Design Ambient : 50 Deg.C<br />

1.2 Relative humidity :<br />

a) Average : As per project synopsis<br />

b) Maximum : -do-<br />

1.3 Details of Operating parameters<br />

a) AC Supply<br />

i. Rated voltage : 415 V<br />

ii. Rated frequency : 50 Hz<br />

iii. Voltage variation : + 10 %<br />

(Permissible)<br />

iv. Frequency variation : + 5 %<br />

(Premissible)<br />

v. Combined voltage & : 10%<br />

Frequency variation<br />

(sum of absolutes<br />

permissible)<br />

vi. System fault level : 50 kA for 0.25 sec.<br />

At rated voltage<br />

vii. System grounding : Solidly<br />

b) DC Supply Not applicable<br />

i. Rated voltage : V<br />

ii. Voltage variation : %<br />

(Permissible)<br />

iii. System fault level :<br />

at rated voltage<br />

c) AC Emergency luminaries : Not applicable %<br />

as per percentage of total luminaries<br />

2.0 APPLICABLE STANDARDS : As per Annexure I