MLC <strong>Maintenance</strong> -- C,S Bits and Register<br />

4.8 MLC Initial Setting Description(PLCIO.CFG)<br />

In <strong>LNC</strong>MILL\MACHINE, file name is PLCIO.CFG, this file is to set MLC I/O configuration<br />

and definition, file content is as following:<br />

InputSignalInverse=0 // I point is reverse turning, 0=No , 1=Yes<br />

OutputSignalInverse=0 // O point is reverse turning, 0=No , 1=Yes<br />

BaseAddress=0x200 // pcc1620 base address<br />

Set1Slave1=1<br />

// whether to use Set1’s Slave1, 0=No, 1=Yes<br />

Set1Slave2=0<br />

// whether to use Set1’s Slave2, 0=No, 1=Yes<br />

Set2Slave1=1<br />

// whether to use Set2’s Slave1, 0=No, 1=Yes<br />

Set2Slave2=0<br />

// whether to use Set2’s Slave2, 0=No, 1=Yes<br />

I 0 1 0x200 // column [I or O][NUMBER][SET][ADDRESS][able to add footnot]<br />

I 8 1 0x201 // no empty space in between<br />

I 16 1 0x202 // I or i is okay<br />

I 24 1 0x203 // O or o is okay<br />

I 32 1 0x204 // SET=1means SET1, SET=2 means SET2<br />

I 40 2 0x200 // must starts from I0<br />

O 0 1 0x200 // due to EPCIO factor, O point must be set as even number.<br />

O 16 1 0x202<br />

O 32 2 0x200<br />

O 48 2 0x202<br />

(Note)I 0 1 0x200<br />

Means the corresponding hardware address (the following explains how to set)<br />

I0 ~ I15 to hardware SET1<br />

means LADDER configures from I0 ~ I15<br />

124 <strong>LNC</strong> Technology Co., Ltd.