12.07.2015 Views

Specifications - City of Montpelier, Vermont

Specifications - City of Montpelier, Vermont

Specifications - City of Montpelier, Vermont

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Title:<strong>Montpelier</strong> District Heating<strong>City</strong> <strong>of</strong> <strong>Montpelier</strong>, VT15030 – Electrical Requirements for Mechanical EquipmentIssue Date:September 28, 2012Page #:6 <strong>of</strong> 6E. Motor connections: Flexible conduit, except where plugin electrical cords arespecifically indicated.2.3 DISCONNECT SWITCHESA. Fusible switches: Fused, each phase; general duty; horsepower rated; quickmake/ quickbreak mechanism; dead front line side shield; solderless lugs suitable forcopper or aluminum conductors; spring reinforced fuse clips; electro silver platedcurrent carrying parts; hinged doors; operating lever arranged for locking in the"OPEN" position; arc quenchers; capacity and characteristics as required.B. Nonfusible switches: For equipment 2 horsepower and smaller, shall behorsepower rated; toggle switch type; quantity <strong>of</strong> poles and voltage rating asrequired. For equipment larger than 2 horsepower, switches shall be the same asfusible type.PART 3 EXECUTION (Not Applicable)END OF SECTION 15030ELECTRICAL REQUIREMENTS FOR MECHANICAL EQUIPMENT150306