Title:16110 – Raceways<strong>Montpelier</strong> District Heating<strong>City</strong> <strong>of</strong> <strong>Montpelier</strong>, VTIssue Date:September 28, 2012Page #:3 <strong>of</strong> 102. Conduit Bodies:a. AdaletPLMb. Appleton Electric Co.c. CrouseHinds Division, Cooper Industries, Inc.d. Killark Electric Mfg. Co.e. OZ/Gedneyf. Spring <strong>City</strong> Electrical Mfg. Co.3. Wireway:a. Anchor Electric Co.b. Circle AW Products.c. Cross Brothers, Inc.d. Erickson Electric Equipment Co.e. GS Metals Corp.f. H<strong>of</strong>fman Engineering Co.g. Square D Co.4. Surface Raceway:a. Carlon, Inc.b. Hubbell Co.c. The Wiremold Co.2.2 METAL CONDUIT AND TUBINGA. General: Minimum conduit size shall be 1/2" for interior installation and 3/4" forexterior underground installations.B. Rigid Aluminum Conduit: ANSI C80.5.C. Rigid Steel Conduit: ANSI C80.1.D. Intermediate Steel Conduit: UL 1242.E. PVC Externally Coated Rigid Steel Conduit: ANSI C80.1 and NEMA RN 1.F. Electrical Metallic Tubing: ANSI C80.3.G. Flexible Metal Conduit: UL 1, zinccoated steel.RACEWAYS161103