Drive modules<br />

3.<br />

DRIVE MODULES<br />

Modular drives<br />

188<br />

DDS<br />

HARDWARE<br />

Ref.1307<br />

100<br />

Load duty cycles<br />

Load cycle S1<br />

Continuous duty. Operation with constant load and long enough to achieve<br />

thermal balance.<br />

IS1<br />

F. H3/4<br />

Load cycle S1.<br />

Load cycle S1 with current peak<br />

Periodic intermittent duty. Succession of identical duty cycles each having<br />

a period at constant maximum load and a period at constant rated load. In<br />

this duty cycle, the overheating effect of the start-up current is negligible.<br />

The 5% running factor means that for a 10 second cycle, it works at constant<br />

current Imax (2xInom) for 0.5 seconds and at rated current (Inom) for 9.5<br />

seconds.<br />

Imax<br />

IN<br />

F. H3/5<br />

Load cycle S1 with current peak Imax.<br />

Load cycle S6-40<br />

Periodic uninterrupted duty cycle with intermittent load. Succession of<br />

identical duty cycles, each with a running period under constant load and<br />

another period without load. There is no rest period. The 40% running factor<br />

indicates that for a 10 minute cycle, it works at constant current for 4 minutes<br />

(I S6 -40%) and without load for 6 minutes (with magnetizing current = 0.7 x<br />

rated current In).<br />

IS6-40<br />

IN<br />

0.7·IN<br />

F. H3/6<br />

Load cycle S6-40.<br />

I<br />

I<br />

I<br />

0.5 s<br />

10 s<br />

10 min<br />

4 min<br />

Load cycle S1<br />

S1 cycle with Imax<br />

current peak<br />

Load cycle S6-40<br />

t<br />

t<br />

t