WARNING. Before handling these leads, proceed in the following order:<br />

• Stop the motors<br />

• Disconnect the mains voltage at the electrical cabinet.<br />

• Wait, before handling these leads. The power supply module needs<br />

time to decrease the voltage of the power bus down to safe values<br />

(< 42 V DC). The green indicator DC BUS ON being turned OFF does<br />

not mean that the power bus may be handled or manipulated.<br />

• The discharge time depends on the number of elements connected<br />

and it is about 4 minutes.<br />

WARNING. Never connect in parallel the power buses of different power<br />

supplies.<br />

MANDATORY. Install an auxiliary power supply APS-24 (24 V DC, 10 A)<br />

to the DC bus of any DDS system with non-regenerative power supply<br />

PS-65A (mandatory) or PS-25B4 (suggested, not mandatory).<br />

INFORMATION. Do not install external protection fuses in these power<br />

lines of the auxiliary power supply. They are already integrated in the<br />

power supply itself.<br />

Remember that the purpose of connecting an auxiliary power supply APS-<br />

24 to the DC bus of a DDS system is to ensure the supply to all the control<br />

circuits of the power supply and of the drive modules connected to the<br />

DC bus in case of a mains power outage in the auxiliary power supply ensuring<br />

a controlled stop of the moving axes instead of braking out of control<br />

by friction.<br />

Bear in mind that the PS-65A power supplies do not come with internal<br />

auxiliary power supply for their own control circuits and for those of the<br />

modules connected to the DC bus as well as other elements like fans, etc.<br />

That is why it is a must to install the APS-24 auxiliary power supply to do<br />

the installation properly.<br />

PS-25B4 power supplies do come with an internal auxiliary power supply<br />

(24 V DC and a total of 8 A, 192 W). Therefore, it is not a must to install<br />

an APS-24 next to them, but it is highly suggested because, sometimes,<br />

higher power may be required to feed the control circuits of the modules<br />

than what the internal auxiliary power supply can provide (when installing<br />

a lot of drive modules).<br />

Observe that the APS-24 auxiliary power supply offers 3 outputs with 24 V<br />

DC and a total of 10 A, 240 W.<br />

For further information about the auxiliary module APS-24, see chapter 4.<br />

AUXILIARY MODULES in this manual.<br />

Power supplies<br />

POWER SUPPLIES<br />

Non-regenerative power supplies 2.<br />

DDS<br />

HARDWARE<br />

Ref.1307<br />

45