Ground connection<br />

MANDATORY. It is up to the system integrator to meet all the requirements<br />

of local and national electrical codes as well as all the regulations<br />

applicable regarding the grounding of the whole unit.<br />

The chassis of each modules must be connected to a single point and from<br />

there to the ground terminal of the electrical cabinet. When applying a 10 A<br />

current between this ground point and any of these points, the voltage drop<br />

must not exceed 1 V. Use the washers and nuts supplied with each module<br />

to make the ground connection.<br />

When not having a separate ground point, join the plates to the terminal of<br />

the power supply module which, in turn, will be connected to mains ground.<br />

F. H8/10<br />

Ground connection.<br />

The tightening torque must be between 2.32.8 Nm.<br />

MANDATORY. Take a ground cable (as short as possible) from each module<br />

to each main machine ground point.<br />

MANDATORY. In order to ensure compliance with the European Directive<br />

on Electromagnetic Compatibility 2004/108/EC, it is a must to:<br />

• Verify that all the requirements of local and national electrical codes are<br />

met as well as all the regulations applicable regarding the grounding of<br />

the whole unit.<br />

• Power the system through “MAINS FILTER A”.<br />

• Secure the filter onto a metallic support with a good contact on its<br />

whole base, good ground connection and as close to the power supply<br />

as possible.<br />

• Make all the ground connections indicated in the figure F. H8/10 with a<br />

cable having a section equal to or greater than the three-phase power<br />

supply and at least 6 mm².<br />

• Always use shielded cables for three-phase motor connections. See<br />

chapter 7. CABLES.<br />

Installation<br />

INSTALLATION<br />

Connection between modules 8.<br />

DDS<br />

HARDWARE<br />

Ref.1307<br />