Power supplies<br />

2.<br />

POWER SUPPLIES<br />

94<br />

80<br />

Regenerative regulated power supplies<br />

DDS<br />

HARDWARE<br />

Ref.1307<br />

i<br />

Power connectors<br />

Terminal strip for mains connection<br />

This connector may be used to connect the power supply to mains. When<br />

connecting the power suppliy to mains, the phases may be connected in<br />

any order RST, RTS, TRS, etc.<br />

N<br />

From mains<br />

S T R<br />

u1 v1 w1<br />

u2<br />

v2<br />

L1<br />

L2<br />

L3<br />

L1 L2 L3<br />

w2<br />

1.<br />

2<br />

)<br />

MPC - 4x ... (mm2 )<br />

F. H2/41<br />

Terminal strip for connection to mains.<br />

The RST phases may be connected in any sequence<br />

at the power connector.<br />

Important note: Make sure that the phase sequence<br />

matches the one at the line voltage input connector.<br />

Choke RPS-XX<br />

Cable without connectors<br />

POWER CONNECTOR<br />

L1 L2 L3<br />

The ground connection of the cable shield is made from the vertical plate<br />

(A) next to the terminal strip. See figure F. H2/41.<br />

The following table shows the values for gap, tightening torque, sections<br />

and other interesting data of the power feed-through terminal blocks:<br />

T. H2/29 Technical data of the feed-through terminal blocks for mains<br />

connection.<br />

Connector data<br />

RPS-80<br />

RPS-75<br />

RPS-45 RPS-20<br />

Gap (mm) - - 10.16<br />

Min/max tightening torque (N·m) 15/20 6/8 1.2/1.5<br />

Screw thread M8 M6 M4<br />

Min./max. section (mm²) 35/95 16/50 0.75/10<br />

Rated current In (A)<br />

Wire data<br />

232 125 41<br />

Length to strip (mm) 27 24 12<br />

(A)<br />

This detail represents the terminal<br />

strip for connecting the RPS-<br />

80 power supply to mains.<br />

MANDATORY. As for possible high leak currents, use a protection ground<br />

wire with a cross section of at least 10 mm² (Cu) or 16mm² (Al) or two<br />

protection ground wires with the same cross section as that of the wires<br />

connected to the power supply terminals. Comply with local regulations on<br />

grounding.<br />

INFORMATION. IGBT components cannot actually be protected with fuses.<br />

Therefore, installing protection fuses when using RPS power supplies<br />

does not prevent a failure of the module, but it does minimize the number of<br />

components that may be destroyed as a result of a possible failure. RE-<br />

COMMENDATION. Install fast fuses in three-phase power supply lines L1,<br />

L2 and L3, for a higher current than the one for S6 of the RPS used. See table<br />

T. H6/3.<br />