Installation<br />

8.<br />

INSTALLATION<br />

Location<br />

312<br />

DDS<br />

HARDWARE<br />

Ref.1307<br />

272<br />

Use equipotential wires in systems with:<br />

MANDATORY.<br />

• Wide-area installation.<br />

• Different voltage sources.<br />

• Mains through several buildings reducing the current in the cable shield<br />

and the emissions. Connect to ground the electrical cabinet, the door,<br />

the mounting plate, with ground straps or cables with a cross section<br />

larger than 10 mm² (6 AWG).<br />

• The ground shields of the digital signal wires must be connected at both<br />

ends to a large surface or through a conductive housing of the connector.<br />

This reduces disturbances that affect the signal cables and also the<br />

emissions.<br />

• The ground shields of the analog signal wires must be connected directly<br />

to the device (signal input), reducing the ground loops due to low frequency<br />

disturbances.<br />

• When a unit does not have a ground connection, the shield must be<br />

connected on the side of the unit connected to ground.<br />

• To connect large cable shield surfaces, use cable and ground clamps.<br />

• Run a single shielded cable, in one piece, without joints. If a cable must<br />

necessary be cut for the installation, connect it with the shield connections<br />

and through a metal cover at the cut (joint) point. In the worst<br />

case, if it is not possible to use shielded connectors, keep a minimum<br />

length of cable exposed to disturbances guaranteeing a good connection<br />

between the shields. See figure F. H8/2.A.<br />

• Mount switching devices such as contactors, relays or electro-valves<br />

with interference suppression elements or arc suppressors (e.g. diodes,<br />

varistors, RC circuits).<br />

• Install power and control components separately.<br />

• Install before mains and the servo drive system mains chokes to reduce<br />

harmonics and expand the useful life of the product. EMC limit values<br />

may be improved by also using external filters.<br />

• Use equipotential cables when having long lines to reduce the current<br />

through the cable shield.<br />

• When connecting power cables, the shield of this cable should be connected<br />

to a ground bar. See figure F. H8/2.B.<br />

A B<br />

F. H8/2<br />

A. Make the shielded cables as short as possible when the connectors<br />

are not shielded. B. Connection of the power cable shield to a bar that is<br />

connected to ground.