28.08.2013 Views

2 - Fagor Automation

2 - Fagor Automation

2 - Fagor Automation

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Functional safety<br />

9.<br />

FUNCTIONAL SAFETY<br />

Technical data of the safety function<br />

326<br />

DDS<br />

HARDWARE<br />

Ref.1307<br />

320<br />

9.6 Technical data of the safety function<br />

<strong>Fagor</strong> <strong>Automation</strong> drives AXD/SPD only offer the safety function STO<br />

(Safe Torque Off) defined according to the standard IEC 61800-5-2.<br />

To calculate the Performance Level (PL of ISO 13849-1) and/or the Safety<br />

Integrated Level (SIL of IEC 62061) use the following data referred to<br />

AXD/SPD drives given in the following tables:<br />

T. H9/1 Calculation data according to IEC 61508 and IEC 61800-5-2.<br />

Lifetime years 20<br />

SFF (Safe Failure Fraction) % 99<br />

PFH (Average frequency of a dangerous<br />

Failure per Hour)<br />

1/h 1.5654E-07<br />

HFT (Hardware Fault Tolerance) 1<br />

SIL (Safety Integrity Level) 2<br />

This data is calculated considering a contactor with 500,000 life cycles<br />

and a demand from the STO safety function every 5 minutes running 24<br />

hours a day. For higher demands, check with <strong>Fagor</strong> <strong>Automation</strong>.<br />

T. H9/2 Calculation data according to ISO 13849-1.<br />

PL (Performance Level) d<br />

MTTFd (Mean Time To dangerous Failure) years 21.4<br />

DC (Diagnostic Coverage) % 98<br />

Category 3<br />

CCF (Common Cause Failure) 80<br />

Note. Bear in mind that PFH and MTTFd are calculated values and show<br />

the probability of failure. This does not guarantee the useful life of a particular<br />

product.<br />

The external main contactor - KM1 installed must comply with standard<br />

IEC 60947-4-1 (if it is a mirror-contact type) or with IEC 60947-5-1 (if its<br />

contact is joined mechanically).<br />

The Drive Enable has been designed to be used in high-demand mode<br />

(more than once a year) according to standard IEC 61800-5-2.