1x<br />

Terminal strip for connecting the mains voltage input<br />

Three-phase line input taken at a point before the three single-phase RPS<br />

chokes (one choke per phase). This connection is needed to receive the<br />

mains line voltages and it is done through connector (2) as shown in the<br />

next figure:<br />

S<br />

T<br />

L1<br />

L2<br />

L3<br />

L1 L2 L3<br />

R<br />

2.<br />

LINE VOLTAGE<br />

INPUT CONNECTOR<br />

3x1 mm²<br />

F. H2/42<br />

Terminal strip for connecting the mains voltage input.<br />

N<br />

From mains<br />

S T R<br />

u1 v1 w1<br />

L1<br />

L2<br />

L3<br />

L1 L2 L3<br />

The RST phases may be<br />

connected in any sequence<br />

Choke RPS-XX<br />

Cable without connectors<br />

2<br />

)<br />

MPC - 4x ... (mm2 )<br />

POWER CONNECTOR<br />

Important note: Make sure that if the phase sequence is e.g. S-L1,T-L2,R-L3<br />

at the power connector, it must then match the sequence set at the line voltage<br />

connector; that is: S - L1, T-L2, R-L3 .<br />

T. H2/30 Data of the pins of the mains voltage sensor connector. See<br />

connector 2 of the previous figure.<br />

Connector data<br />

RPS-80<br />

RPS-75<br />

RPS-45 RPS-20<br />

Nr of poles 3 3 3<br />

Gap (mm) 7.62 7.62 7.62<br />

Min/max tightening torque (N·m) 0.5/0.6 0.5/0.6 0.5/0.6<br />

Screw thread M3 M3 M3<br />

Min./max. section (mm²) 0.2/2.5 0.2/2.5 0.2/2.5<br />

Rated current In (A)<br />

Wire data<br />

12 12 12<br />

Length to strip (mm) 7 7 7<br />

The max. current circulating through the wires (screwed into this connector)<br />

will be 8.5 mA for a mains voltage of 460 V AC (rms) Therefore, use<br />

wires with a minimum section of 1 mm².<br />

MANDATORY. The phase order in the line voltage input (2) must be exactly<br />

the same as the one selected at the power connector (1). See figure F.<br />

H6/2.<br />

For further detail, see chapter 6. POWER LINE CONNECTION of this manual.<br />

Connection to an external braking resistor (Ballast)<br />

RPS power supplies do not carry a Ballast circuit and, consequently,<br />

FAGOR does not have external braking resistors (Ballast) associated with<br />

them. In applications requiring a Ballast circuit, one off-the-shelf will have to<br />

be installed.<br />

u2<br />

v2<br />

w2<br />

1.<br />

Power supplies<br />

POWER SUPPLIES<br />

Regenerative regulated power supplies 2.<br />

DDS<br />

HARDWARE<br />

Ref.1307<br />

81