High Temp Cap Override (H.TMP) — If stages of mechanical<br />

cooling are on <strong>and</strong> the error is greater than twice Y.PLU,<br />

<strong>and</strong> the rate of change of error is greater than 0.5F, then a<br />

stage of mechanical cooling will be added every 30 seconds.<br />

This override is intended to react to situations where the load<br />

rapidly increases.<br />

Low Temp Cap Override (L.TMP) — If the error is less than<br />

twice Y.MIN, <strong>and</strong> the rate of change of error is less than<br />

–0.5F, then a mechanical stage will be removed every 30 seconds.<br />

This override is intended to quickly react to situations<br />

where the load is rapidly reduced.<br />

Pull Down Cap Override (PULL) — If the error from set<br />

point is above 4F, <strong>and</strong> the rate of change is less than –1F per<br />

minute, then pulldown is in effect, <strong>and</strong> “SUM” is set to 0. This<br />

keeps mechanical cooling stages from being added when the<br />

error is very large, but there is no load in the space. Pulldown<br />

for units is expected to rarely occur, but is included for the rare<br />

situation when it is needed. Most likely pulldown will occur<br />

when mechanical cooling first becomes available shortly after<br />

the control goes into an occupied mode (after a warm unoccupied<br />

mode).<br />

Slow Change Cap Override (SLOW) — With a rooftop unit,<br />

the design rise at 100% total unit capacity is generally around<br />

30 F. For a unit with 4 stages, each stage represents about<br />

7.5F of change to EDT. If stages could reliably be cycled at<br />

Table 83 — Economizer Run Status Display Table<br />

104<br />

very fast rates, the set point could be maintained very precisely.<br />

Since it is not desirable to cycle compressors more than 6 cycles<br />

per hour, slow change override takes care of keeping the<br />

PID under control when “relatively” close to set point.<br />

VFD INFORMATION DISPLAY TABLE — The VFD information<br />

display table provides information on the supply fan<br />

VFD <strong>and</strong> exhaust fan VFD. See Table 85.<br />

MODE TRIP HELPER — The Mode Trip Helper table provides<br />

information on the unit modes <strong>and</strong> when the modes start<br />

<strong>and</strong> stop. See Table 86. This information can be used to help<br />

determine why the unit is in the current mode.<br />

CCN/LINKAGE DISPLAY TABLE — The CCN/Linkage<br />

display table provides information on unit linkage. See Table 87.<br />

COMPRESSOR RUN HOURS DISPLAY TABLE — The<br />

Compressor Run Hours Display Table displays the number of<br />

run time hours for each compressor. See Table 88.<br />

COMPRESSOR STARTS DISPLAY TABLE — The Compressor<br />

<strong>Start</strong>s Display Table displays the number of starts for<br />

each compressor. See Table 89.<br />

SOFTWARE VERSION NUMBERS DISPLAY TABLE —<br />

The Software Version Numbers Display Table displays the<br />

software version numbers of the unit boards <strong>and</strong> devices. See<br />

Table 90.<br />

ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />

ECON ECONOMIZER RUN STATUS<br />

ECN.P Economizer Act.Curr.Pos. 0-100 % ECONOPOS<br />

EC2.P Economzr2 Act.Curr.Pos. 0-100 % ECON2POS<br />

ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible<br />

ACTV Economizer Active ? YES/NO ECACTIVE<br />

DISA ECON DISABLING CONDITIONS<br />

UNV.1 Econ Act. Unavailable? YES/NO ECONUNAV<br />

UNV.2 Econ2 Act. Unavailable? YES/NO ECN2UNAV<br />

ENTH Enth. Switch Read High ? YES/NO ENTH<br />

DBC DBC - OAT Lockout? YES/NO DBC_STAT<br />

DEW DEW - OA Dewpt.Lockout? YES/NO DEW_STAT<br />

DDBC DDBD- OAT > RAT Lockout? YES/NO DDBCSTAT<br />

OAEC OAEC- OA Enth Lockout? YES/NO OAECSTAT<br />

DEC DEC - Diff.Enth.Lockout? YES/NO DEC_STAT<br />

EDT EDT Sensor Bad? YES/NO EDT_STAT<br />

OAT OAT Sensor Bad ? YES/NO OAT_STAT<br />

FORC Economizer Forced ? YES/NO ECONFORC<br />

SFON Supply Fan Not On 30s ? YES/NO SFONSTAT<br />

CLOF Cool Mode Not In Effect? YES/NO COOL_OFF<br />

OAQL OAQ Lockout in Effect ? YES/NO OAQLOCKD<br />

HELD Econ Recovery Hold Off? YES/NO ECONHELD<br />

DH.DS Dehumid. Disabled Econ.? YES/NO DHDISABL<br />

O.AIR OUTSIDE AIR INFORMATION<br />

OAT Outside Air Temperature dF OAT forcible<br />

OA.RH Outside Air Rel. Humidity % OARH forcible<br />

OA.E Outside Air Enthalpy OAE<br />

OA.D.T OutsideAir Dewpoint Temp dF OADEWTMP