CONTROLS SET POINT AND CONFIGURATION LOG (cont)<br />
ITEM EXPANSION RANGE DEFAULT SETTING<br />
IAQ (cont)<br />
AQ.SP AIR QUALITY SETPOINTS<br />
AQ.SPIQ.O.P IAQ Econo Override Pos. 0 - 100% 100<br />
AQ.SPIQ.O.C IAQ Override Flow 0 - 31000 CFM 10000<br />
AQ.SPDAQ.L Diff.Air Quality LoLimit 0 - 1000 100<br />
AQ.SPDAQ.H Diff. Air Quality HiLimit 100 - 2000 700<br />
AQ.SPD.F.OF DAQ PPM Fan Off Setpoint 0 - 2000 200<br />
AQ.SPD.F.ON DAQ PPM Fan On Setpoint 0 - 2000 400<br />
AQ.SPIAQ.R Diff. AQ Responsiveness -5 - 5 0<br />
AQ.SPOAQ.L OAQ Lockout Value 0 - 2000 0<br />
AQ.SPOAQ.U User Determined OAQ 0 - 5000 400<br />
AQ.S.R AIR QUALITY SENSOR RANGE<br />
AQ.S.RIQ.R.L IAQ Low Reference 0 - 5000 0<br />
AQ.S.RIQ.R.H IAQ High Reference 0 - 5000 2000<br />
AQ.S.ROQ.R.L OAQ Low Reference 0 - 5000 0<br />
AQ.S.ROQ.R.H OAQ High Reference 0 - 5000 2000<br />
IAQ.P IAQ PRE-OCCUPIED PURGE<br />
IAQ.PIQ.PG IAQ Purge Yes/No No<br />
IAQ.PIQ.P.T IAQ Purge Duration 5 - 60 min 15<br />
IAQ.PIQ.P.L IAQ Purge LoTemp Min Pos 0 - 100% 10<br />
IAQ.PIQ.P.H IAQ Purge HiTemp Min Pos 0 - 100% 35<br />
IAQ.PIQ.L.O IAQ Purge OAT Lockout 35 - 70 dF 50<br />
HUMD HUMIDITY CONFIGURATION<br />
HM.CF Humidifier Control Cfg. 0 - 4 0<br />
HM.SP Humidifier Setpoint 0 - 100% 40<br />
H.PID HUMIDIFIER PID CONFIGS<br />
H.PIDHM.TM Humidifier PID Run Rate 10 - 120 sec 30<br />
H.PIDHM.P Humidifier Prop. Gain 0 - 5 1<br />
H.PIDHM.I Humidifier Integral Gain 0 - 5 0.3<br />
H.PIDHM.D Humidifier Deriv. Gain 0 - 5 0.3<br />
ACT.C HUMIDIFIER ACTUATOR CFGS<br />
ACTCSN.1 Humd Serial Number 1 0 - 9999 0<br />
ACTCSN.2 Humd Serial Number 2 0 - 6 0<br />
ACTCSN.3 Humd Serial Number 3 0 - 9999 0<br />
ACTCSN.4 Humd Serial Number 4 0 - 254 0<br />
ACTCC.A.LM Humd Ctrl Angle Lo Limit 0 - 90 85<br />
DEHU DEHUMIDIFICATION CONFIG.<br />
D.SEL Dehumidification Config 0 - 3 (multi-text strings) 0<br />
D.SEN Dehumidification Sensor 1 - 3 (multi-text strings) 1<br />
D.EC.D Econ disable in DH mode? Yes/No Yes<br />
D.V.CF Vent Reheat Setpt Select 0 - 1 (multi-text strings) 0<br />
D.V.RA Vent Reheat RAT offset 0 - 8 delta F 0<br />
D.V.HT Vent Reheat Setpoint 55 - 95 dF 70<br />
D.C.SP Dehumidify Cool Setpoint 40 - 55 dF 45<br />
D.RH.S Dehumidify RH Setpoint 10 - 90% 55<br />
HZ.RT Humidimizer Adjust Rate 5-120 sec 30<br />
HZ.PG Humidimizer Prop. Gain 0-10 0.8<br />
CCN CCN CONFIGURATION<br />
CCNA CCN Address 1 - 239 1<br />
CCNB CCN Bus Number 0 - 239 0<br />
BAUD CCN Baud Rate 1 - 5 (multi-text strings) 3<br />
BROD CCN BROADCST DEFINITIONS<br />
BRODTM.DT CCN Time/Date Broadcast ON/OFF On<br />
BRODOAT.B CCN OAT Broadcast ON/OFF Off<br />
BRODORH.B CCN OARH Broadcast ON/OFF Off<br />
BRODOAQ.B CCN OAQ Broadcast ON/OFF Off<br />
BRODG.S.B Global Schedule Broadcst ON/OFF Off<br />
BRODB.ACK CCN Broadcast Ack'er ON/OFF Off<br />
SC.OV CCN SCHEDULES-OVERRIDES<br />
SC.OVSCH.N Schedule Number 0 - 99 1<br />
SC.OVHOL.T Accept Global Holidays? YES/NO No<br />
SC.OVO.T.L. Override Time Limit 0 - 4 HRS 1<br />
SC.OVOV.EX Timed Override Hours 0 - 4 HRS 0<br />