Table 58 — Humidity Configuration<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
HUMD HUMIDITY CONFIGURATION<br />
HM.CF Humidifier Control Cfg. 0 - 4 HUMD_CFG 0<br />
HM.SP Humidifier Setpoint 0 - 100 % HUSP 40<br />
H.PID HUMIDIFIER PID CONFIGS<br />
HM.TM Humidifier PID Run Rate 10 - 120 sec HUMDRATE 30<br />
HM.P Humidifier Prop. Gain 0 - 5 HUMID_PG 1<br />
HM.I Humidifier Integral Gain 0 - 5 HUMID_IG 0.3<br />
HM.D Humidifier Deriv. Gain 0 - 5 HUMID_DG 0.3<br />
ACT.C HUMIDIFIER ACTUATOR CFGS<br />
SN.1 Humd Serial Number 1 0 - 9999 HUMD_SN1 0<br />
SN.2 Humd Serial Number 2 0 - 6 HUMD_SN2 0<br />
SN.3 Humd Serial Number 3 0 - 9999 HUMD_SN3 0<br />
SN.4 Humd Serial Number 4 0 - 254 HUMD_SN4 0<br />
C.A.LM Humd Ctrl Angle Lo Limit 0-90 HUMDCALM 85<br />
CONFIGURING THE HUMIDIFIER ACTUATOR —<br />
Every actuator used in the P Series control system has its own<br />
unique serial number. The rooftop control uses this serial<br />
number to communicate with the actuator. The actuator serial<br />
number is located on a two-part sticker affixed to the side of the<br />
actuator housing. Remove one of the actuator’s serial number<br />
labels <strong>and</strong> paste it onto the actuator serial number records label<br />
located inside the left-h<strong>and</strong> access panel at the unit’s control<br />
panel. Four individual numbers make up this serial number.<br />
Program the serial number of the actuator in its Humidifier Actuator<br />
Configurations group, ACT.C (SN.1, SN.2, SN.3, SN.4)<br />
NOTE: The serial numbers for all actuators can be found<br />
inside the control doors of the unit as well as on the actuator<br />
itself. If an actuator is replaced in the field, it is a good idea to<br />
remove the additional peel-off serial number sticker on the<br />
actuator <strong>and</strong> cover up the old one inside the control doors.<br />
Control Angle Alarm (ConfigurationHUMDACTC<br />
C.A.LM) — The humidifier actuator learns what its end stops<br />
are though a calibration at the factory. Field-installed actuators<br />
may be calibrated in the <strong>Service</strong> Test mode. When an actuator<br />
learns its end stops through calibration, it determines its control<br />
angle. The actuator will resolve this control angle <strong>and</strong> express<br />
its operation in a percent (%) of this learned range.<br />
If the humidifier actuator has not learned a sufficient control<br />
angle during calibration, the actuator will be unable to control<br />
humidity. For this reason, the humidifier actuator has a configurable<br />
control angle alarm low limit (C.A.LM). If the control<br />
angle learned through calibration is less than C.A.LM, an alert<br />
will occur <strong>and</strong> the actuator will not function.<br />
NOTE: This configuration does not typically need adjustment.<br />
It is configurable for the small number of jobs which may<br />
require a custom solution or workaround.<br />
Dehumidification <strong>and</strong> Reheat — The Dehumidification<br />
function will override comfort condition set points<br />
based on dry bulb temperature <strong>and</strong> deliver cooler air to the<br />
space in order to satisfy a humidity set point at the space or<br />
return air humidity sensor. The Reheat function will energize a<br />
suitable heating system concurrent with dehumidification<br />
sequence should the dehumidification operation result in<br />
excessive cooling of the space condition.<br />
The dehumidification sequence requires the installation of a<br />
space or return air humidity sensor or a discrete switch input. A<br />
CEM (option or accessory) is required to accommodate an RH<br />
(relative humidity) sensor connection. Reheat is possible when<br />
multiple-step staged gas control option or hydronic heat<br />
Table 59 — Related Humidity Points<br />
ITEM EXPANSION UNITS CCN POINT WRITE STATUS<br />
ConfigUNITSENSSRH.S Space Air RH Sensor SPRHSENS<br />
ConfigUNITSENSRRH.S Return Air RH Sensor RARHSENS<br />
InputsREL.HRA.RH Return Air Rel. Humidity % RARH forcible<br />
InputsREL.HSP.RH Space Relative Humidity % SPRH forcible<br />
OutputsACTUHMD.P Humidifier Act.Curr.Pos. % HUMDRPOS<br />
OutputsACTUHMD.C Humidifier Comm<strong>and</strong> Pos. % HUMDCPOS<br />
OutputsGEN.OHUM.R Humidifier Relay HUMIDRLY<br />
79<br />
(option or field-installed coil) is installed. Reheat is also possible<br />
using a heat reclaim coil (field-supplied <strong>and</strong> installed) or a<br />
hot gas reheat coil (special order, factory-installed).<br />
Dehumidification <strong>and</strong> reheat control are allowed during<br />
Cooling <strong>and</strong> Vent modes in the Occupied period.<br />
On constant volume units using thermostat inputs (C.TYP =<br />
3), the discrete switch input must be used as the dehumidification<br />
control input. The commercial Thermidistat device is<br />
the recommended accessory device.<br />
SETTING UP THE SYSTEM — The settings for dehumidification<br />
can be found at the local display at Configuration<br />
DEHU. See Table 60.<br />
Dehumidification Configuration (D.SEL) — The dehumidification<br />
configuration can be set for the following settings:<br />
• D.SEL = 0 — No dehumidification <strong>and</strong> reheat.<br />
• D.SEL = 1 — The control will perform both dehumidification<br />
<strong>and</strong> reheat with modulating valve (hydronic).<br />
• D.SEL = 2 — The control will perform dehumidification<br />
<strong>and</strong> reheat with staged gas only.<br />
• D.SEL = 3 — The control will perform both dehumidification<br />
<strong>and</strong> reheat with third party heat via an alarm relay.<br />
In the case of D.SEL=3, during dehumidification, the<br />
alarm relay will close to convey the need for reheat. A<br />
typical application might be to energize a 3-way valve to<br />
perform hot gas reheat.<br />
• D.SEL = 4 — The control will use the Humidi-MiZer ®<br />
adaptive dehumidification system.<br />
Dehumidification Sensor (D.SEN) — The sensor can be configured<br />
for the following settings:<br />
• D.SEN = 1 — Initiated by return air relative humidity<br />
sensor.<br />
• D.SEN = 2 — Initiated by space relative humidity sensor.<br />
• D.SEN = 3 — Initiated by discrete input.<br />
Economizer Disable in Dehum Mode (D.EC.D) — This<br />
configuration determines economizer operation during Dehumidification<br />
mode.<br />
• D.EC.D = YES — Economizer disabled during dehumidification<br />
(default).<br />
• D.EC.D = NO — Economizer not disabled during dehumidification.<br />
Vent Reheat Set Point Select (D.V.CF) — This configuration<br />
determines how the vent reheat set point is selected.<br />
• D.V.CF = 0 — Reheat follows an offset subtracted from<br />
return air temperature (D.V.RA).