06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Table 53 — Dirty Filter Switch Points<br />

ITEM EXPANSION RANGE<br />

CCN<br />

POINT<br />

ConfigurationUNIT<br />

SENSFLT.S<br />

Filter<br />

Stat.Sw.Enabled ? Enable/<br />

Disable<br />

FLTS_ENA<br />

InputsGEN.I<br />

FLT.S<br />

Filter Status Input DRTY/CLN FLTS<br />

Monitoring of the filter status switch is disabled in the<br />

<strong>Service</strong> Test mode <strong>and</strong> when the supply fan is not comm<strong>and</strong>ed<br />

on. If the fan is on <strong>and</strong> the unit is not in a test mode <strong>and</strong> the<br />

filter status switch reads “dirty” for 2 continuous minutes, an<br />

alert is generated. Recovery from this alert is done through a<br />

clearing of all alarms or after cleaning the filter <strong>and</strong> the switch<br />

reads “clean” for 30 seconds.<br />

NOTE: The filter switch should be adjusted to allow for the<br />

operating cfm <strong>and</strong> the type of filter. Refer to the accessory<br />

installation instructions for information on adjusting the switch.<br />

Economizer — The economizer control is used to manage<br />

the outside <strong>and</strong> return air dampers of the unit to provide ventilation<br />

air as well as free cooling based on several configuration<br />

options. This section contains a description of the economizer<br />

<strong>and</strong> its ability to provide free cooling. See the section on indoor<br />

air quality for more information on setting up <strong>and</strong> using the<br />

economizer to perform dem<strong>and</strong> controlled ventilation (DCV).<br />

See the Third Party Control section for a description on how to<br />

take over the operation of the economizer through external<br />

control.<br />

The economizer system also permits this unit to perform<br />

smoke control functions based on external control switch<br />

inputs. Refer to the Smoke Control Modes section for detailed<br />

discussions.<br />

Economizer control can be based on automatic control<br />

algorithms using unit-based set points <strong>and</strong> sensor inputs. This<br />

economizer control system can also be managed through external<br />

logic systems.<br />

The economizer system is a factory-installed option. This<br />

option includes a factory-installed enthalpy control device to<br />

determine the changeover condition that permits free cooling<br />

operation. This unit can also have the following devices<br />

installed to enhance economizer control:<br />

• Outside air humidity sensor<br />

• Return air humidity sensor<br />

• Outside airflow control<br />

NOTE: All these options require the controls expansion module<br />

(CEM).<br />

The P Series economizer damper is managed by a communicating<br />

actuator motor(s). This provides the ability of the control<br />

system to monitor, diagnose <strong>and</strong> report the health <strong>and</strong> operation<br />

of the actuator <strong>and</strong> damper system to the local display <strong>and</strong><br />

CCN network, thus providing extensive diagnostic tools to<br />

servicers.<br />

SETTING UP THE SYSTEM — The economizer configuration<br />

options are under the Local Display Mode Configuration<br />

ECON. See Table 54.<br />

Economizer Installed? (EC.EN) — If an economizer is not<br />

installed or is to be completely disabled the configuration<br />

option EC.EN may be set to No. Otherwise in the case of an installed<br />

economizer, this option must be set to Yes.<br />

Economizer Actuator 2 Installed? (EC2.E) — For 48/50P055-<br />

100 units, a second economizer actuator is required. For sizes<br />

055-100, set this configuration to Yes.<br />

Economizer Minimum Position (EC.MN) — The configuration<br />

option EC.MN is the economizer minimum position. See<br />

the section on indoor air quality for further information on how<br />

to reset the economizer further to gain energy savings <strong>and</strong> to<br />

more carefully monitor IAQ problems.<br />

67<br />

Economizer Maximum Position (EC.MX) — The upper limit<br />

of the economizer may be limited by setting EC.MX. It defaults<br />

to 98% to avoid problems associated with slight changes<br />

in the economizer damper’s end stop over time. Typically this<br />

will not need to be adjusted.<br />

Economizer Trim for Sum Z? (E.TRM) — Sum Z is the<br />

adaptive cooling control algorithm used for multiple stages<br />

of mechanical cooling capacity. The configuration option,<br />

E.TRM is typically set to Yes, <strong>and</strong> allows the economizer to<br />

modulate to the same control point (Sum Z) that is used to<br />

control capacity staging. The advantage is lower compressor<br />

cycling coupled with tighter temperature control. Setting this<br />

option to No will cause the economizer, if it is able to provide<br />

free cooling, to open to the Economizer Max. Position<br />

(EC.MX) during mechanical cooling.<br />

ECONOMIZER OPERATION — There are four potential<br />

elements which are considered concurrently which determine<br />

whether the economizer is able to provide free cooling:<br />

1. Dry bulb changeover (outside-air temperature qualification)<br />

2. Enthalpy switch (discrete control input monitoring)<br />

3. Economizer changeover select (E.SEL economizer<br />

changeover select configuration option)<br />

4. Outdoor dewpoint limit check (requires an installed outdoor<br />

relative humidity sensor installed)<br />

Dry Bulb Changeover — Outside-air temperature may be<br />

viewed under TemperaturesAIR.TOAT. The control<br />

constantly compares its outside-air temperature reading against<br />

the high temperature OAT lockout (OAT.L). If the temperature<br />

reads above OAT.L, the economizer will not be allowed to perform<br />

free cooling.<br />

NOTE: If the user wishes to disable the enthalpy switch from<br />

running concurrently, a field-supplied jumper must be installed<br />

between TB201 terminals 3 <strong>and</strong> 4.<br />

Enthalpy Switch — The state of the enthalpy switch can be<br />

viewed under InputsGEN.IENTH. Enthalpy switches are<br />

installed as st<strong>and</strong>ard on all P Series rooftops. When the switch<br />

reads high, free cooling will be disallowed.<br />

The enthalpy switch opens (reads high) when the outdoor<br />

enthalpy is above 24 Btu/lb or dry bulb temperature is above<br />

70 F <strong>and</strong> will close when the outdoor enthalpy is below<br />

23 Btu/lb or the dry bulb temperature is below 69.5 F.<br />

NOTE: The enthalpy switch has both a low <strong>and</strong> a high output.<br />

To use this switch as designed the control must be connected to<br />

the low output. Additionally there is a switch logic setting for<br />

the enthalpy switch under ConfigurationSW.LGENT.L.<br />

This setting must be configured to closed (CLSE) to work properly<br />

when connected to the low output of the enthalpy switch.<br />

There are two jumpers under the cover of the enthalpy<br />

switch. One jumper determines the mode of the enthalpy<br />

switch/receiver. The other is not used. For the enthalpy switch,<br />

the factory setting is M1 <strong>and</strong> should not need to be changed. See<br />

Fig. 10 for a diagram showing the settings on the enthalpy<br />

switch.<br />

The enthalpy switch may also be field converted to a differential<br />

enthalpy switch by field installing an enthalpy sensor<br />

(33CSENTSEN or HH57ZC001). The enthalpy switch/receiver<br />

remains installed in its factory location to sense outdoor air<br />

enthalpy. The additional enthalpy sensor (33CSENTSEN) is<br />

mounted in the return airstream to measure return air enthalpy.<br />

The enthalpy control jumper must be changed from M1 to M2<br />

for differential enthalpy control. For the 2-wire return air enthalpy<br />

sensor, connect power to the Vin input <strong>and</strong> signal to the<br />

4 to 20 mA loop input. See Fig. 10 for diagram showing the<br />

settings <strong>and</strong> inputs on the enthalpy switch.<br />

There is another way to accomplish differential enthalpy<br />

control when both an outdoor <strong>and</strong> return air relative humidity

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!