Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Table 53 — Dirty Filter Switch Points<br />
ITEM EXPANSION RANGE<br />
CCN<br />
POINT<br />
ConfigurationUNIT<br />
SENSFLT.S<br />
Filter<br />
Stat.Sw.Enabled ? Enable/<br />
Disable<br />
FLTS_ENA<br />
InputsGEN.I<br />
FLT.S<br />
Filter Status Input DRTY/CLN FLTS<br />
Monitoring of the filter status switch is disabled in the<br />
<strong>Service</strong> Test mode <strong>and</strong> when the supply fan is not comm<strong>and</strong>ed<br />
on. If the fan is on <strong>and</strong> the unit is not in a test mode <strong>and</strong> the<br />
filter status switch reads “dirty” for 2 continuous minutes, an<br />
alert is generated. Recovery from this alert is done through a<br />
clearing of all alarms or after cleaning the filter <strong>and</strong> the switch<br />
reads “clean” for 30 seconds.<br />
NOTE: The filter switch should be adjusted to allow for the<br />
operating cfm <strong>and</strong> the type of filter. Refer to the accessory<br />
installation instructions for information on adjusting the switch.<br />
Economizer — The economizer control is used to manage<br />
the outside <strong>and</strong> return air dampers of the unit to provide ventilation<br />
air as well as free cooling based on several configuration<br />
options. This section contains a description of the economizer<br />
<strong>and</strong> its ability to provide free cooling. See the section on indoor<br />
air quality for more information on setting up <strong>and</strong> using the<br />
economizer to perform dem<strong>and</strong> controlled ventilation (DCV).<br />
See the Third Party Control section for a description on how to<br />
take over the operation of the economizer through external<br />
control.<br />
The economizer system also permits this unit to perform<br />
smoke control functions based on external control switch<br />
inputs. Refer to the Smoke Control Modes section for detailed<br />
discussions.<br />
Economizer control can be based on automatic control<br />
algorithms using unit-based set points <strong>and</strong> sensor inputs. This<br />
economizer control system can also be managed through external<br />
logic systems.<br />
The economizer system is a factory-installed option. This<br />
option includes a factory-installed enthalpy control device to<br />
determine the changeover condition that permits free cooling<br />
operation. This unit can also have the following devices<br />
installed to enhance economizer control:<br />
• Outside air humidity sensor<br />
• Return air humidity sensor<br />
• Outside airflow control<br />
NOTE: All these options require the controls expansion module<br />
(CEM).<br />
The P Series economizer damper is managed by a communicating<br />
actuator motor(s). This provides the ability of the control<br />
system to monitor, diagnose <strong>and</strong> report the health <strong>and</strong> operation<br />
of the actuator <strong>and</strong> damper system to the local display <strong>and</strong><br />
CCN network, thus providing extensive diagnostic tools to<br />
servicers.<br />
SETTING UP THE SYSTEM — The economizer configuration<br />
options are under the Local Display Mode Configuration<br />
ECON. See Table 54.<br />
Economizer Installed? (EC.EN) — If an economizer is not<br />
installed or is to be completely disabled the configuration<br />
option EC.EN may be set to No. Otherwise in the case of an installed<br />
economizer, this option must be set to Yes.<br />
Economizer Actuator 2 Installed? (EC2.E) — For 48/50P055-<br />
100 units, a second economizer actuator is required. For sizes<br />
055-100, set this configuration to Yes.<br />
Economizer Minimum Position (EC.MN) — The configuration<br />
option EC.MN is the economizer minimum position. See<br />
the section on indoor air quality for further information on how<br />
to reset the economizer further to gain energy savings <strong>and</strong> to<br />
more carefully monitor IAQ problems.<br />
67<br />
Economizer Maximum Position (EC.MX) — The upper limit<br />
of the economizer may be limited by setting EC.MX. It defaults<br />
to 98% to avoid problems associated with slight changes<br />
in the economizer damper’s end stop over time. Typically this<br />
will not need to be adjusted.<br />
Economizer Trim for Sum Z? (E.TRM) — Sum Z is the<br />
adaptive cooling control algorithm used for multiple stages<br />
of mechanical cooling capacity. The configuration option,<br />
E.TRM is typically set to Yes, <strong>and</strong> allows the economizer to<br />
modulate to the same control point (Sum Z) that is used to<br />
control capacity staging. The advantage is lower compressor<br />
cycling coupled with tighter temperature control. Setting this<br />
option to No will cause the economizer, if it is able to provide<br />
free cooling, to open to the Economizer Max. Position<br />
(EC.MX) during mechanical cooling.<br />
ECONOMIZER OPERATION — There are four potential<br />
elements which are considered concurrently which determine<br />
whether the economizer is able to provide free cooling:<br />
1. Dry bulb changeover (outside-air temperature qualification)<br />
2. Enthalpy switch (discrete control input monitoring)<br />
3. Economizer changeover select (E.SEL economizer<br />
changeover select configuration option)<br />
4. Outdoor dewpoint limit check (requires an installed outdoor<br />
relative humidity sensor installed)<br />
Dry Bulb Changeover — Outside-air temperature may be<br />
viewed under TemperaturesAIR.TOAT. The control<br />
constantly compares its outside-air temperature reading against<br />
the high temperature OAT lockout (OAT.L). If the temperature<br />
reads above OAT.L, the economizer will not be allowed to perform<br />
free cooling.<br />
NOTE: If the user wishes to disable the enthalpy switch from<br />
running concurrently, a field-supplied jumper must be installed<br />
between TB201 terminals 3 <strong>and</strong> 4.<br />
Enthalpy Switch — The state of the enthalpy switch can be<br />
viewed under InputsGEN.IENTH. Enthalpy switches are<br />
installed as st<strong>and</strong>ard on all P Series rooftops. When the switch<br />
reads high, free cooling will be disallowed.<br />
The enthalpy switch opens (reads high) when the outdoor<br />
enthalpy is above 24 Btu/lb or dry bulb temperature is above<br />
70 F <strong>and</strong> will close when the outdoor enthalpy is below<br />
23 Btu/lb or the dry bulb temperature is below 69.5 F.<br />
NOTE: The enthalpy switch has both a low <strong>and</strong> a high output.<br />
To use this switch as designed the control must be connected to<br />
the low output. Additionally there is a switch logic setting for<br />
the enthalpy switch under ConfigurationSW.LGENT.L.<br />
This setting must be configured to closed (CLSE) to work properly<br />
when connected to the low output of the enthalpy switch.<br />
There are two jumpers under the cover of the enthalpy<br />
switch. One jumper determines the mode of the enthalpy<br />
switch/receiver. The other is not used. For the enthalpy switch,<br />
the factory setting is M1 <strong>and</strong> should not need to be changed. See<br />
Fig. 10 for a diagram showing the settings on the enthalpy<br />
switch.<br />
The enthalpy switch may also be field converted to a differential<br />
enthalpy switch by field installing an enthalpy sensor<br />
(33CSENTSEN or HH57ZC001). The enthalpy switch/receiver<br />
remains installed in its factory location to sense outdoor air<br />
enthalpy. The additional enthalpy sensor (33CSENTSEN) is<br />
mounted in the return airstream to measure return air enthalpy.<br />
The enthalpy control jumper must be changed from M1 to M2<br />
for differential enthalpy control. For the 2-wire return air enthalpy<br />
sensor, connect power to the Vin input <strong>and</strong> signal to the<br />
4 to 20 mA loop input. See Fig. 10 for diagram showing the<br />
settings <strong>and</strong> inputs on the enthalpy switch.<br />
There is another way to accomplish differential enthalpy<br />
control when both an outdoor <strong>and</strong> return air relative humidity