Use CSBs for HPS detect? (CS.HP) – On units with multiple<br />
compressors running on a circuit, the Current Sensor Boards<br />
are used to help detect a High Pressure Switch trip. Setting this<br />
configuration to NO disables this additional High Pressure<br />
switch trip detection.<br />
COOL MODE SELECTION PROCESS — The P Series<br />
ComfortLink controls offer three distinct methods by which<br />
they may select a cooling mode.<br />
1. Thermostat (C.TYP=3): The thermostat does not depend<br />
upon the state of occupancy or temperature <strong>and</strong> the<br />
modes are called out directly by the discrete inputs (InputsSTATY1<br />
<strong>and</strong> Y2).<br />
2. VAV cooling types (C.TYP=1 <strong>and</strong> 2) are called out<br />
in the occupied period (Operating ModesMODE<br />
OCC=ON).<br />
3. VAV cooling types (C.TYP=1 <strong>and</strong> 2) are called out in the<br />
unoccupied period (Operating ModesMODE<br />
OCC=OFF). They are also used for space sensor control<br />
types (C.TYP=4) in both the occupied <strong>and</strong> unoccupied<br />
periods.<br />
This section is devoted to the process of cooling mode<br />
determination for the three types outlined above.<br />
VAV Cool Mode Selection during the Occupied Period<br />
(C.TYP = 1,2 <strong>and</strong> Operating ModesMODEOCC =ON)<br />
— There is no difference in the selection of a cooling mode for<br />
either VAV-RAT or VAV-SPT in the occupied period. The actual<br />
selection of a cool mode, for both control types, is based upon<br />
the controlling return-air temperature (Temperatures<br />
AIR.TCTRLR.TMP). Typically this is the same as the return<br />
air temperature thermistor (TemperaturesAIR.T RAT)<br />
except when under CCN Linkage.<br />
Cool Mode Determination — If the machine control type<br />
(ConfigurationUNITC.TYP) = 1 (VAV-RAT) or 2 (VAV-<br />
SPT) <strong>and</strong> the control is occupied (Operating<br />
ModesMODEOCC=ON), then the unit will not follow<br />
the occupied cooling set point (OCSP). Instead, the control<br />
will follow two offsets in the determination of an occupied<br />
VAV cooling mode (SetpointsV.C.ON <strong>and</strong> SetpointsV.C.OF),<br />
applying them to the low-heat off trip point<br />
<strong>and</strong> comparing the resulting temperature to the controlling<br />
return temperature (R.TMP).<br />
The SetpointsV.C.ON (VAV cool mode on offset) <strong>and</strong><br />
SetpointsV.C.OF (VAV cool mode off offset) offsets are<br />
used in conjunction with the low heat mode off trip point to<br />
determine when to bring cooling on <strong>and</strong> off <strong>and</strong> in enforcing a<br />
true “vent” mode between heating <strong>and</strong> cooling. See Fig. 5. The<br />
occupied cooling set point is not used in the determination of<br />
the cool mode. The occupied cooling set point is used for supply<br />
air reset only.<br />
The advantage of this offset technique is that the control can<br />
safely enforce a vent mode without worrying about crossing set<br />
points. Even more importantly, under CCN linkage, the<br />
occupied heating set point may drift up <strong>and</strong> down <strong>and</strong> as such<br />
this technique of using offsets ensures a guaranteed separation<br />
in degrees F between the calling out of a heating or cooling<br />
mode at all times.<br />
VAV Occupied Cool Mode Evaluation Configuration — There<br />
are VAV occupied cooling offsets under Setpoints.<br />
ITEM EXPANSION RANGE UNITS<br />
CCN<br />
POINT<br />
DEFAULT<br />
V.C.ON VAV Occ.<br />
Cool On Delta<br />
0-25 deltaF VAVOCON 3.5<br />
V.C.OF VAV Occ.<br />
Cool Off Delta<br />
1-25 deltaF VAVOCOFF 2<br />
48<br />
NOTE: There is a sub-menu at the local display (Run Status<br />
TRIP) that allows the user to see the exact trip points for<br />
both the heating <strong>and</strong> cooling modes without having to calculate<br />
them. Refer to the Cool Mode Diagnostic Help section on<br />
page 49 for more information.<br />
To enter into a VAV Occupied Cool mode, the controlling<br />
temperature must rise above [OHSP minus L.H.ON plus<br />
L.H.OF plus V.C.ON].<br />
To exit out of a VAV Occupied Cool Mode, the controlling<br />
temperature must fall below [OHSP minus L.H.ON plus<br />
L.H.OF plus V.C.ON minus V.C.OF].<br />
NOTE: With vent mode, it is possible to exit out of a cooling<br />
mode during the occupied period if the return-air temperature<br />
drops low enough. When supply-air temperature reset is not<br />
configured, this capability will work to prevent over-cooling<br />
the space during the occupied period.<br />
Supply Air Set Point Control <strong>and</strong> the Staging of Compressors<br />
— Once the control has determined that a cooling mode is in<br />
effect, the cooling control point (Run StatusVIEW<br />
CL.C.P) is calculated <strong>and</strong> is based upon the supply air set<br />
point (SetpointsSASP) plus any supply air reset being<br />
applied (InputsRSETSA.S.R).<br />
Refer to the SumZ Cooling Algorithm section on page 50<br />
for a discussion of how the P Series ComfortLink controls<br />
manage the staging of compressors to maintain supply-air<br />
temperature.<br />
VAV Cool Mode Selection during the Unoccupied Period<br />
(C.TYP = 1,2; Operating ModesMODEOCC=OFF)<br />
<strong>and</strong> Space Sensor Cool Mode Selection (C.TYP=4) — The<br />
machine control types that utilize this technique of mode selection<br />
are:<br />
• C.TYP = 1 (VAV-RAT) in the unoccupied period<br />
• C.TYP = 2 (VAV-SPT) in the unoccupied period<br />
• C.TYP = 4 (SPT-MULTI) in both the occupied <strong>and</strong><br />
unoccupied period<br />
These particular control types operate differently than the<br />
VAV types in the occupied mode in that there is both a LOW<br />
COOL <strong>and</strong> a HIGH COOL mode. For both of these modes, the<br />
control offers two independent set points, SetpointsSA.LO<br />
(for LOW COOL mode) <strong>and</strong> SetpointsSA.HI (for HIGH<br />
COOL mode).<br />
The occupied <strong>and</strong> unoccupied cooling set points can be<br />
found under Setpoints.<br />
ITEM EXPANSION RANGE UNITS CCN<br />
POINT DEFAULT<br />
OCSP Occupied<br />
Cool Setpoint<br />
55-80 dF OCSP 75<br />
UCSP Unoccupied<br />
Cool Setpoint<br />
75-95 dF UCSP 90<br />
The heat/cool set point offsets are found under ConfigurationD.LV.T.<br />
See Table 36.<br />
OHSP<br />
L.H.ON<br />
DMDLHON<br />
V.C. ON<br />
VAVOCON<br />
L.H.OF<br />
DMDLHOFF<br />
V.C. OF<br />
VAVOCOFF<br />
a48-8414<br />
Fig. 5 — VAV Occupied Period Trip Logic