Use CSBs for HPS detect? (CS.HP) – On units with multiple<br />

compressors running on a circuit, the Current Sensor Boards<br />

are used to help detect a High Pressure Switch trip. Setting this<br />

configuration to NO disables this additional High Pressure<br />

switch trip detection.<br />

COOL MODE SELECTION PROCESS — The P Series<br />

ComfortLink controls offer three distinct methods by which<br />

they may select a cooling mode.<br />

1. Thermostat (C.TYP=3): The thermostat does not depend<br />

upon the state of occupancy or temperature <strong>and</strong> the<br />

modes are called out directly by the discrete inputs (InputsSTATY1<br />

<strong>and</strong> Y2).<br />

2. VAV cooling types (C.TYP=1 <strong>and</strong> 2) are called out<br />

in the occupied period (Operating ModesMODE<br />

OCC=ON).<br />

3. VAV cooling types (C.TYP=1 <strong>and</strong> 2) are called out in the<br />

unoccupied period (Operating ModesMODE<br />

OCC=OFF). They are also used for space sensor control<br />

types (C.TYP=4) in both the occupied <strong>and</strong> unoccupied<br />

periods.<br />

This section is devoted to the process of cooling mode<br />

determination for the three types outlined above.<br />

VAV Cool Mode Selection during the Occupied Period<br />

(C.TYP = 1,2 <strong>and</strong> Operating ModesMODEOCC =ON)<br />

— There is no difference in the selection of a cooling mode for<br />

either VAV-RAT or VAV-SPT in the occupied period. The actual<br />

selection of a cool mode, for both control types, is based upon<br />

the controlling return-air temperature (Temperatures<br />

AIR.TCTRLR.TMP). Typically this is the same as the return<br />

air temperature thermistor (TemperaturesAIR.T RAT)<br />

except when under CCN Linkage.<br />

Cool Mode Determination — If the machine control type<br />

(ConfigurationUNITC.TYP) = 1 (VAV-RAT) or 2 (VAV-<br />

SPT) <strong>and</strong> the control is occupied (Operating<br />

ModesMODEOCC=ON), then the unit will not follow<br />

the occupied cooling set point (OCSP). Instead, the control<br />

will follow two offsets in the determination of an occupied<br />

VAV cooling mode (SetpointsV.C.ON <strong>and</strong> SetpointsV.C.OF),<br />

applying them to the low-heat off trip point<br />

<strong>and</strong> comparing the resulting temperature to the controlling<br />

return temperature (R.TMP).<br />

The SetpointsV.C.ON (VAV cool mode on offset) <strong>and</strong><br />

SetpointsV.C.OF (VAV cool mode off offset) offsets are<br />

used in conjunction with the low heat mode off trip point to<br />

determine when to bring cooling on <strong>and</strong> off <strong>and</strong> in enforcing a<br />

true “vent” mode between heating <strong>and</strong> cooling. See Fig. 5. The<br />

occupied cooling set point is not used in the determination of<br />

the cool mode. The occupied cooling set point is used for supply<br />

air reset only.<br />

The advantage of this offset technique is that the control can<br />

safely enforce a vent mode without worrying about crossing set<br />

points. Even more importantly, under CCN linkage, the<br />

occupied heating set point may drift up <strong>and</strong> down <strong>and</strong> as such<br />

this technique of using offsets ensures a guaranteed separation<br />

in degrees F between the calling out of a heating or cooling<br />

mode at all times.<br />

VAV Occupied Cool Mode Evaluation Configuration — There<br />

are VAV occupied cooling offsets under Setpoints.<br />

ITEM EXPANSION RANGE UNITS<br />

CCN<br />

POINT<br />

DEFAULT<br />

V.C.ON VAV Occ.<br />

Cool On Delta<br />

0-25 deltaF VAVOCON 3.5<br />

V.C.OF VAV Occ.<br />

Cool Off Delta<br />

1-25 deltaF VAVOCOFF 2<br />

48<br />

NOTE: There is a sub-menu at the local display (Run Status<br />

TRIP) that allows the user to see the exact trip points for<br />

both the heating <strong>and</strong> cooling modes without having to calculate<br />

them. Refer to the Cool Mode Diagnostic Help section on<br />

page 49 for more information.<br />

To enter into a VAV Occupied Cool mode, the controlling<br />

temperature must rise above [OHSP minus L.H.ON plus<br />

L.H.OF plus V.C.ON].<br />

To exit out of a VAV Occupied Cool Mode, the controlling<br />

temperature must fall below [OHSP minus L.H.ON plus<br />

L.H.OF plus V.C.ON minus V.C.OF].<br />

NOTE: With vent mode, it is possible to exit out of a cooling<br />

mode during the occupied period if the return-air temperature<br />

drops low enough. When supply-air temperature reset is not<br />

configured, this capability will work to prevent over-cooling<br />

the space during the occupied period.<br />

Supply Air Set Point Control <strong>and</strong> the Staging of Compressors<br />

— Once the control has determined that a cooling mode is in<br />

effect, the cooling control point (Run StatusVIEW<br />

CL.C.P) is calculated <strong>and</strong> is based upon the supply air set<br />

point (SetpointsSASP) plus any supply air reset being<br />

applied (InputsRSETSA.S.R).<br />

Refer to the SumZ Cooling Algorithm section on page 50<br />

for a discussion of how the P Series ComfortLink controls<br />

manage the staging of compressors to maintain supply-air<br />

temperature.<br />

VAV Cool Mode Selection during the Unoccupied Period<br />

(C.TYP = 1,2; Operating ModesMODEOCC=OFF)<br />

<strong>and</strong> Space Sensor Cool Mode Selection (C.TYP=4) — The<br />

machine control types that utilize this technique of mode selection<br />

are:<br />

• C.TYP = 1 (VAV-RAT) in the unoccupied period<br />

• C.TYP = 2 (VAV-SPT) in the unoccupied period<br />

• C.TYP = 4 (SPT-MULTI) in both the occupied <strong>and</strong><br />

unoccupied period<br />

These particular control types operate differently than the<br />

VAV types in the occupied mode in that there is both a LOW<br />

COOL <strong>and</strong> a HIGH COOL mode. For both of these modes, the<br />

control offers two independent set points, SetpointsSA.LO<br />

(for LOW COOL mode) <strong>and</strong> SetpointsSA.HI (for HIGH<br />

COOL mode).<br />

The occupied <strong>and</strong> unoccupied cooling set points can be<br />

found under Setpoints.<br />

ITEM EXPANSION RANGE UNITS CCN<br />

POINT DEFAULT<br />

OCSP Occupied<br />

Cool Setpoint<br />

55-80 dF OCSP 75<br />

UCSP Unoccupied<br />

Cool Setpoint<br />

75-95 dF UCSP 90<br />

The heat/cool set point offsets are found under ConfigurationD.LV.T.<br />

See Table 36.<br />

OHSP<br />

L.H.ON<br />

DMDLHON<br />

V.C. ON<br />

VAVOCON<br />

L.H.OF<br />

DMDLHOFF<br />

V.C. OF<br />

VAVOCOFF<br />

a48-8414<br />

Fig. 5 — VAV Occupied Period Trip Logic