06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Building Pressure Sensor (BP.S) — This configuration allows<br />

the reading of a building pressure sensor when enabled.<br />

This is automatically enabled when BP.CF = 2, 3, 4 or 5.<br />

Building Pressure (+/–) Range (BP.R) — This configuration<br />

establishes the range in in. wg that a 4 to 20 mA sensor will be<br />

scaled to. The control only allows sensors that measure both<br />

positive <strong>and</strong> negative pressure.<br />

Building Pressure SETP (BP.SP) — This set point is the<br />

building pressure control set point. If the unit is configured for<br />

a type of modulating building pressure control, then this is the<br />

set point that the control will control to.<br />

BP Setpoint Offset (BP.SO) — For building pressure configurations<br />

BP.CF=2, 3, <strong>and</strong> 4, this is the offset below the building<br />

pressure set point that the building pressure must fall below to<br />

turn off power exhaust control.<br />

Power Exhaust on Setp.1 (BP.P1) — When configured for<br />

building pressure control type BP.CF = 1 (constant volume<br />

two-stage control), the control will turn on the first power<br />

exhaust fan when the economizer’s position exceeds this set<br />

point.<br />

Power Exhaust on Setp.2 (BP.P2) — When configured for<br />

building pressure control type BP.CF = 1 (constant volume<br />

two-stage control), the control will turn on the second power<br />

exhaust fan when the economizer’s position exceeds this set<br />

point.<br />

VFD/Act. Fire Speed/Pos (BP.FS) — For BP.CF = 2, 3, 4,<br />

<strong>and</strong> 5, this configuration is the VFD speed position override<br />

when the control is in the purge <strong>and</strong> evacuation smoke control<br />

modes.<br />

VFD/Act. Min Speed/Pos (BP.MN) — For BP.CF = 2, 3, 4,<br />

<strong>and</strong> 5, this configuration is the minimum VFD speed/actuator<br />

position during building pressure control.<br />

VFD Maximum Speed/Pos (BP.MX) — For BP.CF = 3 <strong>and</strong><br />

5, this configuration is the maximum VFD speed during building<br />

pressure control.<br />

BP 1 Actuator Max Pos. (BP.1M) — For BP.CF = 2, this<br />

configuration is the maximum actuator no. 1 position during<br />

building pressure control.<br />

BP 2 Actuator Max Pos. (BP.2M) — For BP.CF = 2, this<br />

configuration is the maximum actuator no. 2 position during<br />

building pressure control.<br />

BP Hi Cap VFD Clamp Val. (BP.CL) — For BP.CF = 4, this<br />

configuration is a limit which creates a deadb<strong>and</strong> which controls<br />

the action of the second power exhaust relay.<br />

Fan Track Learn Enable (FT.CF) — For BP.CF = 5, this<br />

return/exhaust control configuration selects whether the fan<br />

tracking algorithm will make corrections over time <strong>and</strong> add a<br />

learned offset to FT.ST. If this configuration is set to No, the<br />

unit will try to control the delta cfm value between the supply<br />

<strong>and</strong> return VFDs only based on FT.ST.<br />

Fan Track Learn Rate (FT.TM) — For BP.CF = 5, this return/<br />

exhaust control configuration is a timer that affects corrections<br />

to the delta cfm operation. The smaller this value, the more often<br />

corrections may be made based on building pressure error.<br />

This configuration is only valid when FT.CF = Yes.<br />

Fan Track Initial DCFM (FT.ST) — For BP.CF = 5, this<br />

return/exhaust control configuration is the start point upon<br />

which corrections (offset) are made over time when FT.CF =<br />

Yes. It is the constant control point for delta cfm control when<br />

FT.CF = No.<br />

Fan Track Max Clamp (FT.MX) — For BP.CF = 5, this<br />

return/exhaust control configuration is the maximum positive<br />

delta cfm control value allowed unless outdoor air cfm control<br />

is available <strong>and</strong> then the delta cfm control value would<br />

be clamped to the outdoor air cfm value directly (see the<br />

Economizer section for a description of outdoor air cfm<br />

configuration).<br />

72<br />

Fan Track Max Correction (FT.AD) — For BP.CF = 5, this<br />

return/exhaust control configuration is the maximum correction<br />

allowed every time a correction is made based on FT.TM.<br />

This configuration is only valid when FT.CF = Yes.<br />

Fan Track Internal EEPROM (FT.OF) — For BP.CF = 5,<br />

this return/exhaust control internal EEPROM value is a learned<br />

correction that is stored in non-volatile RAM <strong>and</strong> adds to the<br />

offset when FT.CF = Yes. This value is stored once per day<br />

after the first correction. This configuration is only valid when<br />

FT.CF = Yes.<br />

Fan Track Internal Ram (FT.RM) — For BP.CF = 5, this<br />

return/exhaust control internal value is not a configuration but a<br />

run time correction that adds to the offset throughout the day<br />

when FT.CF = Yes. This value is only valid when FT.CF =<br />

Yes.<br />

Fan Track Reset Internal (FT.RS) — This option is a one<br />

time reset of the internal RAM <strong>and</strong> internal EEPROM stored<br />

offsets. If the system is not set up correctly <strong>and</strong> the offsets are<br />

incorrect, this learned value can be reset.<br />

Supply Air Cfm Config (SCF.C) — For BP.CF = 5, this configuration<br />

is set at the factory depending on whether an air foil<br />

or forward curve supply air fan is being used. This information<br />

is then used by the control to determine the correct cfm tables<br />

to be used when measuring supply air cfm.<br />

Building Pressure Run Rate (BP.TM) — For BP.CF = 2,3,4,<br />

<strong>and</strong> 5, this configuration is the PID run time rate.<br />

Building Pressure Proportional Gain (BP.P) — For BP.CF =<br />

2,3,4, <strong>and</strong> 5, this configuration is the PID Proportional Gain.<br />

Building Pressure Integral Gain (BP.I) — For BP.CF =<br />

2,3,4, <strong>and</strong> 5, this configuration is the PID Integral Gain.<br />

Building Pressure Derivative Gain (BP.D) — For BP.CF =<br />

2,3,4, <strong>and</strong> 5, this configuration is the PID Derivative Gain.<br />

BUILDING PRESSURE CONTROL OPERATION<br />

ConfigurationBPBP.CF = 1 (Constant Volume 2-Stage<br />

Control) — Two exhaust fan relays will be turned on <strong>and</strong> off<br />

based on economizer position to maintain building pressure<br />

control. The two trip set points are Configuration<br />

BPBP.P1 <strong>and</strong> ConfigurationBPBP.P2. If the economizer<br />

position is greater than or equal to BP.P1, then power exhaust<br />

relay 1 is energized, turning on the first stage. A 60-second timer<br />

is initialized. If the economizer falls 5% below the BP.P1,<br />

then the power exhaust fan relay is turned off. If the economizer<br />

position is less than BP.P1 <strong>and</strong> the 60-second timer has expired,<br />

the power exhaust fan relay is turned off. The same logic applies<br />

to the second power exhaust fan relay, except the BP.P2 trip<br />

point is monitored. If the economizer position is greater than or<br />

equal to BP.P2, then power exhaust relay 2 is energized, turning<br />

on the second stage. A 60-second timer is initialized. If the<br />

economizer is 5% below the BP.P2 the second power exhaust<br />

fan relay is turned off. If the economizer is less than BP.P2 <strong>and</strong><br />

the 60-second timer has expired, the power exhaust fan relay is<br />

turned off.<br />

ConfigurationBPBP.CF = 2 (Modulating Power Exhaust)<br />

— Control is accomplished with two LEN communicating actuators<br />

in t<strong>and</strong>em <strong>and</strong> one exhaust fan relay. If building pressure<br />

(PressuresAIR.PBP) rises above the building pressure<br />

set point (BP.SP) <strong>and</strong> the supply fan is on, building pressure<br />

control is initialized. Thereafter, if the supply fan relay<br />

goes off or if the building pressure drops below the BP.SP minus<br />

the building pressure set point offset (BP.SO) for 5 continuous<br />

minutes, building pressure control will be stopped. Any<br />

time building pressure control becomes active, the exhaust fan<br />

relay turns on, starting the dual exhaust fan motors. After the<br />

exhaust fan relay turns on, control is performed with a PID<br />

loop where:<br />

Error = BP – BP.SP<br />

K = 1000 * BP.TM / 60 (normalize the PID control for run rate)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!