Table 42 — Mode Trip Helper Table<br />

ITEM EXPANSION UNITS CCN POINT<br />

TRIP MODE TRIP HELPER<br />

UN.C.S Unoccup. Cool Mode <strong>Start</strong> dF UCCLSTRT<br />

UN.C.E Unoccup. Cool Mode End dF UCCL_END<br />

OC.C.S Occupied Cool Mode <strong>Start</strong> dF OCCLSTRT<br />

OC.C.E Occupied Cool Mode End dF OCCL_END<br />

TEMP Ctl.Temp RAT,SPT or Zone dF CTRLTEMP<br />

OC.H.E Occupied Heat Mode End dF OCHT_END<br />

OC.H.S Occupied Heat Mode <strong>Start</strong> dF OCHTSTRT<br />

UN.H.E Unoccup. Heat Mode End dF UCHT_END<br />

UN.H.S Unoccup. Heat Mode <strong>Start</strong> dF UCHTSTRT<br />

HVAC the current HVAC MODE String<br />

L.H.ON<br />

L.H.OF L.H.OF/2<br />

H.H.ON<br />

66.0 F<br />

67.5 F<br />

HEATING SET POINT<br />

Fig. 8 — Heating Offsets<br />

66.5 F<br />

a48-8407<br />

68.0 F<br />

The PID terms are calculated as follows:<br />

P = K * HW.P * error<br />

I = K * HW.I * error + “I” last time through<br />

D = K * HW.D * (error – error last time through)<br />

Where K = HW.TM/60 to normalize the effect of changing the<br />

run time rate.<br />

NOTE: The PID values should be not be modified without<br />

approval from Carrier.<br />

Freeze Status Switch Logic (InputsGEN.IFRZ.S) — If<br />

the freezestat input (FRZ) alarms, indicating that the coil is<br />

freezing, normal heat control is overridden <strong>and</strong> the following<br />

actions will be taken:<br />

1. Comm<strong>and</strong> the hot water coil actuator to 100%.<br />

2. Comm<strong>and</strong> the economizer damper to 0%.<br />

3. Comm<strong>and</strong> the supply fan on.<br />

Configuring Hydronic Heat to Communicate Via Actuator<br />

Serial Number — Every actuator used in the P Series control<br />

system has its own unique serial number. The rooftop control<br />

uses this serial number to communicate with the actuator.<br />

These serial numbers are programmed at the factory <strong>and</strong><br />

should not need changing. Should field replacement of an actuator<br />

become necessary, it will be required to configure the serial<br />

numbers of the new actuator. Four individual numbers make<br />

up this serial number <strong>and</strong> these can be programmed to match<br />

the serial number of the actuator in its Hydronic Heating Actuator<br />

Configs group, ACT.C (SN.1, SN.2, SN.3, SN.4). See<br />

Fig. 9.<br />

NOTE: The serial numbers for all actuators can be found<br />

inside the control doors of the unit as well as on the actuator<br />

itself. If an actuator is replaced in the field, it is a good idea to<br />

Table 43 — Hydronic Heat Configuration<br />

60<br />

remove the additional peel off serial number sticker on the<br />

actuator <strong>and</strong> cover up the old one inside the control doors.<br />

STAGED GAS HEATING CONTROL (HT.CF = 3) — As<br />

an option, the units with gas heat can be equipped with staged<br />

gas heat controls that will provide from 5 to 11 stages of heat<br />

capacity. This is intended for tempering mode <strong>and</strong> tempering<br />

economizer air when in a cooling mode <strong>and</strong> the dampers<br />

are fully closed. Tempering can also be used during a preoccupancy<br />

purge to prevent low temperature air from being<br />

delivered to the space. Tempering for both staged gas <strong>and</strong><br />

hydronic heat will be discussed in its own section. This section<br />

will focus on heat mode control, which ultimately is relevant to<br />

tempering, minus the consideration of the supply air heating<br />

control point.<br />

The staged gas configurations are located at the local<br />

display under ConfigurationHEATSG.CF. See Table 44.<br />

Staged Gas Heat Type (HT.ST) — This configuration instructs<br />

the control how many stages <strong>and</strong> in what order are they<br />

staged.<br />

Max Cap Change per Cycle (CAP.M) — This configuration<br />

limits the maximum change in capacity per PID run time<br />

cycle.<br />

S.Gas DB Min.dF/PID Rate (M.R.DB) — This configuration<br />

is a deadb<strong>and</strong> minimum temperature per second rate. See<br />

capacity calculation logic on next page for more details.<br />

St.Gas Temp.Dead B<strong>and</strong> (S.G.DB) — This configuration is a<br />

deadb<strong>and</strong> delta temperature. See capacity calculation logic on<br />

next page for more details.<br />

Heat Rise in dF/Sec Clamp (RISE) — This configuration<br />

clamps heat staging up when the leaving-air temperature is<br />

rising too fast.<br />

LAT Limit Config (LAT.L) — This configuration senses<br />

when leaving air temperature is outside a delta temperature<br />

b<strong>and</strong> around set point <strong>and</strong> allows staging to react quicker.<br />

Limit Switch Monitoring? (LIM.M) — This configuration<br />

allows the operation of the limit switch monitoring routine.<br />

This is always enabled for P Series as a limit switch temperature<br />

sensor is always present for staged gas operation.<br />

Limit Switch High Temp (SW.H.T) — This configuration is<br />

the temperature limit above which stages of heat will be shed.<br />

ACTUATOR SERIAL NUMBER<br />

NOT<br />

USED<br />

00850 - 30063 - 084 -083<br />

{<br />

{<br />

SN.1 SN.2 SN.3<br />

{<br />

{<br />

NOT<br />

USED<br />

SN.4<br />

SN.1 = 850<br />

SN.2 = 3<br />

SN.3 = 63<br />

SN.4 = 83<br />

a48-8507<br />

Fig. 9 — Actuator Serial Number Configuration<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

HH.CF HYDRONIC HEAT CONFIGS<br />

HW.P Hydronic Ctl.Prop. Gain 0 - 1.5 HW_PGAIN 1<br />

HW.I Hydronic Ctl.Integ. Gain 0 - 1.5 HW_IGAIN 1<br />

HW.D Hydronic Ctl.Derv. Gain 0 - 1.5 HW_DGAIN 1<br />

HW.TM Hydronic PID Rate Config 15 - 300 sec HOTWPIDR 90<br />

ACT.C HYDR.HEAT ACTUATOR CFGS.<br />

SN.1 Hydronic Ht.Serial Num.1 0 - 9999 HTCL_SN1 0<br />

SN.2 Hydronic Ht.Serial Num.2 0 - 6 HTCL_SN2 0<br />

SN.3 Hydronic Ht.Serial Num.3 0 - 9999 HTCL_SN3 0<br />

SN.4 Hydronic Ht.Serial Num.4 0 - 254 HTCL_SN4 0<br />

C.A.LM Hydr.Ht.Ctl.Ang.Lo Limit 0-90 HTCLCALM 85