06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Alarms <strong>and</strong> Alarm History for for any unresolved alarm codes<br />

<strong>and</strong> correct. Verify Humidi-MiZer configuration settings are<br />

correct for the site requirements. If alarm conditions are corrected<br />

<strong>and</strong> cleared, then operation of the compressors, fans, <strong>and</strong><br />

Humidi-MiZer valves may be verified by using the <strong>Service</strong><br />

Test mode. See page 35. In addition to the Cooling <strong>Service</strong><br />

Analysis (Table 71), see the Humidi-MiZer <strong>Service</strong> Analysis<br />

(Table 72) for more information.<br />

Thermistor Troubleshooting — The OAT, SAT,<br />

RAT, CCT, T55, T56, <strong>and</strong> T58 temperature sensors use 10K<br />

thermistors. Resistances at various temperatures are listed in<br />

Tables 75 <strong>and</strong> 76. The DTT uses an 86K thermistor. See Table<br />

77. The RGTA uses a 5K thermistor. See Tables 78 <strong>and</strong> 79.<br />

THERMISTOR/TEMPERATURE SENSOR CHECK — A<br />

high quality digital volt-ohmmeter is required to perform this<br />

check.<br />

1. With the unit powered down, remove the terminal strip of<br />

the thermistor being diagnosed from the appropriate control<br />

board (MBB-J8 or RCB-J6). Connect the digital<br />

LEGEND<br />

CB — Circuit Breaker<br />

TXV — Thermostatic Expansion Valve<br />

Table 71 — Cooling <strong>Service</strong> Analysis<br />

91<br />

ohmmeter across the appropriate thermistor terminals in<br />

the terminal strip.<br />

2. Using the resistance reading obtained, read the sensor<br />

temperature from the appropriate sensor table.<br />

3. To check thermistor accuracy, measure the temperature at<br />

the thermistor location with an accurate thermocouple–<br />

type temperature measuring instrument. Insulate thermocouple<br />

to avoid ambient temperatures from influencing<br />

reading. The temperature measured by the thermocouple<br />

<strong>and</strong> the temperature determined from the thermistor resistance<br />

reading should be within 5° F (3° C) if care was taken<br />

in applying thermocouple <strong>and</strong> taking readings.<br />

If a more accurate check is required, unit must be powered<br />

down <strong>and</strong> thermistor removed <strong>and</strong> checked at a known temperature<br />

(freezing point or boiling point of water) by measuring<br />

the resistance of the thermistor with the terminal strip removed<br />

from the control board. With the terminal strip plugged back<br />

into the control board <strong>and</strong> the unit powered up, compare the<br />

temperature determined from the resistance measurement with<br />

the value displayed by the control in the Temperatures menu<br />

using the scrolling marquee display.<br />

PROBLEM CAUSE REMEDY<br />

Compressor <strong>and</strong> Fan Will Not Power failure. Call power company.<br />

<strong>Start</strong>.<br />

Fuse blown or circuit breaker tripped. Check CB1,<br />

CB2, <strong>and</strong> CB3.<br />

Replace fuse or reset circuit breaker.<br />

Disconnect off. Power disconnect.<br />

Compressor time guard to prevent short cycling. Check using ComfortLink scrolling marquee.<br />

Thermostat or occupancy schedule set point not calling<br />

for Cooling.<br />

Check using ComfortLink scrolling marquee.<br />

Outdoor temperature too low. Check Compressor Lockout Temperature (MC.LO)<br />

using ComfortLink scrolling marquee.<br />

Active alarm. Check active alarms using ComfortLink scrolling<br />

marquee.<br />

Compressor Cycles (Other Than Insufficient line voltage. Determine cause <strong>and</strong> correct.<br />

Normally Satisfying Thermostat). Active alarm. Check active alarms using ComfortLink scrolling<br />

marquee.<br />

Compressors Operates<br />

Unit undersized for load. Decrease load or increase of size of unit.<br />

Continuously.<br />

Thermostat or occupancy schedule set point too low. Reset thermostat or schedule set point.<br />

Dirty air filters. Replace filters.<br />

Low refrigerant charge. Check pressure, locate leak, repair evacuate, <strong>and</strong><br />

recharge.<br />

Condenser coil dirty or restricted. Clean coil or remove restriction.<br />

Excessive Head Pressures. Loose condenser thermistors. Tighten thermistors.<br />

Dirty condenser coil. Clean coil.<br />

Refrigerant overcharge. Recover excess refrigerant.<br />

Faulty TXV. 1. Check TXV bulb mounting <strong>and</strong> secure tightly to<br />

suction line <strong>and</strong> insulate.<br />

2. Replace TXV (<strong>and</strong> filter drier) if stuck open or<br />

closed.<br />

Condenser air restricted or air short cycling. Determine cause <strong>and</strong> correct.<br />

Restriction in liquid tube. Remove restriction.<br />

Condenser Fans Not Operating. No Power to contactors. Fuse blown or plug at motor loose.<br />

Excessive Suction Pressure. High heat load. Check for sources <strong>and</strong> eliminate<br />

Faulty TXV. 1. Check TXV bulb mounting <strong>and</strong> secure tightly to<br />

suction line <strong>and</strong> insulate.<br />

2. Replace TXV (<strong>and</strong> filter drier) if stuck open or<br />

closed.<br />

Refrigerant overcharged. Recover excess refrigerant.<br />

Suction Pressure Too Low. Dirty air filters. Replace air filters.<br />

Low refrigerant charge. Check for leaks, repair, <strong>and</strong> recharge.<br />

Faulty TXV. 1. Check TXV bulb mounting <strong>and</strong> secure tightly to<br />

suction line <strong>and</strong> insulate.<br />

2. Replace TXV (<strong>and</strong> filter drier) if stuck open or<br />

closed.<br />

Insufficient evaporator airflow. Check belt tension. Check for other restrictions.<br />

Temperature too low in conditioned area (low returnair<br />

temperature).<br />

Reset thermostat or occupancy schedule.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!