APPENDIX B — CCN TABLES (cont)<br />

SERVICE-CONFIG TABLES (cont)<br />

TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT<br />

ECON<br />

Economizer Installed ? Yes/No ECON_ENA Yes<br />

Econ. Act.2 Installed ? Yes/No ECON_TWO No<br />

Economizer Min.Position 0 - 100 % ECONOMIN 5<br />

Economizer Max.Position 0 - 100 % ECONOMAX 98<br />

Economzr trim for sumZ ? Yes/No ECONTRIM Yes<br />

Econ ChangeOver Select 0 - 3 ECON_SEL 0<br />

OA Enthalpy ChgOvr Selct 1 - 5 OAEC_SEL 4<br />

Outdr.Enth Compare Value 18 - 28 BTU/LBM OAEN_CFG 24<br />

High OAT Lockout Temp 55 - 120 dF OAT_LOCK 60<br />

OA Dewpoint Temp Limit 50 - 62 dF OADEWCFG 55<br />

Outside Air RH Sensor Enable/Disable OARHSENS Disable<br />

Outdoor Air CFM Sensor Enable/Dsable OCFMSENS Dsable<br />

Economizer Min.Flow 0 - 20000 CFM OACFMMAX 2000<br />

IAQ Dem<strong>and</strong> Vent Min.Flow 0 - 20000 CFM OACFMMIN 0<br />

Econ.Min.Flow Deadb<strong>and</strong> 200 - 1000 CFM OACFM_DB 400<br />

Economizer Prop.Gain 0.7 - 3.0 EC_PGAIN 1<br />

Economizer Range Adjust 0.5 - 5 ^F EC_RANGE 2.5<br />

Economizer Speed Adjust 0.1 - 10 EC_SPEED 0.75<br />

Economizer Deadb<strong>and</strong> 0.1 - 2 ^F EC_DBAND 0.5<br />

Unoc Econ Free Cool Cfg 0-2 UEFC_CFG 0<br />

Unoc Econ Free Cool Time 0-720 min UEFCTIME 120<br />

Un.Ec.Free Cool OAT Lock 40-70 dF UEFCNTLO 50<br />

Econ Serial Number 1 0-9999 ECON_SN1<br />

Econ Serial Number 2 0-6 ECON_SN2<br />

Econ Serial Number 3 0-9999 ECON_SN3<br />

Econ Serial Number 4 0-254 ECON_SN4<br />

Econ Ctrl Angle Lo Limit 0-90 ECONCALM 85<br />

Econ 2 Serial Number 1 0-9999 ECN2_SN1<br />

Econ 2 Serial Number 2 0-6 ECN2_SN2<br />

Econ 2 Serial Number 3 0-9999 ECN2_SN3<br />

Econ 2 Serial Number 4 0-254 ECN2_SN4<br />

Ecn2 Ctrl Angle Lo Limit 0-90 ECN2CALM 85<br />

EDTR<br />

EDT Reset Configuration 0 - 3 EDRSTCFG 2<br />

Reset Ratio 0 - 10 RTIO 3<br />

Reset Limit 0 - 20 ^F LIMT 10<br />

EDT 4-20 ma Reset Input Enable/Disable EDTRSENS Disable<br />

HEAT<br />

Heating Control Type 0 - 4 HEATTYPE 0<br />

Heating Supply Air Setpt 80-120 dF SASPHEAT 85<br />

Occupied Heating Enabled Yes/No HTOCCENA No<br />

MBB Sensor Heat Relocate Yes/No HTLATMON No<br />

Staged Gas Heat Type 0 - 4 HTSTGTYP 0<br />

Max Cap Change per Cycle 5 - 45 HTCAPMAX 45<br />

S.Gas DB min.dF/PID Rate 0 - 5 HT_MR_DB 0.5<br />

St.Gas Temp. Dead B<strong>and</strong> 0 - 5 ^F HT_SG_DB 2<br />

Heat Rise dF/sec Clamp 0.05 - 0.2 HTSGRISE 0.06<br />

LAT Limit Config 0 - 20 ^F HTLATLIM 10<br />

Limit Switch Switch Monitoring? Yes/No HTLIMMON Yes<br />

Limit Switch High Temp 110 - 180 dF HT_LIMHI 170<br />

Limit Switch Low Temp 100 - 170 dF HT_LIMLO 160<br />

Heat Control Prop. Gain 0 - 1.5 HT_PGAIN 1<br />

Heat Control Derv. Gain 0 - 1.5 HT_DGAIN 1<br />

Heat PID Rate Config 60 - 300 sec HTSGPIDR 90<br />

Hydronic Ctl.Prop. Gain 0 - 1.5 HW_PGAIN 1<br />

Hydronic Ctl.Integ. Gain 0 - 1.5 HW_IGAIN 1<br />

Hydronic Ctl.Derv. Gain 0 - 1.5 HW_DGAIN 1<br />

Hydronic PID Rate Config 15 - 300 sec HOTWPIDR 90<br />

Hydronic Ht.Serial Num.1 0 - 9999 HTCL_SN1 0<br />

Hydronic Ht.Serial Num.2 0 - 6 HTCL_SN2 0<br />

Hydronic Ht.Serial Num.3 0 - 9999 HTCL_SN3 0<br />

Hydronic Ht.Serial Num.4 0 - 254 HTCL_SN4 0<br />

Hydr.Ht.Ctl.Ang.Lo Limit 0-90 HTCLCALM 85<br />

HUMD<br />

Humidifier Control Cfg. 0 - 4 HUMD_CFG 0<br />

Humidifier Setpoint 0 - 100 % HUSP 40<br />

Humidifier PID Run Rate 10 - 120 sec HUMDRATE 30<br />

Humidifier Prop. Gain 0 - 5 HUMID_PG 1<br />

Humidifier Integral Gain 0 - 5 HUMID_IG 0.3<br />

Humidifier Deriv. Gain 0 - 5 HUMID_DG 0.3<br />

Humd Serial Number 1 0 - 9999 HUMD_SN1 0<br />

Humd Serial Number 2 0 - 6 HUMD_SN2 0<br />

Humd Serial Number 3 0 - 9999 HUMD_SN3 0<br />

Humd Serial Number 4 0 - 254 HUMD_SN4 0<br />

Humd Ctrl Angle Lo Limit 0-90 HUMDCALM 85<br />