Table 72 — Humidi-MiZer ® <strong>Service</strong> Analysis<br />
PROBLEM CAUSE REMEDY<br />
Circuit B compressors unavailable Check alarm history for general cooling mode operation problems.<br />
See "Cooling Troubleshooting," Table 71.<br />
Check for Circuit B compressors locked out.<br />
General Cooling Mode problem See "Cooling Troubleshooting," Table 71.<br />
Humidi-MiZer relative humidity sensor Check that a relative humidity sensor is connected <strong>and</strong> that the<br />
not functioning - RARH, SPRH, or field<br />
installed RH sensor<br />
appropriate sensor is configured in the unit software, (ConfigurationDEHUD.SEN).<br />
See page 80.<br />
Subcooling Mode Will Not<br />
Activate<br />
Check for 24VDC from CEM (RARH, SPRH).<br />
Check 4-20 ma signal from sensor.<br />
Humidi-MiZer temperature sensors not<br />
functioning - SAT, CCT<br />
See "Thermistor Troubleshooting," see page 91.<br />
No Dehumidification dem<strong>and</strong> See "No Dehumidification Dem<strong>and</strong>, below.<br />
3-way valve malfunction See "3-Way valve malfunction," below.<br />
Unit control software is not configured<br />
for Humidi-MiZer system<br />
Check that the unit is configured for Humidi-MiZer (ConfigurationDEHUD.SEL).<br />
Circuit B compressors unavailabe Check alarm history for general cooling mode operation problems.<br />
See "Cooling Troubleshooting," Table 71.<br />
Check for Circuit B compressors locked out.<br />
Humidi-MiZer relative humidity sensor Check that a relative humidity sensor is connected <strong>and</strong> that the<br />
not functioning - RARH, SPRH, or field<br />
installed RH sensor<br />
appropriate sensor is configured in the unit software, (ConfigurationDEHUD.SEN).<br />
See page 80.<br />
Reheat Mode Will Not Activate<br />
Check for 24 VDC from CEM (RARH, SPRH).<br />
Check 4-20 mA signal from sensor.<br />
No Dehumidification dem<strong>and</strong> See "No Dehumidification Dem<strong>and</strong>,” below.<br />
3-way valve malfunction See "3-Way Valve Malfunction."<br />
Unit control software is not configured<br />
for Humidi-MiZer system<br />
Check that the unit is configured for Humidi-MiZer (Configuration<br />
DEHUD.SEL).<br />
Relative Humidity setpoint is too low -<br />
discrete input (Humidistat, Thermidistat,<br />
etc.)<br />
Check/reduce setting on discrete humidity input device.<br />
No Dehumidification Dem<strong>and</strong><br />
Relative Humidity setpoint is too low -<br />
RH sensor<br />
Check the dehumidification relative humidity trip point (ConfigurationDEHUD.RH.S)<br />
Software configuration error for the<br />
type of relative humidity sensor being<br />
Check that the unit software is configured for the correct relative<br />
humidity sensor (ConfigurationDEHUD.SEN). D.SEN = 1:<br />
used<br />
RARH, 2:SPRH, 3: Discrete Input. See page 80.<br />
No humidity signal Check wiring <strong>and</strong> sensor.<br />
No 24V signal to input terminals Check using <strong>Service</strong> Test mode.<br />
Check wiring.<br />
Check transformer <strong>and</strong> circuit breakers.<br />
Check RCB relay output.<br />
3-Way Valve Malfunction Solenoid coil burnout Check continuous over-voltage is less than 10%.<br />
Check continuous under-voltage is less than 15%.<br />
Check for missing coil assembly parts.<br />
Replace solenoid coil.<br />
Stuck valve Replace valve. Replace filter drier.<br />
Humid-MiZer Vent Reheat Set Point is<br />
too low<br />
Check the Vent Reheat Set Point Selection (Configuration<br />
DEHUD.V.CF) <strong>and</strong> Vent Reheat Setpoint (Configuration<br />
DEHU D.V.HT). If used, check the Vent Reheat RAT Offset<br />
also (ConfigurationDEHUD.V.RA). See page XX for Humid-<br />
Mizer controls set-up<br />
Evaporator discharge temperature See "Thermistor Troubleshooting,” page 91.<br />
(CCT) or Supply air temperature (SAT)<br />
thermistor is reading incorrectly.<br />
Check if SAT thermistor is in a location that is measuring stratified<br />
air<br />
Unit Initiates a Humidi-mizer<br />
Reheat Mode, but Supply Air<br />
Temperature is Overheating/<br />
Overcooling the Space<br />
Valve controlling gas bypass around<br />
the condenser is not functioning<br />
properly<br />
Valve controlling refrigerant flow to the<br />
condenser is not functioning properly<br />
See "Modulating Valves Not Functioning Properly"<br />
See "Modulating Valves Not Functioning Properly"<br />
Modulating valves are not calibrated<br />
properly<br />
Run valve calibration through <strong>Service</strong> Test<br />
Unit control software indicates a<br />
Humidi-MiZer Reheat Mode, but the 3way<br />
valve is not functioning properly<br />
See "3-Way Valve Malfunction"<br />
Unit is not sized to meet the load at the Check product data tables or ECAT for rated capacity at current<br />
current entering air <strong>and</strong> outdoor<br />
conditions.<br />
entering air <strong>and</strong> outdoor conditions.<br />
92