Table 72 — Humidi-MiZer ® <strong>Service</strong> Analysis<br />

PROBLEM CAUSE REMEDY<br />

Circuit B compressors unavailable Check alarm history for general cooling mode operation problems.<br />

See "Cooling Troubleshooting," Table 71.<br />

Check for Circuit B compressors locked out.<br />

General Cooling Mode problem See "Cooling Troubleshooting," Table 71.<br />

Humidi-MiZer relative humidity sensor Check that a relative humidity sensor is connected <strong>and</strong> that the<br />

not functioning - RARH, SPRH, or field<br />

installed RH sensor<br />

appropriate sensor is configured in the unit software, (ConfigurationDEHUD.SEN).<br />

See page 80.<br />

Subcooling Mode Will Not<br />

Activate<br />

Check for 24VDC from CEM (RARH, SPRH).<br />

Check 4-20 ma signal from sensor.<br />

Humidi-MiZer temperature sensors not<br />

functioning - SAT, CCT<br />

See "Thermistor Troubleshooting," see page 91.<br />

No Dehumidification dem<strong>and</strong> See "No Dehumidification Dem<strong>and</strong>, below.<br />

3-way valve malfunction See "3-Way valve malfunction," below.<br />

Unit control software is not configured<br />

for Humidi-MiZer system<br />

Check that the unit is configured for Humidi-MiZer (ConfigurationDEHUD.SEL).<br />

Circuit B compressors unavailabe Check alarm history for general cooling mode operation problems.<br />

See "Cooling Troubleshooting," Table 71.<br />

Check for Circuit B compressors locked out.<br />

Humidi-MiZer relative humidity sensor Check that a relative humidity sensor is connected <strong>and</strong> that the<br />

not functioning - RARH, SPRH, or field<br />

installed RH sensor<br />

appropriate sensor is configured in the unit software, (ConfigurationDEHUD.SEN).<br />

See page 80.<br />

Reheat Mode Will Not Activate<br />

Check for 24 VDC from CEM (RARH, SPRH).<br />

Check 4-20 mA signal from sensor.<br />

No Dehumidification dem<strong>and</strong> See "No Dehumidification Dem<strong>and</strong>,” below.<br />

3-way valve malfunction See "3-Way Valve Malfunction."<br />

Unit control software is not configured<br />

for Humidi-MiZer system<br />

Check that the unit is configured for Humidi-MiZer (Configuration<br />

DEHUD.SEL).<br />

Relative Humidity setpoint is too low -<br />

discrete input (Humidistat, Thermidistat,<br />

etc.)<br />

Check/reduce setting on discrete humidity input device.<br />

No Dehumidification Dem<strong>and</strong><br />

Relative Humidity setpoint is too low -<br />

RH sensor<br />

Check the dehumidification relative humidity trip point (ConfigurationDEHUD.RH.S)<br />

Software configuration error for the<br />

type of relative humidity sensor being<br />

Check that the unit software is configured for the correct relative<br />

humidity sensor (ConfigurationDEHUD.SEN). D.SEN = 1:<br />

used<br />

RARH, 2:SPRH, 3: Discrete Input. See page 80.<br />

No humidity signal Check wiring <strong>and</strong> sensor.<br />

No 24V signal to input terminals Check using <strong>Service</strong> Test mode.<br />

Check wiring.<br />

Check transformer <strong>and</strong> circuit breakers.<br />

Check RCB relay output.<br />

3-Way Valve Malfunction Solenoid coil burnout Check continuous over-voltage is less than 10%.<br />

Check continuous under-voltage is less than 15%.<br />

Check for missing coil assembly parts.<br />

Replace solenoid coil.<br />

Stuck valve Replace valve. Replace filter drier.<br />

Humid-MiZer Vent Reheat Set Point is<br />

too low<br />

Check the Vent Reheat Set Point Selection (Configuration<br />

DEHUD.V.CF) <strong>and</strong> Vent Reheat Setpoint (Configuration<br />

DEHU D.V.HT). If used, check the Vent Reheat RAT Offset<br />

also (ConfigurationDEHUD.V.RA). See page XX for Humid-<br />

Mizer controls set-up<br />

Evaporator discharge temperature See "Thermistor Troubleshooting,” page 91.<br />

(CCT) or Supply air temperature (SAT)<br />

thermistor is reading incorrectly.<br />

Check if SAT thermistor is in a location that is measuring stratified<br />

air<br />

Unit Initiates a Humidi-mizer<br />

Reheat Mode, but Supply Air<br />

Temperature is Overheating/<br />

Overcooling the Space<br />

Valve controlling gas bypass around<br />

the condenser is not functioning<br />

properly<br />

Valve controlling refrigerant flow to the<br />

condenser is not functioning properly<br />

See "Modulating Valves Not Functioning Properly"<br />

See "Modulating Valves Not Functioning Properly"<br />

Modulating valves are not calibrated<br />

properly<br />

Run valve calibration through <strong>Service</strong> Test<br />

Unit control software indicates a<br />

Humidi-MiZer Reheat Mode, but the 3way<br />

valve is not functioning properly<br />

See "3-Way Valve Malfunction"<br />

Unit is not sized to meet the load at the Check product data tables or ECAT for rated capacity at current<br />

current entering air <strong>and</strong> outdoor<br />

conditions.<br />

entering air <strong>and</strong> outdoor conditions.<br />