* 41 for Supply Fan Motor VFD, 42 for Exhaust Fan Motor VFD.<br />

APPENDIX D — VFD INFORMATION (cont)<br />

Table B — VFD Parameters Configured by Carrier Assistant<br />

PARAMETER GROUP PARAMETER TITLE PARAMETER INDEX HVAC DEFAULT CARRIER DEFAULT<br />

Options COMM PROT SEL 9802 NOT SEL (0) LEN (6)<br />

EFB Protocol<br />

PARAMETER<br />

GROUP<br />

<strong>Start</strong>-<strong>Up</strong> Data<br />

EFB PROTOCOL ID 5301 0000 hex 0601 hex<br />

EFB STATION ID 5302 0 41/42*<br />

EFB BAUD RATE 5303 9.6 kb/s 38.4 kb/s<br />

EFB PARITY 5304 8 NONE 1 8 NONE 1<br />

EFB CTRL PROFILE 5305 ABB DRV LIM DCU PROFILE<br />

Table C — VFD Parameters with CCN Points Configured with ComfortLink <strong>Controls</strong><br />

PARAMETER<br />

TITLE<br />

MOTOR NOM<br />

VOLT<br />

MOTOR NOM<br />

CURR<br />

MOTOR NOM<br />

FREQ<br />

MOTOR NOM<br />

SPEED<br />

MOTOR NOM<br />

POWER<br />

PARAMETER<br />

INDEX<br />

HVAC DEFAULT<br />

Table D — VFD Parameters Configured with ComfortLink <strong>Controls</strong><br />

195<br />

CARRIER<br />

DEFAULT<br />

CCN POINT<br />

SUPPLY FAN<br />

VFD<br />

CCN POINT<br />

EXHAUST FAN<br />

VFD<br />

9905 230V,460V,575V *TBD* VFD1NVLT VFD2NVLT<br />

9906 1.0*In *TBD* VFD1NAMP VFD2NAMP<br />

9907 60 Hz 60 Hz VFD1NFRQ VFD2NFRQ<br />

9908 1750 rpm 1750 rpm VFD1NRPM VFD2NRPM<br />

9909 1.0*Pn *TBD* VFD1NPWR VFD2NPWR<br />

<strong>Start</strong>/Stop/Dir DIRECTION 1003 FORWARD REQUEST VFD1MDIR VFD2MDIR<br />

Accel/Decel<br />

ACCELER TIME 1 2202 30.0s 30.0s VFD1ACCL VFD2ACCL<br />

DECELER TIME 1 2203 30.0s 30.0s VFD1DECL VFD2DECL<br />

Motor Control SWITCHING FREQ 2606 4 kHz 8 kHz VFD1SWFQ VFD2SWFQ<br />

PARAMETER GROUP PARAMETER TITLE PARAMETER INDEX HVAC DEFAULT CARRIER DEFAULT<br />

<strong>Start</strong>/Stop/Dir EXT1 COMMANDS 1001 DI1 COMM (10)<br />

Reference Select REF1 SELECT 1103 AI1 COMM (8)<br />

Constant Speeds CONST SPEED SEL 1201 DI3 NOT SEL (0)<br />

CONST SPEED 7 1208 60 Hz 0 Hz<br />

System <strong>Controls</strong> RUN ENABLE 1601 NOT SEL NOT SEL (0)<br />

FAULT RESET SEL 1604 KEYPAD COMM (8)<br />

START ENABLE 1 1608 DI4 DI4 (4)<br />

<strong>Start</strong>/Stop START FUNCTION 2101 SCALAR FLYSTART AUTO (1)<br />

STOP FUNCTION 2102 COAST RAMP (2)<br />

Fault Functions COMM FAULT FUNC 3018 NOT SEL CONST SP 7 (2)<br />

COMM FAULT TIME 3019 10.0 s 10.0 s