CONTROLS SET POINT AND CONFIGURATION LOG<br />

MODEL NUMBER: Software Version<br />

SERIAL NUMBER: MBB CESR131461--<br />

DATE: RXB CESR131465--<br />

TECHNICIAN: EXB CESR131465--<br />

NAVI CESR130227--<br />

SCB CESR131226--<br />

CEM CESR131174--<br />

MARQ CESR131171--<br />

CXB CESR131173--<br />

EXV CESR131172--<br />

ITEM EXPANSION RANGE DEFAULT SETTING<br />

UNIT UNIT CONFIGURATION<br />

C.TYP Machine Control Type 1 - 4 (multi-text strings) 4<br />

SIZE Unit Size (30-100) 3 - 100 30<br />

FN.MD Fan Mode (0=Auto, 1=Cont) 1 - 1 (multi-text strings) 1<br />

RM.CF Remote Switch Config 0 - 3 (multi-text strings) 0<br />

CEM CEM Module Installed Yes/No No<br />

TCS.C Temp.Cmp.Strt.Cool Factr 0 - 60 min 0<br />

TCS.H Temp.Cmp.Strt.Heat Factr 0 - 60 min 0<br />

SFS.S Fan Fail Shuts Down Unit Yes/No No<br />

SFS.M Fan Stat Monitoring Type 0 - 2 (multi-text strings) 0<br />

VAV.S VAV Unocc.Fan Retry Time 0 - 720 min 50<br />

50.HZ 50 Hertz Unit ? Yes/No No<br />

MAT.S MAT Calc Config 0 - 2 (multi-text strings) 1<br />

MAT.R Reset MAT Table Entries? Yes/No No<br />

MAT.D MAT Outside Air Default 0 - 100% 20<br />

ALTI Altitude……..in feet: 0 - 60000 0<br />

DLAY <strong>Start</strong>up Delay Time 0 - 900 secs 0<br />

AUX.R Auxiliary Relay Config 0 - 3 (multi-text strings) 0<br />

SENS INPUT SENSOR CONFIG<br />

SENSSPT.S Space Temp Sensor Enable/Disable Disable<br />

SENSSP.O.S Space Temp Offset Sensor Enable/Disable Disable<br />

SENSSP.O.R Space Temp Offset Range 1 - 10 5<br />

SENSSRH.S Space Air RH Sensor Enable/Disable Disable<br />

SENSRRH.S Return Air RH Sensor Enable/Disable Disable<br />

SENSFLT.S Filter Stat.Sw.Enabled ? Enable/Disable Disable<br />

COOL COOLING CONFIGURATION<br />

A1.EN Enable Compressor A1 Enable/Disable Enable<br />

A2.EN Enable Compressor A2 Enable/Disable Enable<br />

A3.EN Enable Compressor A3 Enable/Disable Enable<br />

B1.EN Enable Compressor B1 Enable/Disable Enable<br />

B2.EN Enable Compressor B2 Enable/Disable Enable<br />

B3.EN Enable Compressor B3 Enable/Disable Enable<br />

CS.A1 CSB A1 Feedback Alarm Enable/Disable Enable<br />

CS.A2 CSB A2 Feedback Alarm Enable/Disable Enable<br />

CS.A3 CSB A3 Feedback Alarm Enable/Disable Enable<br />

CS.B1 CSB B1 Feedback Alarm Enable/Disable Enable<br />

CS.B2 CSB B2 Feedback Alarm Enable/Disable Enable<br />

CS.B3 CSB B3 Feedback Alarm Enable/Disable Enable<br />

Z.GN Capacity Threshold Adjst 0.1 - 10 1<br />

MC.LO Compressor Lockout Temp -20 - 55 dF 40<br />

LLAG Lead/Lag Configuration 0 - 2 (multi-text strings) 0<br />

M.M. Motor Master Control ? Yes/No No<br />

SCT.H Maximum Condenser Temp 100 - 150 dF 115<br />

SCT.L Minimum Condenser Temp 40 - 90 dF 72<br />

DG.A1 A1 is a Digital Scroll Yes/No No<br />

MC.A1 A1 Min Digital Capacit 10 - 100% 50<br />

DS.AP Dig Scroll Adjust Delta 0 - 100% 100<br />

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice <strong>and</strong> without incurring obligations.<br />

Catalog No. 04-53480071-01 Printed in U.S.A. Form 48/50P-2T Pg CL-1 1-10 Replaces: 48/50P-1T