Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Table 38 — Run Status Cool Display<br />
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />
COOL COOLING INFORMATION<br />
C.CAP Current Running Capacity % CAPTOTAL<br />
CUR.S Current Cool Stage COOL_STG<br />
REQ.S Requested Cool Stage CL_STAGE<br />
MAX.S Maximum Cool Stages CLMAXSTG<br />
DEM.L Active Dem<strong>and</strong> Limit % DEM_LIM forcible<br />
SUMZ COOL CAP. STAGE CONTROL<br />
SMZ Capacity Load Factor -100 – +100 SMZ<br />
ADD.R Next Stage EDT Decrease ^F ADDRISE<br />
SUB.R Next Stage EDT Increase ^F SUBRISE<br />
R.PCT Rise Per Percent Capacity RISE_PCT<br />
Y.MIN Cap Deadb<strong>and</strong> Subtracting Y_MINUS<br />
Y.PLU Cap Deadb<strong>and</strong> Adding Y_PLUS<br />
Z.MIN Cap Threshold Subtracting Z_MINUS<br />
Z.PLU Cap Threshold Adding Z_PLUS<br />
H.TMP High Temp Cap Override HI_TEMP<br />
L.TMP Low Temp Cap Override LOW_TEMP<br />
PULL Pull Down Cap Override PULLDOWN<br />
SLOW Slow Change Cap Override SLO_CHNG<br />
HMZR HUMIDIMIZER<br />
CAPC Humidimizer Capacity HMZRCAPC<br />
C.EXV Condenser EXV Position COND_EXV<br />
B.EXV Bypass EXV Position BYP_EXV<br />
RHV Humidimizer 3-Way Valve HUM3WVAL<br />
C.CPT Cooling Control Point COOLCPNT<br />
EDT Evaporator Discharge Tmp EDT<br />
H.CPT Heating Control Point HEATCPNT<br />
LAT Leaving Air Temperature LAT<br />
Pull Down Cap Override (PULL) — If the error from set<br />
point is above 4F, <strong>and</strong> the rate of change is less than –1F per<br />
minute, then pulldown is in effect, <strong>and</strong> “SUM” is set to 0. This<br />
keeps mechanical cooling stages from being added when the<br />
error is very large, but there is no load in the space. Pulldown<br />
for units is expected to rarely occur, but is included for the rare<br />
situation when it is needed. Most likely pulldown will occur<br />
when mechanical cooling first becomes available shortly after<br />
the control goes into an occupied mode (after a warm unoccupied<br />
mode).<br />
Slow Change Cap Override (SLOW) — With a rooftop unit,<br />
the design rise at 100% total unit capacity is generally around<br />
30 F. For a unit with 4 stages, each stage represents about<br />
7.5F of change to EDT. If stages could reliably be cycled at<br />
very fast rates, the set point could be maintained very precisely.<br />
Since it is not desirable to cycle compressors more than 6 cycles<br />
per hour, slow change override takes care of keeping the<br />
PID under control when “relatively” close to set point.<br />
Humidi-MiZer® Capacity (CAPC) — This variable represents<br />
the total reheat capacity currently in use during a Humidi-<br />
MiZer mode. A value of 100% indicates that all of the discharge<br />
gas is being bypassed around the condenser <strong>and</strong> into the<br />
Humidi-MiZer dehumidification/reheat coil (maximum reheat).<br />
A value of 0% indicates that all of the flow is going<br />
through the condenser before entering the Humidi-MiZer dehumidification/reheat<br />
coil (dehum/subcooling mode).<br />
Condenser EXV Position (C.EXV) — This variable represents<br />
the position of the condenser EXV (percent open).<br />
Bypass EXV Position (B.EXV) — This variable represents<br />
the position of the bypass EXV (percent open).<br />
Humidi-MiZer 3-Way Valve (RHV) — This variable represents<br />
the position of the 3-way valve used to switch the unit<br />
into <strong>and</strong> out of a Humidi-MiZer mode. A value of 0 indicates<br />
that the unit is in a st<strong>and</strong>ard cooling mode. A value of 1 indicates<br />
that the unit has energized the 3-way valve <strong>and</strong> entered<br />
into a Humidi-MiZer mode.<br />
Cooling Control Point (C.CPT) — Displays the current cooling<br />
control point (a target value for air temperature leaving the<br />
evaporator coil location). During a Humidi-MiZer mode, this<br />
variable will take on the value of the dehumidify cool set point<br />
(D.C.SP COOL). Compressors will stage up or down to<br />
meet this temperature.<br />
51<br />
Evaporator Discharge Temperature (EDT) — Displays the<br />
temperature measured between the evaporator coils <strong>and</strong> the<br />
Humidi-MiZer dehumidification/reheat coil. Units configured<br />
with Humidi-MiZer have a thermistor grid installed between<br />
these two coils to provide the measurement. This temperature<br />
can also be read at TemperaturesAIR.TCCT.<br />
Heating Control Point (H.CPT) — Displays the current heating<br />
control point for Humidi-MiZer. During a Reheat mode,<br />
this temperature will be either an offset subtracted from return<br />
air temperature (D.V.RA) or the Vent Reheat Set Point<br />
(D.V.HT). During a Dehumidification Mode, this temperature<br />
will take on the value of the original cooling control point so<br />
that the supply air is reheated just enough to meet the sensible<br />
dem<strong>and</strong> in the space. The Humidi-Mizer modulating valves<br />
will adjust to meet this temperature set point.<br />
Leaving Air Temperature (LAT) — Displays the leaving air<br />
temperature after the Humidi-MiZer reheat/dehumidification<br />
coil.<br />
SumZ <strong>Operation</strong> — The SumZ algorithm is an adaptive PID<br />
style of control. The PID is programmed within the control <strong>and</strong><br />
the relative speed of staging can only be influenced by the user<br />
through the adjustment of the Z.GN configuration, described in<br />
the reference section. The capacity control algorithm uses a<br />
modified PID algorithm, with a self adjusting gain which<br />
compensates for varying conditions, including changing flow<br />
rates across the evaporator coil.<br />
Previous implementations of SumZ made static assumptions<br />
about the actual size of the next capacity jump up or<br />
down. This control uses a “rise per percent capacity” technique<br />
in the calculation of SumZ, instead of the previous “rise per<br />
stage” method. For each jump, up or down in capacity, the<br />
control will know beforeh<strong>and</strong> the exact capacity change<br />
brought on. Better overall staging control can be realized with<br />
this technique.<br />
SUM Calculation — The PID calculation of the “SUM” is<br />
evaluated once every 80 seconds.<br />
SUM = Error + “SUM last time through” + (3 * Error Rate)<br />
Where:<br />
SUM = the PID calculation<br />
Error = EDT – Cooling Control Point<br />
Error Rate = Error – “Error last time through”