06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Table 38 — Run Status Cool Display<br />

ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />

COOL COOLING INFORMATION<br />

C.CAP Current Running Capacity % CAPTOTAL<br />

CUR.S Current Cool Stage COOL_STG<br />

REQ.S Requested Cool Stage CL_STAGE<br />

MAX.S Maximum Cool Stages CLMAXSTG<br />

DEM.L Active Dem<strong>and</strong> Limit % DEM_LIM forcible<br />

SUMZ COOL CAP. STAGE CONTROL<br />

SMZ Capacity Load Factor -100 – +100 SMZ<br />

ADD.R Next Stage EDT Decrease ^F ADDRISE<br />

SUB.R Next Stage EDT Increase ^F SUBRISE<br />

R.PCT Rise Per Percent Capacity RISE_PCT<br />

Y.MIN Cap Deadb<strong>and</strong> Subtracting Y_MINUS<br />

Y.PLU Cap Deadb<strong>and</strong> Adding Y_PLUS<br />

Z.MIN Cap Threshold Subtracting Z_MINUS<br />

Z.PLU Cap Threshold Adding Z_PLUS<br />

H.TMP High Temp Cap Override HI_TEMP<br />

L.TMP Low Temp Cap Override LOW_TEMP<br />

PULL Pull Down Cap Override PULLDOWN<br />

SLOW Slow Change Cap Override SLO_CHNG<br />

HMZR HUMIDIMIZER<br />

CAPC Humidimizer Capacity HMZRCAPC<br />

C.EXV Condenser EXV Position COND_EXV<br />

B.EXV Bypass EXV Position BYP_EXV<br />

RHV Humidimizer 3-Way Valve HUM3WVAL<br />

C.CPT Cooling Control Point COOLCPNT<br />

EDT Evaporator Discharge Tmp EDT<br />

H.CPT Heating Control Point HEATCPNT<br />

LAT Leaving Air Temperature LAT<br />

Pull Down Cap Override (PULL) — If the error from set<br />

point is above 4F, <strong>and</strong> the rate of change is less than –1F per<br />

minute, then pulldown is in effect, <strong>and</strong> “SUM” is set to 0. This<br />

keeps mechanical cooling stages from being added when the<br />

error is very large, but there is no load in the space. Pulldown<br />

for units is expected to rarely occur, but is included for the rare<br />

situation when it is needed. Most likely pulldown will occur<br />

when mechanical cooling first becomes available shortly after<br />

the control goes into an occupied mode (after a warm unoccupied<br />

mode).<br />

Slow Change Cap Override (SLOW) — With a rooftop unit,<br />

the design rise at 100% total unit capacity is generally around<br />

30 F. For a unit with 4 stages, each stage represents about<br />

7.5F of change to EDT. If stages could reliably be cycled at<br />

very fast rates, the set point could be maintained very precisely.<br />

Since it is not desirable to cycle compressors more than 6 cycles<br />

per hour, slow change override takes care of keeping the<br />

PID under control when “relatively” close to set point.<br />

Humidi-MiZer® Capacity (CAPC) — This variable represents<br />

the total reheat capacity currently in use during a Humidi-<br />

MiZer mode. A value of 100% indicates that all of the discharge<br />

gas is being bypassed around the condenser <strong>and</strong> into the<br />

Humidi-MiZer dehumidification/reheat coil (maximum reheat).<br />

A value of 0% indicates that all of the flow is going<br />

through the condenser before entering the Humidi-MiZer dehumidification/reheat<br />

coil (dehum/subcooling mode).<br />

Condenser EXV Position (C.EXV) — This variable represents<br />

the position of the condenser EXV (percent open).<br />

Bypass EXV Position (B.EXV) — This variable represents<br />

the position of the bypass EXV (percent open).<br />

Humidi-MiZer 3-Way Valve (RHV) — This variable represents<br />

the position of the 3-way valve used to switch the unit<br />

into <strong>and</strong> out of a Humidi-MiZer mode. A value of 0 indicates<br />

that the unit is in a st<strong>and</strong>ard cooling mode. A value of 1 indicates<br />

that the unit has energized the 3-way valve <strong>and</strong> entered<br />

into a Humidi-MiZer mode.<br />

Cooling Control Point (C.CPT) — Displays the current cooling<br />

control point (a target value for air temperature leaving the<br />

evaporator coil location). During a Humidi-MiZer mode, this<br />

variable will take on the value of the dehumidify cool set point<br />

(D.C.SP COOL). Compressors will stage up or down to<br />

meet this temperature.<br />

51<br />

Evaporator Discharge Temperature (EDT) — Displays the<br />

temperature measured between the evaporator coils <strong>and</strong> the<br />

Humidi-MiZer dehumidification/reheat coil. Units configured<br />

with Humidi-MiZer have a thermistor grid installed between<br />

these two coils to provide the measurement. This temperature<br />

can also be read at TemperaturesAIR.TCCT.<br />

Heating Control Point (H.CPT) — Displays the current heating<br />

control point for Humidi-MiZer. During a Reheat mode,<br />

this temperature will be either an offset subtracted from return<br />

air temperature (D.V.RA) or the Vent Reheat Set Point<br />

(D.V.HT). During a Dehumidification Mode, this temperature<br />

will take on the value of the original cooling control point so<br />

that the supply air is reheated just enough to meet the sensible<br />

dem<strong>and</strong> in the space. The Humidi-Mizer modulating valves<br />

will adjust to meet this temperature set point.<br />

Leaving Air Temperature (LAT) — Displays the leaving air<br />

temperature after the Humidi-MiZer reheat/dehumidification<br />

coil.<br />

SumZ <strong>Operation</strong> — The SumZ algorithm is an adaptive PID<br />

style of control. The PID is programmed within the control <strong>and</strong><br />

the relative speed of staging can only be influenced by the user<br />

through the adjustment of the Z.GN configuration, described in<br />

the reference section. The capacity control algorithm uses a<br />

modified PID algorithm, with a self adjusting gain which<br />

compensates for varying conditions, including changing flow<br />

rates across the evaporator coil.<br />

Previous implementations of SumZ made static assumptions<br />

about the actual size of the next capacity jump up or<br />

down. This control uses a “rise per percent capacity” technique<br />

in the calculation of SumZ, instead of the previous “rise per<br />

stage” method. For each jump, up or down in capacity, the<br />

control will know beforeh<strong>and</strong> the exact capacity change<br />

brought on. Better overall staging control can be realized with<br />

this technique.<br />

SUM Calculation — The PID calculation of the “SUM” is<br />

evaluated once every 80 seconds.<br />

SUM = Error + “SUM last time through” + (3 * Error Rate)<br />

Where:<br />

SUM = the PID calculation<br />

Error = EDT – Cooling Control Point<br />

Error Rate = Error – “Error last time through”

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!