Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
the motor position to be configured at initial unit start-up. The<br />
motor(s) is located on the economizer <strong>and</strong> can be reached<br />
through the filter access door.<br />
THERMISTORS AND PRESSURE TRANSDUCERS —<br />
The unit is equipped with several thermistors for measurement<br />
of temperatures. The thermistors are summarized in Table 102.<br />
The units have two pressure transducers that are connected<br />
to the low side of the system. These two pressure transducers<br />
measure the low side pressure <strong>and</strong> are used for low pressure<br />
protection <strong>and</strong> coil freeze protection.<br />
The units also have two pressure transducers that are connected<br />
to the high side of the system. These two pressure transducers<br />
measure the discharge pressure <strong>and</strong> are used to cycle the<br />
condenser fans to maintain head pressure.<br />
By using the high <strong>and</strong> low side pressure transducers, the<br />
ComfortLink controls display the high <strong>and</strong> low side pressures<br />
<strong>and</strong> saturation temperatures <strong>and</strong> a normal gage set is not<br />
required.<br />
SMOKE DETECTOR — The units can be equipped with an<br />
accessory smoke detector located in the return air. The detector<br />
is wired to the ComfortLink controls <strong>and</strong>, if activated, will stop<br />
the unit by means of a special fire mode. The smoke detector<br />
can also be wired to an external alarm system through TB201<br />
terminals 1 <strong>and</strong> 2. The sensor is located in the return air section.<br />
FILTER STATUS SWITCH — The units can be equipped<br />
with an optional filter status switch. The switch measures the<br />
pressure drop across the filters <strong>and</strong> closes when an adjustable<br />
pressure set point is exceeded. The sensor is located in the return<br />
air section behind the filter access door.<br />
FAN STATUS SWITCH — The units can be equipped with<br />
an optional fan status switch that will monitor the pressure rise<br />
across the indoor fans.<br />
RETURN AIR CO 2 SENSOR — The unit can be equipped<br />
with a return air IAQ CO 2 sensor that is used for the dem<strong>and</strong><br />
control ventilation. The sensor is located in the return air section<br />
<strong>and</strong> can be accessed from the filter access door.<br />
+24 V<br />
GND<br />
DCOM<br />
DI-1<br />
DI-2<br />
DI-3<br />
Terminal X1<br />
DI-4<br />
DI-5<br />
135<br />
BOARD ADDRESSES — Each board in the system has an<br />
address. The MBB has a default address of 1 but it does have<br />
an instance jumper that should be set to 1 as shown in Fig. 29.<br />
For the other boards in the system there is a 4-dip switch header<br />
on each board that should be set as shown below.<br />
BOARD SW1 SW2 SW3 SW4<br />
RXB 0 0 0 0<br />
EXB 1 0 0 0<br />
SCB 0 0 0 0<br />
CEM 0 0 0 0<br />
0 = On; 1 = Off<br />
Accessory Control Components — In addition to<br />
the factory-installed options, the units can also be equipped<br />
with several field-installed accessories that exp<strong>and</strong> the control<br />
features of the unit. The following hardware components can<br />
be used as accessories.<br />
ROOM THERMOSTATS — The ComfortLink controls<br />
support a conventional electro-mechanical or electronic thermostat<br />
that uses the Y1, Y2, W1, W2, <strong>and</strong> G signals. The<br />
control also supports an additional input for an occupied/<br />
unoccupied comm<strong>and</strong> that is available on some new thermostats.<br />
The ComfortLink controls can be configured to run with<br />
up to 6 stages of capacity. The room thermostat is connected to<br />
TB201.<br />
The ComfortLink controls also support the use of space<br />
temperature sensors <strong>and</strong> can be used with the T55 <strong>and</strong> T56<br />
sensors. The controls can also be used with CCN communicating<br />
T58 room sensor. The T55 <strong>and</strong> T56 sensors are connected<br />
to TB201 terminals 1, 2, <strong>and</strong> 3. The T58 sensor is connected to<br />
the CCN connections on COMM board. Whenever a unit<br />
equipped with heat is operated without a thermostat, the user<br />
must install the red jumpers from R to W1, <strong>and</strong> W2 on TB201<br />
for the heat function to work correctly.<br />
SPACE CO 2 SENSORS — The ComfortLink controls also<br />
support a CO 2 IAQ sensor that can be located in the space for<br />
use in dem<strong>and</strong> ventilation. The sensor must be a 4 to 20 mA<br />
sensor <strong>and</strong> should be connected to TB201 terminals 7 <strong>and</strong> 8.<br />
10 11 12 13 14 15 16 17 18 28 29 30 31 32<br />
DI-6<br />
Fig. 34 — VFD Wiring<br />
SCR<br />
B(+)<br />
A(-)<br />
AGND<br />
SCR<br />
LEN connection from ComfortLink