06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

the motor position to be configured at initial unit start-up. The<br />

motor(s) is located on the economizer <strong>and</strong> can be reached<br />

through the filter access door.<br />

THERMISTORS AND PRESSURE TRANSDUCERS —<br />

The unit is equipped with several thermistors for measurement<br />

of temperatures. The thermistors are summarized in Table 102.<br />

The units have two pressure transducers that are connected<br />

to the low side of the system. These two pressure transducers<br />

measure the low side pressure <strong>and</strong> are used for low pressure<br />

protection <strong>and</strong> coil freeze protection.<br />

The units also have two pressure transducers that are connected<br />

to the high side of the system. These two pressure transducers<br />

measure the discharge pressure <strong>and</strong> are used to cycle the<br />

condenser fans to maintain head pressure.<br />

By using the high <strong>and</strong> low side pressure transducers, the<br />

ComfortLink controls display the high <strong>and</strong> low side pressures<br />

<strong>and</strong> saturation temperatures <strong>and</strong> a normal gage set is not<br />

required.<br />

SMOKE DETECTOR — The units can be equipped with an<br />

accessory smoke detector located in the return air. The detector<br />

is wired to the ComfortLink controls <strong>and</strong>, if activated, will stop<br />

the unit by means of a special fire mode. The smoke detector<br />

can also be wired to an external alarm system through TB201<br />

terminals 1 <strong>and</strong> 2. The sensor is located in the return air section.<br />

FILTER STATUS SWITCH — The units can be equipped<br />

with an optional filter status switch. The switch measures the<br />

pressure drop across the filters <strong>and</strong> closes when an adjustable<br />

pressure set point is exceeded. The sensor is located in the return<br />

air section behind the filter access door.<br />

FAN STATUS SWITCH — The units can be equipped with<br />

an optional fan status switch that will monitor the pressure rise<br />

across the indoor fans.<br />

RETURN AIR CO 2 SENSOR — The unit can be equipped<br />

with a return air IAQ CO 2 sensor that is used for the dem<strong>and</strong><br />

control ventilation. The sensor is located in the return air section<br />

<strong>and</strong> can be accessed from the filter access door.<br />

+24 V<br />

GND<br />

DCOM<br />

DI-1<br />

DI-2<br />

DI-3<br />

Terminal X1<br />

DI-4<br />

DI-5<br />

135<br />

BOARD ADDRESSES — Each board in the system has an<br />

address. The MBB has a default address of 1 but it does have<br />

an instance jumper that should be set to 1 as shown in Fig. 29.<br />

For the other boards in the system there is a 4-dip switch header<br />

on each board that should be set as shown below.<br />

BOARD SW1 SW2 SW3 SW4<br />

RXB 0 0 0 0<br />

EXB 1 0 0 0<br />

SCB 0 0 0 0<br />

CEM 0 0 0 0<br />

0 = On; 1 = Off<br />

Accessory Control Components — In addition to<br />

the factory-installed options, the units can also be equipped<br />

with several field-installed accessories that exp<strong>and</strong> the control<br />

features of the unit. The following hardware components can<br />

be used as accessories.<br />

ROOM THERMOSTATS — The ComfortLink controls<br />

support a conventional electro-mechanical or electronic thermostat<br />

that uses the Y1, Y2, W1, W2, <strong>and</strong> G signals. The<br />

control also supports an additional input for an occupied/<br />

unoccupied comm<strong>and</strong> that is available on some new thermostats.<br />

The ComfortLink controls can be configured to run with<br />

up to 6 stages of capacity. The room thermostat is connected to<br />

TB201.<br />

The ComfortLink controls also support the use of space<br />

temperature sensors <strong>and</strong> can be used with the T55 <strong>and</strong> T56<br />

sensors. The controls can also be used with CCN communicating<br />

T58 room sensor. The T55 <strong>and</strong> T56 sensors are connected<br />

to TB201 terminals 1, 2, <strong>and</strong> 3. The T58 sensor is connected to<br />

the CCN connections on COMM board. Whenever a unit<br />

equipped with heat is operated without a thermostat, the user<br />

must install the red jumpers from R to W1, <strong>and</strong> W2 on TB201<br />

for the heat function to work correctly.<br />

SPACE CO 2 SENSORS — The ComfortLink controls also<br />

support a CO 2 IAQ sensor that can be located in the space for<br />

use in dem<strong>and</strong> ventilation. The sensor must be a 4 to 20 mA<br />

sensor <strong>and</strong> should be connected to TB201 terminals 7 <strong>and</strong> 8.<br />

10 11 12 13 14 15 16 17 18 28 29 30 31 32<br />

DI-6<br />

Fig. 34 — VFD Wiring<br />

SCR<br />

B(+)<br />

A(-)<br />

AGND<br />

SCR<br />

LEN connection from ComfortLink

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!