06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

LEGEND<br />

MLV — Minimum Load Valve<br />

VAV — Variable Air Volume<br />

VFD — Variable Frequency Drive<br />

Table 102 — Thermistors <strong>and</strong> Unit <strong>Operation</strong> Control Pressure Transducers<br />

SENSOR<br />

Thermistors<br />

DESCRIPTION AND LOCATION PART NO.<br />

CCT<br />

Cooling Coil Thermistor input. Provided with factory-option hydronic heat. Located on face of the<br />

hydronic heating coil. Consists of 4 thermistors wired into a 2x2 array.<br />

HH79NZ039 (4)<br />

LST<br />

Limit Switch Thermistor. Provided with Staged Gas Control option. Located in the heating<br />

compartment.<br />

HH79NZ034<br />

OAT Outside Air Thermistor. Located in top of the return plenum, attached to roof pole. HH79NZ039<br />

Return Air Thermistor.<br />

HH79NZ039<br />

RAT<br />

Without Economizer: Located on left side base rail in the return plenum.<br />

With Economizer: Located on left side face of return damper section in the return plenum.<br />

SAT<br />

Supply Air Thermistor. Located in the Supply Fan section, on left side of the fan housing.<br />

(May be relocated or replaced when unit is used with CCN Linkage systems; see page 63.)<br />

HH79NZ039<br />

LAT 1,2,3<br />

Leaving Air Thermistors, provided with Staged Gas Control option. Shipped in the heating<br />

compartment. Installer must pull out <strong>and</strong> mount in the supply duct.<br />

HH79NZ034 (3)<br />

Control Pressure Transducers<br />

Building Pressure. Provided with Modulating Power Exhaust, High-Capacity Power Exhaust HK05ZG018<br />

BP<br />

<strong>and</strong> Return Fan options. Located in the auxiliary control box (left-h<strong>and</strong> side of unit near return<br />

plenum).<br />

DPT-A Discharge Pressure (refrigerant), Circuit A. HK05ZZ001<br />

DPT-B Discharge Pressure (refrigerant), Circuit B. HK05ZZ001<br />

SPT-A Suction Pressure (refrigerant), Circuit A. HK05SZ003<br />

SPT-B Suction Pressure (refrigerant), Circuit B. HK05SZ003<br />

DSP<br />

Duct Static Pressure. Provided with VAV models equipped with VFD or Inlet Guide Vane options.<br />

Located in the auxiliary control box (right-h<strong>and</strong> side of unit near return plenum).<br />

HK05ZG010<br />

FT_SF<br />

Supply Air Cfm (velocity pressure). Provided with factory-option return fan system<br />

(sizes 075-100 only). Located in the supply fan compartment, on right side, on vertical post.<br />

HK05ZG015<br />

FT_RF<br />

Return Air Cfm (velocity pressure). Provided with factory-option return fan system<br />

(sizes 075-100 only). Located in auxiliary control box (right-h<strong>and</strong> side, filter access panel).<br />

HK05ZG07<br />

Outside Air CFM Outside Air Cfm Monitor (velocity pressure). Provided with the Outside Air Cfm Control option. 50ZZ400290 (030-070)<br />

Control<br />

Located in auxiliary control box (right-h<strong>and</strong> side, filter access panel).<br />

50ZZ400289 (075-100)<br />

DTT<br />

Digital Scroll Discharge Temperature Thermistor. Provided with digital scroll compressor option.<br />

Located on discharge line.<br />

HH79EZ003<br />

Circuit A Return Gas Thermistor. Provided with MLV option. Located in suction line well. HH79NZ016 (030-060)<br />

RGTA<br />

HH79NZ020 (070, 075)<br />

HH79NZ014 (090, 100)<br />

ECONOMIZER HUMIDITY CHANGEOVER SEN-<br />

SORS — The ComfortLink controls support 5 different<br />

changeover systems for the economizer. These are:<br />

• Outdoor enthalpy switch<br />

• Outdoor air dry bulb<br />

• Differential dry bulb<br />

• Outdoor air enthalpy curves<br />

• Differential enthalpy<br />

• Custom curves (a combination of an enthalpy/dewpoint<br />

curve <strong>and</strong> a dry bulb curve).<br />

The units are equipped as st<strong>and</strong>ard with an outdoor air<br />

enthalpy control. Outside air <strong>and</strong> return air dry bulb sensors<br />

which support the dry bulb changeover method are also<br />

supplied as st<strong>and</strong>ard. If the other methods are to be used, then a<br />

field-installed humidity sensor must be installed for outdoor air<br />

enthalpy <strong>and</strong> customer curve control <strong>and</strong> two humidity sensors<br />

must be installed for differential enthalpy. Installation holes are<br />

pre-drilled <strong>and</strong> wire harnesses are installed in every unit for<br />

connection of the humidity sensors. The ComfortLink controls<br />

have the capability to convert the measured humidity <strong>and</strong><br />

dry bulb temperature into enthalpy.<br />

ACCESSORY NAVIGATOR DISPLAY — The accessory<br />

h<strong>and</strong>held Navigator display can be used with the 48/50P<br />

Series units. See Fig. 35. The Navigator display operates the<br />

same way as the scrolling marquee device. The RXB <strong>and</strong> EXB<br />

boards contain a second LEN port than can be used with the<br />

h<strong>and</strong>held Navigator display.<br />

136<br />

CONTROL MODULE COMMUNICATIONS<br />

Red LED — Proper operation of the control boards can be<br />

visually checked by looking at the red status LEDs as shown<br />

on Fig. 29-33. When operating correctly, the red status LEDs<br />

should blink in unison at a rate of once every 2 seconds. If the<br />

red LEDs are not blinking in unison, verify that correct power<br />

is being supplied to all modules. Also, be sure that the main<br />

base board is supplied with the current software <strong>and</strong> that all<br />

boards are configured on. If necessary, reload current software.<br />

If the problem still persists, a board may need to be replaced. A<br />

board LED that is lit continuously or blinking at a rate of once<br />

per second or faster indicates that the board should be replaced.<br />

Green LED — The boards also have a green LED, which is<br />

the indicator of the operation of the LEN communications,<br />

which is used for communications between the boards. On the<br />

MBB board the local equipment network (LEN) LED should<br />

always be blinking whenever power is on. All other boards<br />

have a LEN LED that will blink whenever power is on <strong>and</strong><br />

there is communication occurring. If LEN LED is not blinking,<br />

check LEN connections for potential communication errors (J3<br />

<strong>and</strong> J4 connectors). A 3-wire sensor bus accomplishes communication<br />

between modules. These 3 wires run in parallel from<br />

module to module.<br />

Yellow LED — The MBB has one yellow LED. The Carrier<br />

Comfort Network ® (CCN) LED will blink during times of<br />

network communication. The other boards do not have a CCN<br />

communications port.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!