Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
System Mode Test — When the system mode is Test, the<br />
control is limited to the Test mode <strong>and</strong> is controllable via the<br />
local displays (scrolling marquee <strong>and</strong> Navigator display).<br />
The System Test modes are Factory Test Enabled <strong>and</strong> <strong>Service</strong><br />
Test Enabled. See the <strong>Service</strong> Test section on page 35 for details<br />
on test control in this mode.<br />
1. Factory Test mode (“Factory test enabled”)<br />
2. <strong>Service</strong> Test mode (“<strong>Service</strong> test enabled”)<br />
System Mode Run — When the system mode is Run, the software<br />
application in the control is free to run the HVAC control<br />
routines by which cooling, heating, IAQ, etc., is possible.<br />
There are two possible text displays for this mode, one is<br />
normal run mode <strong>and</strong> the other occurs if one of the following<br />
fire-smoke modes is present: smoke purge, pressurization or<br />
evacuation.<br />
1. Normal run time state (“Unit <strong>Operation</strong> Enabled”)<br />
2. Fire-Smoke control mode (“Fire-Smoke Control”)<br />
HVAC MODES (Operating ModeHVAC) — The HVAC<br />
mode is dependant on the system mode to allow it to further<br />
determine the operational state of the rooftop unit. The actual<br />
determination of an HVAC mode is based on a hierarchal<br />
decision making process whereby certain overrides may interfere<br />
with normal temperature/humidity control. The decision<br />
making process that determines the HVAC mode is shown in<br />
Fig. 4 <strong>and</strong> Appendix E.<br />
Each HVAC mode is described below. The HVAC mode<br />
number is shown in the parenthesis after the mode.<br />
HVAC Mode — STARTING UP (0) — The unit is transitioning<br />
from the OFF mode to a different mode.<br />
HVAC Mode — DISABLED (1) — The unit is shut down<br />
due to a comm<strong>and</strong> software disable through the scrolling marquee,<br />
a CCN emergency stop comm<strong>and</strong>, a service test end, or a<br />
control-type change delay.<br />
HVAC Mode — SHUTTING DOWN (2) — The unit is transitioning<br />
from a mode to the OFF mode.<br />
HVAC Mode — SOFTSTOP REQUEST (3) — The unit is<br />
off due to a soft stop request from the control.<br />
HVAC Mode — REM SW.DISABLE (4) — The unit is off<br />
due to the remote switch.<br />
HVAC Mode — FAN STATUS FAIL (5) — The unit is off<br />
due to a supply fan status failure.<br />
HVAC Mode — STATIC PRESSURE FAIL (6) — The unit<br />
is off due to failure of the static pressure sensor.<br />
HVAC Mode — COMP.STUCK ON (7) — The unit is shutdown<br />
because there is an indication that a compressor is running<br />
even though it has been comm<strong>and</strong>ed off.<br />
HVAC Mode — OFF (8) — The unit is off <strong>and</strong> no operating<br />
modes are active.<br />
HVAC Mode — TEST (9) — The unit is in the self test mode<br />
which is entered through the <strong>Service</strong> Test menu.<br />
HVAC Mode — TEMPERING VENT (10) — The economizer<br />
is at minimum vent position but the supply-air temperature<br />
has dropped below the tempering vent set point. Staged<br />
gas heat or hydronic heat is used to temper the ventilation air.<br />
HVAC Mode — TEMPERING LOCOOL (11) — The economizer<br />
is at minimum vent position but the combination of the<br />
outside-air temperature <strong>and</strong> the economizer position has<br />
dropped the supply-air temperature below the tempering cool<br />
set point. Staged gas heat or hydronic heat is used to temper the<br />
ventilation air.<br />
HVAC Mode — TEMPERING HICOOL (12) — The economizer<br />
is at minimum vent position but the combination of the<br />
outside-air temperature <strong>and</strong> the economizer position has<br />
dropped the supply-air temperature below the tempering cool<br />
set point. Staged gas heat or hydronic heat is used to temper the<br />
ventilation air.<br />
41<br />
HVAC Mode — VENT (13) — This is a normal operation<br />
mode where no heating or cooling is required <strong>and</strong> outside air is<br />
being delivered to the space to control IAQ levels.<br />
HVAC Mode — LOW COOL (14) — This is a normal cooling<br />
mode where a low cooling dem<strong>and</strong> is present.<br />
HVAC Mode — HIGH COOL (15) — This is a normal cooling<br />
mode where a high cooling dem<strong>and</strong> is present.<br />
HVAC Mode — LOW HEAT (16) — The unit will be in low<br />
heating dem<strong>and</strong> mode using either gas, electric, or hydronic<br />
heat.<br />
HVAC Mode — HIGH HEAT (17) — The unit will be in<br />
high heating dem<strong>and</strong> mode using gas, electric, or hydronic<br />
heat.<br />
HVAC Mode — UNOCC. FREE COOL (18) — In this<br />
mode the unit will operate in cooling but will be using the<br />
economizer for free cooling. Entering this mode will depend on<br />
the status of the outside air. The unit can be configured for outside<br />
air dry bulb changeover, differential dry bulb changeover,<br />
outside air enthalpy changeover, differential enthalpy changeover,<br />
or a custom arrangement of enthalpy/dew point <strong>and</strong> dry<br />
bulb. See the Economizer section for further details.<br />
HVAC Mode — FIRE SHUT DOWN (19) — The unit has<br />
been stopped due to a fire shutdown input (FSD) from two or<br />
more of the fire control modes, purge, evacuation, or pressurization.<br />
HVAC Mode — PRESSURIZATION (20) — The unit is in<br />
the special fire pressurization mode where the supply fan is on,<br />
the economizer damper is open <strong>and</strong> the power exhaust fans are<br />
off. This mode is invoked by the Fire Pressurization (PRES) input<br />
which can be found in the INPUTFIRE submenu.<br />
HVAC Mode — EVACUATION (21) — The unit is in the<br />
special Fire Evacuation mode where the supply fan is off, the<br />
economizer damper is closed <strong>and</strong> the power exhaust fans are<br />
on. This mode is invoked by the Fire Evacuation (EVAC) input<br />
which can be found in the INPUTFIRE submenu.<br />
HVAC Mode — SMOKE PURGE (22) — The unit is in the<br />
special Fire Purge mode where the supply fan is on, the economizer<br />
damper is open <strong>and</strong> the power exhaust fans are on. This<br />
mode is invoked by the Fire Evacuation (PURG) input which<br />
can be found in the INPUTFIRE submenu.<br />
HVAC Mode — DEHUMIDIFICATION (23) — The unit is<br />
operating in the Dehumidification mode. On units configured<br />
for Humidi-MiZer ® operation, this is the Humidi-MiZer dehumidification<br />
mode (subcooling).<br />
HVAC Mode — RE-HEAT (24) — The unit is operating in<br />
Reheat mode. On units configured for Humidi-MiZer operation,<br />
this is the Humidi-MiZer reheat mode.<br />
HVAC Mode — FREEZESTAT TRIP (25) — If the freezestat<br />
trips, the unit enters the Freezestat Trip HVAC mode. The<br />
supply fan will run, the hydronic heat valve will be wide open,<br />
<strong>and</strong> the economizer damper will be closed.<br />
HVAC Mode — PLEN.PRESS.FAIL (26) — The unit is off<br />
due to a failure of the plenum pressure switch.<br />
HVAC Mode — RCB COMM FAILURE (27) — The unit is<br />
off due to a Rooftop Control Board (RCB) communication failure.<br />
HVAC Mode — SUPPLY VFD FAULT (28) — The unit is<br />
off due to a supply fan VFD fault or supply fan VFD communications<br />
loss.<br />
Unit Configuration Submenu — The UNIT submenu<br />
under the Configuration mode of the local display<br />
contains general unit configuration items. This section will<br />
define all of these configurations here for easy reference. The<br />
sub-menu which contains these configurations is located at the<br />
local display under ConfigurationUNIT. See Table 31.